Laserfiche WebLink
1.MATERIAL USED FOR THE SIGNAGE SHALL BE REFLECTIVE, WEATHER RESISTANT <br />AND SUITABLE FOR THE ENVIRONMENT. <br />2. ALL SIGNAGE SHALL HAVE ALL CAPITAL LETTERS WITH MINIMUM <br />38" LETTER HEIGHT, <br />WHITE ON RED BACKGROUND. <br />3. MAIN SERVICE DISCONNECT MARKING SHALL BE PLACED ADJACENT TO MAIN <br />SERVICE DISCONNECT IN A LOCATION CLEARLY VISIBLE FROM THE LOCATION <br />WHERE THE LEVER IS OPERATED. <br />4. MARKING IS REQUIRED ON ALL INTERIOR AND EXTERIOR DC CONDUIT, RACEWAYS, <br />ENCLOSURES, CABLE ASSEMBLIES, AND JUNCTION BOXES TO ALERT THE FIRE <br />SERVICE TO AVOID CUTTING THEM. MARKINGS SHALL BE PLACED EVERY 10', AT <br />TURNS AND ABOVE AND/OR BELOW PENETRATIONS, AND AT ALL DC COMBINER <br />AND JUNCTION BOXES. <br />5. DO NOT USE SCREWS FOR SIGNAGE ATTACHMENT. USE ONLY APPROVED ADHESIVE. <br />SIGNAGE NOTES <br />RAPID SHUTDOWN SWITCH FOR <br />SOLAR PV SYSTEM <br />x <br />x <br />AMPS <br />VOLTS <br />PHOTOVOLTAIC POINT OF <br />INTERCONNECTION <br />WARNING: ELECTIC SHOCK HAZARD. DO NOT <br />TOUCH TERMINALS. TERMINALS ON BOTH THE <br />LINE AND LOAD SIDE MAY BE ENERGIZED <br />IN THE OPEN POSITION. FOR SERVICE <br />DE-ENERGIZE BOTH SOURCE AND MAIN BREAKER <br />PV POWER SOURCE <br />x <br />x <br />MAXIMUM RATED AC OUTPUT CURRENT: <br />MAXIMUM OPERATING AC VOLTAGE: <br />12.80 <br />240 <br />x <br />x <br />x <br />x <br />SOLAR PV SYSTEM EQUIPPED WITH <br />RAPID SHUTDOWN <br />TURN RAPID SHUTDOWN <br />SWITCH TO THE "OFF" <br />POSITION TO SHUTDOWN <br />PV SYSTEM AND REDUCE <br />SHOCK HAZARD <br />IN THE ARRAY <br />WARNING <br />POWER SOURCE OUTPUT CONNECTION <br />DO NOT RELOCATE <br />THIS OVERCURRENT DEVICE <br />CONICAL FLASHING <br />CYLINDRICAL FLASHINGCONDUIT ENTRY / EXIT DETAIL <br />PULLBOX MOUNTING - FLAT ROOF <br />FIGURE 2: WIRING ROOF PENETRATION CROSS SECTION <br />DRAWN BY <br />PROJECT NO. <br />DATE DRAWN <br />COMMUNITY ID C024242 <br />RP-486700 <br />2024-05-27 <br />ADRIELLE LATADE717 LYONTRACT/SUBDIVISION #: 19195TOLL BROTHERS - SOCAL OC SAN DIEGO350 COMMERCE ST., SUITE 200 583 SOUTH LYON STREETSANTA ANA, CALIFORNIA 92701IRVINE, CA 92602CH I FU N G LEU <br />NGE <br />LECT R IC ALE22659 <br />Exp. 03-31-25REGISTEREDPROFESSIONAL <br />E <br />NGI <br />NEERS <br />TATEOF CA L IF O RNIA880 H A R B O U R W A Y S O U T HS U I T E 6 0 0C O R P O R A T I O N , S Y S T E M STHIS DOCUMENT CONTAINS PROPRIETARY INFORMATION. REPRODUCTION,DISCLOSURE, OR USE WITHOUT SPECIFIC WRITTEN AUTHORIZATION OFSUNPOWER CORPORATION IS STRICTLY FORBIDDEN.®R I C H M O N D , C A 9 4 8 0 4( 5 1 0 ) 5 4 0 - 0 5 5 0C A L I C E N S E # 8 9 0 8 9 5N <br />FIGURE 1: ELECTRICAL SIGNAGES/STICKERS FIGURE 3: PLACARD IDENTIFYING LOCATION OF DISCONNECTS AND POWER SOURCES <br />ELECTRICAL DETAILS AND PLACARDDRIVEWAY <br />SHEET <br />REV DESCRIPTION DATE CB <br />PVE-3 <br />SUB PANEL <br />PHOTOVOLTAICARRAY ON ROOF <br />MAIN SERVICEPANEL <br />POWER TO THIS BUILDING IS ALSO <br />SUPPLIED FROM THE FOLLOWING <br />SOURCES WITH DISCONNECTS <br />LOCATED AS SHOWN: <br />CAUTION: <br />583 SOUTH LYON STREET <br />583 S Lyon <br />St-101119877 & <br />201832657/9/2024