G N <br />(N) 20A/2P <br />(N) 20A/2P <br />NO <br />2 <br />NO <br />1 <br />ESS HOLD DOWN KIT <br />EATON SKU <br />BRHDK125 PER NEC 710.15 <br />ENCHARGE BREAKER <br />G <br />NC <br />2 <br />NC <br />1 <br />WIRED <br />COMMS <br />NC <br />3 <br />(N) IQ SYSTEM <br />CONTROLLER 3/3G <br />SC200D111C24OUS01 <br />DPST <br />ENPHASE SYSTEM <br />SHUTDOWN SWITCH <br />(N) 100A/2P <br />40A/2P <br />AC COMBINER <br />BREAKER <br />ENCHARGE <br />BREAKER 3A <br />(N) AC DISCONNECT 2: <br />VISIBLE,LOCKABLE AND <br />LABELED SQUARE D <br />DTU223RB 100A NON-FUSIBLE <br />240VAC NEMA-3R, UL LISTED <br />OR EQUIVALENT <br />L1 <br />L2 <br />N <br />G <br />L1 <br />L2 <br />N <br />G <br />GG <br />IQBATTERY-5P-1P-NA <br />(6)IQ8D-BAT <br />L1 <br />L2 <br />4 <br />N <br />G <br />(N) BACKUP LOAD PANEL <br />125A RATED,240V <br />3 <br />NOTE: <br />ESSENTIAL LOADS OF <br />EXISTING SERVICE PANEL <br />& THEIR RESPECTIVE <br />BREAKERS <br />NEEDS TO BE MOVED TO <br />BACKUP ELECTRICAL <br />PANEL BEFORE PV <br />INSTALLATION. <br />N <br />GEC <br />M <br />(N) 175A/2P <br />EXISTING GROUNDING <br />ELECTRODE SYSTEM <br />TO EARTH <br />REF.NEC 250.52, <br />250.53(A) <br />(N) MAIN BREAKER TO <br />HOUSE 240 V, 175A/2P <br />G <br />2 <br />5 <br />(N) DEDICATED PHOTOVOLTAIC <br /> SYSTEM ENPHASE IQ COMBINER 5/5C <br />X-IQ-AM1-240-5/5C NEMA 3R, UL <br /> LISTED,125A RATED <br />TO UTILITY GRID <br />(E) BI-DIRECTIONAL UTILITY <br />METER 1-PHASE, 3-W, <br />120V/240V <br />L2 <br />L1 <br />N <br />ENVOY BREAKER <br />20A/2P <br />AUTO <br />TRANSFORMER <br />(N) METER MAIN COMBO <br />225A RATED, 240V <br />G <br />N <br />G <br />ENVOY IQ <br />(REVENUE GRADE METER) <br />1 <br />(N) JUNCTION BOX <br />ROOFTOP <br />600 V, NEMA 3-R <br />UL LISTED <br />L1 <br />L2 <br />G <br />(N) AC DISCONNECT 3: <br />VISIBLE,LOCKABLE AND <br />LABELED SQUARE D <br />DU221RB 30A NON-FUSIBLE <br />240VAC NEMA-3R, UL LISTED <br />OR EQUIVALENT <br />4 <br />L2 <br />L1 <br />L2 <br />20A/2P <br />8 MICROINVERTERS IN BRANCH CIRCUIT 1 <br />(8) -APTOS SOLAR DNA-120-MF10-440W (440W) SOLAR MODULES <br />8 - ENPHASE ENERGY INC. IQ8PLUS-72-M-US [240V] <br />MICROINVERTERS (240V) - MOUNTED UNDER <br />EACH PANEL (690.14(D)) <br />INTEGRATED GROUNDING WIRE <br />A <br />3 <br />(N) AC DISCONNECT 1: <br />VISIBLE,LOCKABLE AND <br />LABELED SQUARE D <br />DTU223RB 100A NON-FUSIBLE <br />240VAC NEMA-3R, UL LISTED <br />OR EQUIVALENT <br />L1 <br />L2 <br />N <br />G <br />L1 <br />L2 <br />N <br />G <br />(N)PV <br />100A/2P <br />3 <br />(N) TRENCHING ~16 <br />N <br />G <br />(E) 90A/2P <br />(E) SUB SERVICE PANEL <br />100A RATED,240V <br />EXISTING WIRES <br />SPD SURGE PROTECTING <br />DEVICE TYPE 1 <br />33 <br />0 <br /> CA <br />R <br />R <br />I <br />A <br />G <br />E <br /> <br />D <br />R <br />, <br />#D <br /> <br />S <br />A <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br />CA <br /> 92 <br />7 <br />0 <br />7 <br />, <br />U <br />S <br />A <br />AN <br />K <br />I <br />T <br /> <br />M <br />A <br />H <br />A <br />J <br />A <br />N <br />REVDATEDESCRIPTION <br />REVISIONS <br />HOMEOWNER INFO <br />AP <br />N <br />: <br /> <br />93 <br />3 <br />1 <br />7 <br />0 <br />1 <br />5 <br />SHEET NAME <br />SHEET SIZE <br />SHEET NUMBER <br />ANSI B <br />11" X 17" <br />PV-4 <br />SIGNATURE & SEAL <br />CONTRACTOR: MY SMART HOUSE <br />ADDRESS: 39809 AVENIDA ACACIAS, UNIT D <br />MURRIETA, CA 92563 <br />PHONE:8884453020 <br />LICENSE #: C-10 1095569 <br />JOSE EMILIO BAHENA <br />ELECTRICAL LINE <br />CALCS. <br />ELECTRICAL THREE LINE DIAGRAM <br />SCALE: NTS <br />CALCS. <br />ENERGY STORAGE SYSTEMS (ESS) SHALL NOT <br />BELOCATED LESS THAN 3 FEET FROM DOORS AND <br />WINDOWSDIRECTLY ENTERING THE DWELLING UNIT <br />PER 2022CALIFORNIA RESIDENTIAL CODE R328.4 <br />EXTREME CASE MODULE OUTPUT <br />(APTOS SOLAR DNA-120-MF10-440W (440W) SOLAR MODULES) <br />Isc(25°C) = 13.73A, Tisc = 0.054%/°C <br />Isc(T) = Isc(25°C) x [1 + (0.054/100) x (T-25°C)] <br />Isc(-2°C) = 13.53A, Isc(31°C) = 13.77A <br />Voc(25°C) = 41.02V, Tvoc = -0.27%/°C <br />Voc(T) = Voc(25°C) x [1 + (-0.27/100) x (T-25°C)] <br />Voc(-2°C) = 44.01V, Voc(31°C) = 40.36V <br />SYSTEM SUMMARY STC (3.520 kW DC / 2.320 kW AC) <br />STC DC:(8) 440W = 3.520 kW <br />STC AC:(8) 290W = 2.320 kW <br />STORAGE :(1) 5.0kWh = 5.00kWh <br />● (8) - APTOS SOLAR DNA-120-MF10-440W (440W) SOLAR MODULES <br />● (8)- ENPHASE ENERGY INC. IQ8PLUS-72-M-US [240V] MICROINVERTERS <br />● (1) - ENPHASE ENERGY INC. IQBATTERY-5P-1P-NA <br />ELECTRICAL NOTES <br />1) ALL GROUNDING TO COMPLY WITH CEC 690.47. <br />2) ALL TERMINALS SHALL BE MIN. 75°C RATED. <br />3) IQ GATEWAY BREAKER DETERMINED AT FACTORY BY MANUFACTURER (10A or 15A). <br />4) FOR IQ GATEWAY: USE SINGLE CT FOR PV PRODUCTION (L1 FROM ALL PV BRANCH CIRCUITS). USE SINGLE CT FOR <br />BATTERIES (L2 FROM ALL BATTERY BRANCHES LANDING IN SYSTEM CONTROLLER). USE DOUBLE CTs FOR CONSUMPTION <br />(L1 AND L2 FEEDING MSP MAIN BREAKER, SERVICE SIDE). <br />5) IQ COMBINER 5/5C REQUIRES ENPHASE HOLD DOWN KIT X-IQ-NA-HD-125A. <br />6) WHEN IQ SYSTEM CONTROLLER 3 NOT AT SERVICE ENTRANCE, REMOVE N-G JUMPER WIRE FROM CONTROLLER. <br />7) SINGLE LARGEST BREAKER, BASELINE LOAD, AND LRA OF LARGEST LOAD IN BACKUP LOAD PANEL CANNOT EXCEED <br />STORAGE (ESS) OUTPUT CAPACITY, PER CEC 710.15. <br />8) IQ SYSTEM CONTROLLER 3 MAIN INPUT & OUTPUT LUGS RATED FOR #6-300 KCMIL, FOR WIRES SMALLER THAN #6 REMOVE <br />LUG AND USE AN APPROVED UL RING TERMINAL. <br />9) IQ SYSTEM CONTROLLER 3 COMES WITH FACTORY-INSTALLED HOLD DOWN KIT ARM, ADDITIONAL KIT NOT REQUIRED. <br />DIG ALERT (811) IS TO BE CONTACTED AND COMPLIANCE WITH <br />EXCAVATION SAFETY IN ACCORDING WITH GOVERNMENT CODE 4216 <br />WILL BE FOLLOWED, PRIOR TO ANY EXCAVATION TAKING PLACE. <br />NOTE: SPLICING OF THE WIRE-TYPE GROUNDING ELECTRODE SHALL BE <br />PERMITTED ONLY BY IRREVERSIBLE COMPRESSION-TYPE CONNECTORS LISTED <br />AS GROUNDING AND BONDING EQUIPMENT OR BY THE EXOTHERMIC WELDING <br />METAL WATER PIPING SYSTEM INSTALLED IN OR ATTACHED TO A BUILDING OR <br />STRUCTURE SHALL BE BONDED PER NEC TABLE 250.66 AND 250.104(A)(1). <br />•NEW ELECTRICAL SHALL BE LOCATED AT LEAST THREE (3) FEET FROM <br />GAS METER OR GAS SHUT- OFF VALVES. UPC1208.7.1; NEC 110.26.” <br />•GROUNDING ELECTRODE CONDUCTOR SHALL BE SIZED PER NEC 250.66. <br />AC wire details <br /> Tag Line Neutral Ground Min EMT/PVC <br />1 <br />12 AWG (Q-Cable)06 AWG BARE <br />(NOT IN CONDUIT) <br />2 <br />10 AWG THWN-2 <br />10 AWG THWN-2 <br />(2) 10 AWG THWN-2 <br />(2) 10 AWG THWN-2 <br />- <br />- <br />-A <br />3/4 in EMT <br />3/4 in EMT <br />10 AWG THWN-2 <br />3 8 AWG THWN-2(2) 3 AWG THWN-2 3 AWG THWN-2 <br />4 <br />1-1/4 in EMT <br />(2) 10 AWG THWN-2 3/4 in EMT- <br />INTERCONNECTION <br />120% RULE - NEC 705.12(B)(3)(2) <br />UTILITY FEED + SOLAR BACKFEED <br />175A + 90A = 265A <br />BUSS RATING x 120% <br />225A x 120% = 270A <br />●1X BRANCH OF 8 CONNECTED IN PARALLEL <br />10 AWG THWN-2 <br />3A 1-1/4 IN SCH 40 <br /> PVC8 AWG THWN-2(2) 3 AWG THWN-2 3 AWG THWN-2 <br />(2) 10 AWG THWN-2 3/4 in EMT10 AWG THWN-25 - <br />330 W Carriage Dr Unit <br />#D3/21/2025