Project Number: 224730-1 <br />Project Location: Santa Ana, CA 92704 <br />AMERICANA OUTDOORS <br />STRUCTURAL CALCULATIONS <br />Page 9 of 25 <br />6/10/2025 <br />LOAD COMBINATIONS <br />Dead Load:D = 5 psfLive Load:L = 0 psfRoof Live Load: Lr = 20 psfDesign Use Snow Load: SU = 0 psfSnow Load + Drift Case A: SA = #N/A psfSnow Load + Drift Case B: SB = #N/A psfRain Load:R = 5 psfWind Load Case A: WA = 25.5 psfWind Load Case B: WB = -22.5 psfEarthquake Load:E = 0 psf (By inspection, seismic does not controland is therefore excluded.)Maximum Load Combination ("inward"):Σmax = D + .75 L + .75 (.6 W) + .75 Lr =31.5 psf (BLC #6a) <br />Minimum Load Combination ("outward"):Σmin = .6 D + .6 W =-10.5 psf (BLC #7) <br />Determine maximum "inward" and "outward" pressures on roof decking using Allowable Stress Design per ASCE 7,section 2.4.1. Wind pressure values shall be taken as determined in Components & Cladding. For those structures where snow drift loads are required, see Exception 1 in the referenced code. In combinations 4 and 6, Snow Load shall be takenas the design snow load pu and shall exclude drift surcharge load. In combination 3, Snow Load shall be taken as the totalsnow load including drift surcharge. <br />Page 11 of 111