Laserfiche WebLink
ROOF SLOPE 910106217PV-3D52011121413151822S-5D431542524238262SHEETCONTRACTORSOLGEN CONSTRUCTION LLC. 1218 S MOHAWK DR, SANTA ANA, CA 92704 APN:10957103 DATE:9/7/2023GONZALEZRESIDENCELicense#: C-10 1053344DESIGNER: OSDCORE ENERGY GROUP.ADDRESS: 2072 N MAIN STFL 2, LOGANUT 84341-1993CSLB#: 1053344D4DETAIL (TRANSVERSE)NOT TO SCALED5DETAIL (LONGITUDINAL)NOT TO SCALED1RACKING DETAIL (TRANSVERSE)NOT TO SCALED3RACKING DETAIL (TOP)NOT TO SCALED2RACKING DETAIL (LONGITUDINAL)NOT TO SCALE1. ROOF MATERIAL: COMP SHINGLE2. ROOF STRUCTURE: TRUSSES3. ATTACHMENT TYPE: UNIRAC FLASHLOC4. MODULE MANUFACTURER: JA SOLAR5. MODULE MODEL: JAM54S31-395/MR/(395W)6. MODULE LENGTH: 67.79''7. MODULE WIDTH: 44.64"8. MODULE WEIGHT: 42.99 LBS.9. SEE SHEET S-1 FOR DIMENSION(S)10. MIN. FIRE OFFSET: 18"11. TRUSSES SPACING: 24" O.C.12. TRUSSES SIZE: 2 "X 4" NOMINAL13. LAG BOLT DIAMETER: 5/16 IN.14. LAG BOLT EMBEDMENT: 2.5 IN.15. TOTAL # OF ATTACHMENTS: 3016. TOTAL AREA: 231.16 SQ. FT.17. TOTAL WEIGHT: 472.89 LBS.18. WEIGHT PER ATTACHMENT: 15.76 LBS.19. DISTRIBUTED LOAD: 2.05 PSF20. MAX. HORIZONTAL STANDOFF: 72 IN.21. MAX. VERTICAL STANDOFF:LANDSCAPE: 26 IN., PORTRAIT: 43 IN.22. STANDOFF STAGGERING: YES23. RAIL MANUFACTURER AND MODEL(OR EQUIV.):EVEREST CROSSRAIL24. RAIL WEIGHT: 0.436 PLF.25. MAX. TRUSSES SPAN: 12 FT.26. MODULE CLEARANCE: 3 IN. MIN., 6 IN. MAX.PV-3Signed: 07/31/20231218 S Mohawk Dr -2018104310/3/2023