Laserfiche WebLink
Service Voltage <br />240 <br />Section 220.83 Existing Dwelling Unit <br />Part #1 - Section 220.83 (B)(1) General Lighting/Receptacles @ 3 VA per sq ft: <br />Amps Box A (VA) <br />19.1 4584 <br />Part #2 - Section 220.83(B)(2), (3)a, b, c, d - Appliances and Dedicated Circuits: <br />Size in VA Size in VA <br />1500 <br />1500 <br />1500 <br />1000 <br />600 <br />1000 <br />1600 <br />5760 <br />Amps Box B (VA) <br />60.25 14460 <br />Total VA from Parts #1 and #2 combined:Box A + Box B =19044 <br />Total VA 19044 <br />First 8000 VA @ 100%8000 Remaining VA @ 40% <br />Remaining VA =11044 11044 x 40% =4417.6 VA <br />Adding First 8000 VA, if possible 8000 VA <br />Total VA for Gen. Lights/Recep, Appliances & Dedicated circuits:12417.6 VA <br />Total AMP for Gen. Lights/Recep, Appliances & Dedicated circuits:51.74 Amps <br />Part #3 - Section 220.83(B) Heating and A/C loads: <br />*Combine the larger loads of either the Heating or the A/C loads togther <br />100% of all the Heating or A/C loads in VA:0 VA <br />100% of all the Heating or A/C loads in Amps:0.00 A <br />VA Volts Amps <br />Parts #1 & #2 12417.6 240 51.74 <br />Part #3 0 240 0.00 <br />Total VA for all Parts:12,418 <br />Totals Service/Feeder Load 51.74 <br />Microwave <br />EV Charger <br />Totals for Part #2: <br />Totals from all Parts <br />Dishwasher <br />Disposal <br />Refrigerator <br />Laundry <br />Appliance Circuit - 1 <br />Appliance Circuit - 2 <br />Dedicated circuit Dedicated circuit <br />Article 220 - Dedicated Backup Panel Calculation Job Code <br />1414 S Shelton St Santa Ana CA USA 92707 109R-414SER1 <br />Building Square Footage VA (watts)Amps <br />House 1528.00 4584 19.10 <br />Total for Part #1: <br />1414 S Shelton St <br />12/2/2024