Laserfiche WebLink
GENERAL ELECTRICAL NOTES MODULE CHARACTERISTICS <br />OPTIMIZER CHARACTERISTICS <br />STATION CHARACTERISTICS <br />MAX TEMP [°C]: 38 <br />MIN TEMP [°C]: -2 <br />SINGLE LINE DIAGRAM LEGEND <br />CURRENT TRANSFORMER <br />(DOT INDICATES DIRECTION) <br />METER <br />CIRCUIT BREAKER <br />SWITCH <br />PV MODULE <br />FUSE <br />INVERTER~-- <br />M <br />CELLULAR ANTENNA <br />DC COMBINER <br />TRANSFORMER <br />BATTERY MODULE <br />A <br />B TRANSFER SWITCH (ATS/ MTS) <br />JUNCTION BOX <br />+ - <br />INTERCONNECTION NOTES <br />INTERCONNECTION NOTES <br />·SUPPLY SIDE INTERCONNECTIONS SHALL COMPLY WITH ART. 705.11 AND ART 230 FOR THE <br />INSTALLATION OF AN ADDITIONAL SERVICE ENTRANCE <br />·THE OVERCURRENT PROTECTION DEVICE ON THE SUPPLY SIDE OF THE SERVICE <br />DISCONNECTING MEANS SHALL BE WITHIN 10 FEET OF THE INTERCONNECTION POINT UNLESS <br />CABLE LIMITERS OR CURRENT-LIMITED CIRCUIT BREAKERS ARE INSTALLED ON EACH <br />UNGROUNDED CONDUCTOR AT THE POINT OF INTERCONNECTION PER ART. 705.11(C). THIS <br />OVERCURRENT DEVICE MUST BE SIZED FOR THE SHORT-CIRCUIT CURRENT SUPPLIED FROM THE <br />PRIMARY SOURCE(S) OF ELECTRICITY. <br />·SUPPLY SIDE INTERCONNECTIONS SHALL BE MADE IN ACCORDANCE WITH THE EQUIPMENT <br />MANUFACTURER'S INSTRUCTIONS AND SHALL NOT INVALIDATE THE NRTL LISTING OF THE <br />EQUIPMENT. <br />·RMC OR SCH 80 PVC TYPE CONDUIT SHALL BE USED TO ENCLOSE NEW SERVICE CONDUCTORS <br />USED FOR A SUPPLY SIDE INTERCONNECTION. <br />·NEW SERVICE CONDUCTORS USED FOR SUPPLY SIDE INTERCONNECTIONS SHALL BE INSTALLED <br />IN A SEPARATE RACEWAY FROM ANY LOAD SIDE CONDUCTORS WITHIN THE MAIN SWITCHBOARD <br />PER NEC 230.7. <br />GENERAL NOTES <br />·ALL ELECTRICAL WORK SHALL COMPLY WITH THE NEC 2020 CODE AS AMENDED BY <br />APPLICABLE STATE AND LOCAL CODES. <br />·EACH UNGROUNDED CONDUCTOR OF THE MULTIWIRE BRANCH CIRCUIT WILL BE IDENTIFIED <br />BY PHASE AND SYSTEM PER ART 210.5. <br />·BRANCH CIRCUITS SUPPLIED FROM DC SYSTEMS MUST BE IDENTIFIED IN COMPLIANCE WITH <br />ART. 210.5(C)(2) WHERE DC POSITIVE (+) IS RED/ RED-STRIPED AND DC NEGATIVE (-) IS <br />BLACK/BLACK-STRIPED. <br />·ALL EQUIPMENT SHALL BE LISTED BY A NRTL IN COMPLIANCE WITH ART 110.3. <br />·DC CONDUCTORS INSIDE BUILDING SHALL BE IN METALLIC RACEWAY PER ART 690.31(D). <br />·ALL WIRES SHALL BE PROVIDED WITH STRAIN RELIEF AT ALL ENTRY INTO BOXES AS <br />REQUIRED BY NRTL LISTING. <br />·PARALLEL CONDUCTORS SHALL BE INSTALLED PER ART 310.10(G). <br />·ALL VALUES FOR Imp, Isc AND Vmp ARE PER MANUFACTURER'S LISTED DATA AT STC. MAXIMUM <br />VOLTAGE CALCULATED IN ACCORDANCE WITH ARTICLE NEC 690.7. <br />·REFER TO CURRENT MANUFACTURER'S PLANNING AND INSTALLATION MANUAL FOR <br />TORQUE SPECS FOR ALL BOLTS AND TERMINAL CONNECTIONS. <br />·BRANCH CIRCUITS RUN IN OUTDOOR ROOFTOP AMBIENT CONDITIONS SHALL BE INSTALLED <br />> 7/8 INCH ABOVE ROOF SURFACE. <br />·ALL PV CIRCUITS LOCATED OUTSIDE THE ARRAY BOUNDARY OR MORE THAN 3 FT FROM THE <br />POINT OF ENTRY INSIDE A BUILDING SHALL BE LIMITED TO NOT MORE THAN 30 VOLTS <br />WITHIN 30 SECONDS, CIRCUITS INSIDE THE ARRAY BOUNDARY OR NOT MORE THAN 3 FT <br />FROM THE POINT OF PENETRATION SHALL BE LIMITED TO NOT MORE THAN 80 VOLTS UPON <br />RAPID SHUT-DOWN INITIATION PER 690.12. <br />·PV SYSTEM SHALL CONTAIN OR INTERACT WITH DEVICES CAPABLE OF DETECTING AND <br />INTERRUPTING ARCING FAULTS WITHIN THE SYSTEM PER 690.11. <br />·BURIED CONDUCTORS SHALL BE BURIED TO THE MINIMUM DEPTH SPECIFIED IN ART. 300.5 <br />FOR CIRCUITS 1000V AND UNDER AND ART. 300.50 FOR CIRCUITS ABOVE 1000V. <br />·SPACES ABOUT ELECTRICAL EQUIPMENT 1000V AND UNDER SHALL COMPLY WITH 110.26 <br />AND SPACES ABOUT ELECTRICAL ENCLOSURES ABOUT EQUIPMENT ABOVE 1000V SHALL <br />COMPLY WITH 110.34. <br />·REFER TO THE CONDUCTOR SCHEDULE FOR THE TYPE OF CONDUCTORS TO BE USED FOR <br />THE LISTED CIRCUITS. <br />·PV WIRE SHALL BE SECURED USING NON-METALLIC UV-RATED TIE WRAPS. <br />·ALL LINE SIDE AND LOAD SIDE TERMINATIONS OF ALUMINUM AND COPPER CONDUCTORS <br />SHALL BE MADE WITH HIGH PRESS CRIMP LUGS ON BUSSING UNLESS OTHERWISE NOTED. <br />·ALL TERMINATIONS OF ALUMINUM CONDUCTORS SHALL BE PROPERLY INSTALLED WITH <br />BEST PRACTICE PROCEDURES THAT INCLUDE BUT NOT LIMITED TO: USE OF TERMINATION <br />EQUIPMENT RATED FOR ALUMINUM AT THE CONDUCTOR TEMPERATURE, CURRENT, AND <br />VOLTAGE; ALLOWANCE FOR MOVEMENT DUE TO THERMAL EXPANSION/CONTRACTION; <br />PROPER COATING OF EXPOSED ALUMINUM WITH ANTI-OXIDIZATION COMPOUND; USE OF <br />CALIBRATED DEVICES TO TORQUE AND MARK TERMINALS TO REQUIRED SETTINGS. <br />·AT MULTIPLE INVERTERS OUTPUT COMBINER PANEL, TOTAL RATING OF ALL OVERCURRENT <br />DEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR. HOWEVER, THE MAIN OVERCURRENT <br />DEVICE MAY BE EXCLUDED ACCORDING TO NEC 705.12 (B)(3)(3). <br />GROUNDING NOTES <br />·GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND <br />GROUNDING DEVICES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE. <br />·PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC 690.43 AND MINIMUM NEC TABLE <br />250.122. <br />·METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURES CONSIDERED <br />GROUNDED IN ACCORD WITH 250.134 AND 250.136. <br />·EACH MODULE WILL BE GROUNDED USING THE HARDWARE INTEGRATED GROUNDING PINS <br />OR OTHER MEANS APPROVED BY THE MODULE MANUFACTURE AND AHJ. <br />·THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE <br />REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER <br />MODULE. <br />· ·GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED GREEN OR <br />MARKED GREEN IF #4 AWG OR LARGER [NEC 250.119(A)] <br />·THE AC & DC GEC SHALL BE CONTINUOUS FROM THE INVERTER GROUND BUSBAR TO THE <br />MAIN ELECTRICAL SERVICE GROUNDING ELECTRODE SYSTEM. THE DC GEC SHALL BE <br />ATTACHED TO THE GROUND ELECTRODE USING AN IRREVERSIBLE MEANS AS CALLED OUT <br />IN ART 250.64 AND 690.47. <br />·PV INVERTER CONTAINS AN INTEGRATED GFDI CIRCUIT. DO NOT BOND THE GROUNDED DC <br />CONDUCTOR TO GROUND EXCEPT THROUGH THE INVERTER GFDI. <br />·ALL EXPOSED METAL PARTS (MODULE FRAMES, RAIL, PIPE, BOXES, ETC) SHALL BE <br />GROUNDED USING TIN-PLATED COPPER LAY-IN LUGS OR GROUNDING CLIPS LISTED FOR <br />THE PURPOSE. RAIL CLAMPS SHALL BE MADE ELECTRICALLY CONTINUOUS WITH ATTACHED <br />RAIL. <br />·RACKING SYSTEMS SHALL BE BONDED PER MANUFACTURER'S UL 2703 INSTRUCTIONS. <br />·MIN #10 BARE COPPER EGC AT SOURCE CIRCUITS SHALL BE ROUTED SECURELY TO <br />MOUNTING HARDWARE IN A MANNER THAT PROTECTS FROM PHYSICAL HARM. #6 BARE <br />COPPER EGC FOR AREAS SUBJECT TO PHYSICAL DAMAGE. <br />·MODULE FRAMES SHALL BE GROUNDED AT THE LISTED LOCATION PROVIDED BY THE <br />MANUFACTURER OR USING LISTED THIRD-PARTY HARDWARE ONLY IF SPECIFICALLY <br />REFERRED TO IN MANUFACTURER'S INSTRUCTIONS PER UL 1703.INSTALLER SHALL COMPLY <br />WITH MANUFACTURER GROUND IN BONDING REQUIREMENTS <br />·BOTH ENDS OF ALL METALLIC CONDUIT CONTAINING GROUNDING ELECTRODE <br />CONDUCTORS SHALL BE BONDED PER ART 250.64(E). <br />·GROUNDING ELECTRODE CONDUCTOR TO BE BONDED TO (E) GROUNDING ELECTRODE PER <br />ART 250.68. <br />·DC GROUNDING ELECTRODE CONDUCTOR SIZED PER ART 690.47. AC GROUNDING <br />ELECTRODE CONDUCTOR PER 250.66. <br />·MAIN BONDING JUMPERS AND GROUNDED CONDUCTORS (NEUTRALS) SHALL BE SIZED PER <br />250.102 UNLESS OTHERWISE ALLOWED TO BE SIZED PER 705.28(C). <br />·INCREASES IN DC EQUIPMENT GROUNDING CONDUCTOR SIZE TO ADDRESS VOLTAGE <br />CONSIDERATIONS SHALL NOT BE REQUIRED PER ART 690.45. <br />·INCREASES IN AC EQUIPMENT GROUNDING CONDUCTOR SIZE TO ADDRESS VOLTAGE <br />CONSIDERATIONS SHALL BE REQUIRED PER 250.122(B). <br />·INSTALLATION SHALL COMPLY WITH ART 250.52, 250.53. <br />·CIRCUITS OVER 250V SHALL COMPLY WITH ART. 250.97, 250.92(B). <br />NO CONDUCTOR <br />PERMITTED IN SHADED <br />AREA <br />A SCE METERING NOTES <br />NTS <br />GENERATOR <br />CONDUCTORS <br />CONNECT ON LOAD <br />TERMINALS <br />UTILITY <br />CONDUCTORS <br />CONNECT ON LINE <br />TERMINALS <br />SELF-CONTAINED ENCLOSURE <br />COMBINATION CURRENT <br />TRANSFORMER AND METER CAN <br />1. WIRING OF A NGO METER SOCKET FOR VIRTUAL NET METERING PROJECTS , THE GENERATOR SHALL BE <br />CONNECTED TO THE LOAD SIDE OF THE NGO SOCKET. <br />2. THE HORIZONTAL CLEARANCE FROM THE CENTERLINE OF THE METER TO THE NEAREST SIDE WALL OR <br />OTHER OBSTRUCTION SHALL BE 10" MINIMUM. A HORIZONTAL CLEARANCE FROM THE EDGE OF THE <br />METER PANEL TO THE EDGE OF A WINDOW OR DOORWAY (INCLUDING SLIDING GLASS DOORS) SHALL BE <br />10" MINIMUM. <br />3. A CLEAR AND LEVEL WORKING SURFACE SHALL BE PROVIDED WITH A THE MINIMUM WIDTH OF THE <br />WORKSPACE SHALL BE 36 AND A MINIMUM DEPTH OF 36". <br />4. THE MINIMUM HEIGHT OF THE METER SHALL BE 4' AND MAXIMUM HEIGHT SHALL NOT EXCEED 6'-3" <br />MEASURED FROM STANDING SURFACE TO CENTERLINE OF METER SOCKET. <br />4.1. THE MINIMUM HEIGHT CAN BE REDUCED TO 3' IF LOCATED IN A METER ROOM. <br />5. DRAWING IS FOR WIRE REFERENCE ONLY AND IS NOT REFLECTIVE OF ACTUAL WIRE PENETRATIONS. <br />5 5 <br />REMOVABLE TEST <br />PERCH <br />5 <br />5 <br />℄ <br />℄REFER TO DC <br />STRING SCHEDULES <br />FOR FOR STRING <br />LENGTHS AND <br />OPTIMIZER <br />QUANTITY <br />C STRING WIRING - SINGLE OPTIMIZER (TYP.) <br />NTS <br />NOTE: <br />1. NEGATIVE TOO RUN ALONG SIDE THE POSITIVE WIRE. ALL WIRES MUST BE <br />SECURED TO UNDERSIDE OF THE RACKING AND MODULES USING SUNRUN <br />APPROVED METHODS AND MATERIALS WITH APPROPRIATE UV AND <br />ENVIRONMENTAL RATINGS. <br />2. CONDUIT TRANSITIONS SHALL BE MADE UNDER ARRAY. <br />3. INSTALL STRING LABELS ON BOTH ENDS OF HOMERUNS USING LABELS <br />SUITABLE FOR THE ENVIRONMENT. <br />4. FIELD INSTALLED CONNECTOR, 1000VDC, MATING MUST MATCH <br />MANUFACTURES RECOMMENDATIONS (TYP. TWO PER STRING) <br />5. TOTAL CIRCUIT LENGTH SHALL NOT EXCEED MANUFACTURE SPECIFICATIONS <br />6. FREE-AIR PV WIRE TO MATCH GAUGE OF DC-X.X CIRCUIT LOCATED ON DC <br />WIRE SCHEDULES. <br />4 <br />4 <br />3 <br />3 <br />2 1 <br />(N) SOLAREGDE <br />OPTIMIZER <br />(N) PV MODULE <br />5 <br />6 <br />150' MAX DISTANCE <br />FOR WIRELESS <br />OPTIONAL THIRD BATTERY <br />(N) J-BOX WITH 3 OR 4 PORT POLARIS LUG OR <br />EQUIV. <br />(N) SOLAREDGE ENERGY BANK <br />BAT-10K1P, WALL MOUNTED OR <br />USING MANUFACTURES FLOOR <br />STAND KIT (IAC-RBAT-FLRSTD-01) <br />(N) SOLAREDGE HOME HUB INVERTER <br />MC-4 <br />CONNECTORS TO <br />BATTERY <br />CONNECTION <br />UNIT <br />ES-1 <br />ES-2 <br />#CONDUIT CONDUCTOR GROUND <br />ES-1 <br />FLOOR STAND INTERNAL <br />CHANNEL OR 3/4" EMT OR <br />EQUIV. <br />(2) 10 AWG PV WIRE (1) 10 AWG THHN/THWN-2 <br />ES-2 3/4" EMT OR EQUIV.(2) 8 AWG THHN/THWN-2 (1) 10 AWG THHN/THWN-2 <br />SOLAREDGE BESS WIRING <br />NTSD <br />SCE LINE SIDE DISCONNECT <br />LABEL LOCATION: <br />LINE SIDE DISCONNECT <br />LABEL LOCATION: <br />LOAD SIDE DISCONNECT <br />LABEL LOCATION: <br />IF PANEL MODIFICATIONS ARE MADE APPROPRIATE PLACARDS <br />MUST BE INSTALLED LABELING THE SECTIONS. <br />1 <br />2 <br />7 <br />LABEL LOCATION: <br />THE WIRING SEQUENCE OF FACTORY-INSTALLED TEST-BYPASS <br />BLOCKS, FROM LEFT TO RIGHT, IS LINE-LOAD, LINE-LOAD, <br />LINE-LOAD. THIS WIRING SEQUENCE SHALL BE PERMANENTLY <br />LABELED IN 3/4-INCH BLOCK LETTERS BELOW THE <br />TEST-BYPASS TERMINALS. LINE AND LOAD CONDUCTORS <br />SHALL BE CONNECTED ONLY TO TEST-BYPASS BLOCK <br />TERMINALS DESIGNED AS LINE AND LOAD, RESPECTIVELY. <br />3 <br />LABEL LOCATION: <br />THE LABEL SHALL BE LOCATED ON THE METER PANEL OR <br />ADJACENT TO THE METER SOCKET. ACCEPTABLE METHODS FOR <br />LABELING CUSTOMER NGO METERING SECTIONS OR PANEL(S) <br />SHALL BE EITHER BY PERMANENTLY ATTACHED <br />MACHINE-ENGRAVED LAMINATED PHENOLIC (OR EQUAL) TAGS <br />OR BY PERMANENT STENCILED PAINT LETTERING. ALL <br />LETTERING SHALL BE A MINIMUM ONE-QUARTER INCH IN HEIGHT. <br />8 <br />B SCE METERING PLACARDS <br />NTS <br />SOLAR INTERCONNECTION <br />TERMINATION SECTION <br />LINE LOAD <br />SCE UTILITY TERMINATION <br />SECTION <br />DISCONNECT 1 OF 2 <br />GENERATION LOAD SIDE <br />DISCONNECT <br />DISCONNECT 2 OF 2 <br />NET GENERATION OUTPUT <br />METERING <br />NOTE: WHEN SELF-CONTAINED (NON-INSTRUMENT RATED) METERING IS SUPPLIED BY SCE FOR NGO <br />METERING PURPOSES, A SAFETY-SOCKET BOX WITH FACTORY-INSTALLED TEST-BYPASS BLOCKS IS <br />REQUIRED. WHEN SWITCHBOARDS OR SWITCHGEAR ARE INSTALLED, THE CUSTOMER SHALL <br />PROVIDE A TAG OR OTHER IDENTIFICATION METHOD TO INDICATE WHICH BUS OR CABLE DIRECTION <br />FROM THE NGO METERING CONNECTS TO THE GENERATOR OUTPUT. TYPICALLY, THE MARKING <br />SHOULD READ “TOP GENERATOR FED” OR “BOTTOM GENERATOR FED.” IF THE NGO METERING <br />EQUIPMENT AND PCC METERING EQUIPMENT ARE SEPARATED BY A DISTANCE OF MORE THAN 100 <br />FEET, OR ARE LOCATED ON DIFFERENT LEVELS OR FLOORS, THEN A PERMANENT SIGN SHALL BE <br />PLACED AT THE PCC METERING LOCATION WHICH STATES THE LOCATION OF THE NGO METERING <br />EQUIPMENT. <br />CURRENT FLOW <br />LABEL LOCATION: <br />FOR INSTRUMENT TRANSFORMER RATED CT NGOM PANELS, <br />THE ARROW POINTING TOWARDS THE UTILITY SIDE <br />DISCONNECT SHALL BE INSTALLED ON THE INSIDE SIDE WALL <br />OF PANEL OR ON THE OUTSIDE FRONT OF NGOM PANEL. <br />5 <br />SCE LINE SIDE PV LOAD SIDE <br />NGOM <br />M <br />SCE LINE SIDE <br />DISCONNECT <br />GENERATION LOAD <br />SIDE DISCONNECTUTILITY <br />DISTRIBUTION <br />SYSTEM <br />1 <br />3 <br />8 <br />27 <br />5 <br />PV <br />GENERATION <br />FACILITY <br />LABEL LOCATION: <br />PULL SECTIONS4 <br />4 <br /> GRID GENERATION <br />LABEL LOCATION: <br />GRID AND GENERATION CONDUCTORS6 <br />6 <br />OPTIMIZER A: <br />MAKE/MODEL: SOLAREDGE U650 <br />MAX INPUT POWER [W]: 650 <br />MAX INPUT Voc [V]: 60 <br />MAX INPUT Isc [A]: 15 <br />OUTPUT CURRENT [A]: 15 <br />MODULE A: <br />MAKE/MODEL: QCELLS NORTH AMERICA Q.PEAK DUO BLK ML-G10.C+ 410 <br />POWER [W]: 410 <br />Voc [V]: 45.37 <br />Isc [A]: 11.2 <br />Vmp [V]: 37.64 <br />Imp [A]: 10.89 <br />Voc coeff. [%/degC]: -0.27% <br />Isc coeff. [%/degC]: 0.04% <br /># IN SERIES: 1 <br />Vmax CALCULATION: 48.7 VDC = 1 X ( 45.37 VDC - ( 25 - (-2)°C X ( 45.37 X -0.0027 ) V/°C ) <br />C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1233 - TOWNSEND & RAITT I\3 VA - AHJ COMMENTS AND MOD SWAP\1233_TOWNSEND & RAITT I_CAD_V0\TOWNSEND & RAITT I.DWG <br />ELECTRICAL NOTES <br />CONTRACTOR: <br />ENGINEERING APPROVAL: <br />600 CALIFORNIA ST #1800, SAN <br />FRANCISCO, CA 94104 <br />CA CL #750184 <br />UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN <br />PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT <br />LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. <br />TOWNSEND & RAITT I <br />817 S TOWNSEND ST, <br />SANTA ANA, CA 92704, USA <br />APN:109-611-20 <br />DEVELOPER: <br />C&C DEVELOPMENT <br />DESCRIPTION DATE REV <br />0ORIGINAL05/14/25 <br />AAHJ COMMENTS 08/08/25 <br />PROJECT DETAILS: <br />PV SYSTEM: <br />·31.16 kW DC <br />·22.8 kW AC <br />·29.035 CEC AC <br />ENERGY STORAGE: <br />·11.4 kW AC <br />·29.1 kWH <br />E500 <br />SHEET SIZE: <br />REVISION: <br />SHEET TITLE: <br />36" X 24" (ARCH D) <br />DESIGNER: FINS_PK <br />A <br />CONTRACT NUMBER: <br />3003197588 <br />PJT #: PROP-001233 <br />A <br />A