Laserfiche WebLink
12 SERVICE DISCONNECT PLACARDS <br />Scale NTS <br />2" <br />8" <br />2" <br />8" <br />SERVICE DISCONNECT <br />1 OF 2 <br />SERVICE DISCONNECT <br />2 OF 2 <br />PV SYSTEM DISCONNECT <br />FOR UTILITY OPERATION <br />NOTE: <br />1. RED BACKGROUND <br />2. WHITE LETTERING <br />3. TEXT HEIGHT: 1/8" MIN. <br />3 1/8" <br />NOTE: <br />1. MARKING PER ART 690.54 <br />2. RED BACKGROUND <br />3. WHITE LETTERING <br />4. TEXT HEIGHT: 1/8" MIN. <br />NOTE: <br />1. RED BACKGROUND <br />2. WHITE LETTERING <br />3. TEXT HEIGHT: 1/8" MIN. <br />1 POINT OF INTERCONNECTION <br />Scale NTS <br />7 INVERTER AC CIRCUIT BREAKER <br />Scale NTS <br />8 SHOCK HAZARD <br />Scale NTS <br />4 PV SYSTEM MAINTENANCE DISCONNECT <br />Scale NTS <br />2 PV SYSTEM UTILITY AC DISCONNECT <br />Scale NTS <br />5 MAIN SERVICE WITH REMOTE PV SYSTEM DISCONNECT <br />Scale NTS <br />18 UTILITY NET GENERATION OUTPUT <br />Scale NTS <br />19 BESS DISCONNECT (IF APPLICABLE) <br />Scale NTS <br />9 INVERTER ID <br />Scale NTS <br />STRING INVERTERS <br />CENTRAL INVERTERS <br />3 1/8" <br />6 AC COMBINER PANEL <br />Scale NTS <br />3 5/8" <br />3 1/8" <br />3 DC DISCONNECT <br />Scale NTS <br />NOTE: <br />1. MARKING PER ART 690.17, 690.53 <br />2. RED BACKGROUND <br />3. WHITE LETTERING <br />4. TEXT HEIGHT: 1/8" MIN. <br />CAUTION <br />SOLAR ELECTRIC <br />SYSTEM CONNECTED <br />CAUTION <br />POWER TO THIS BUILDING IS <br />ALSO SUPPLIED FROM THE <br />FOLLOWING SOURCES WITH <br />DISCONNECT LOCATED AS <br />SHOWN <br />! <br />DO NOT ADD LOADS <br />PHOTOVOLTAIC SYSTEM <br />COMBINER PANEL <br />WARNING ! <br />LABEL LOCATION: <br />PHOTOVOLTAIC AC COMBINER (IF <br />APPLICABLE). <br />PER CODE(S): CEC 2022: 705.12(B)(3)(2), <br />NEC 2020: 705.12(B)(3)(2), NEC 2017: <br />705.12(B)(2)(3)(b), NEC 2014: <br />705.12(D)(2)(3)(c), NEC 2011: 705.12(D)(4) <br />ELECTRICAL SHOCK HAZARD <br />WARNING! <br />LABEL LOCATION: <br />INVERTER(S), AC DISCONNECT(S), AC <br />COMBINER PANEL (IF APPLICABLE). <br />PER CODE(S): CEC 2022: 690.13(B), NEC <br />2020: 690.13(B), NEC 2017: 690.13(B), <br />NEC 2014: 690.17(E), NEC 2011: <br />690.17(4) <br />TERMINALS ON LINE AND LOAD <br />SIDES MAY BE ENERGIZED IN <br />THE OPEN POSITION <br />MAXIMUM AC OPERATING CURRENT: <br />NOMINAL OPERATING AC VOLTAGE: <br /> AMPS <br /> VAC <br />PHOTOVOLTAIC AC DISCONNECT <br />LABEL LOCATION: <br />AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF <br />INTERCONNECTION. <br />PER CODE(S): CEC 2022: 690.54, NEC 2020: 690.54, NEC <br />2017: 690.54, NEC 2014: 690.54, NEC 2011: 690.54 <br />AC SYSTEM DISCONNECT <br />FOR UTILITY OPERATION <br />LABEL LOCATION: <br />UTILITY DISCONNECT <br />PV SYSTEM DISCONNECT <br />FOR UTILITY OPERATION <br />LABEL LOCATION: <br />UTILITY DISCONNECT <br />INVERTER <br />DC SYSTEM SIZE : <br />NUMBER OF STRINGS: <br />MODULES PER STRING: <br />kW <br />DC SYSTEM SIZE ____kW <br />POINT OF INTERCONNECTION <br />PHOTOVOLTAIC POWER SOURCE <br />ELECTRICAL SHOCK HAZARD <br />WARNING! <br />TERMINALS ON LINE AND LOAD <br />SIDES MAY BE ENERGIZED IN <br />THE OPEN POSITION <br />DC PHOTOVOLTAIC <br />DISCONNECT <br />PHOTOVOLTAIC DC DISCONNECT <br />MAXIMUM POWER POINT VOLTAGE(Vmp): <br />MAXIMUM POWER POINT CURRENT(Imp): <br />MAXIMUM SYSTEM VOLTAGE(Voc): <br />SHORT-CIRCUIT CURRENT(Isc): <br />V <br />A <br />V <br />A <br />LABEL LOCATION: <br />INVERTER(S), DC DISCONNECT(S). <br />PER CODE(S): CEC 2022: 690.53, NEC 2020: 690.53, NEC 2017: 690.53, NEC <br />2014: 690.53, NEC 2011: 690.53 <br />15 INVERTER WARNING <br />Scale NTS <br />ELECTRICAL SHOCK HAZARD <br />WARNING! <br />LABEL LOCATION: <br />INVERTER(S), AC DISCONNECT(S), AC <br />COMBINER PANEL (IF APPLICABLE). <br />PER CODE(S): CEC 2022: 690.13(B), NEC <br />2020: 690.13(B), NEC 2017: 690.13(B), <br />NEC 2014: 690.17(E), NEC 2011: <br />690.17(4) <br />TERMINALS ON LINE AND LOAD <br />SIDES MAY BE ENERGIZED IN <br />THE OPEN POSITION <br />13 DC PV CIRCUIT INSIDE BLDG <br />Scale NTS <br />LABEL LOCATION: <br />CONDUIT, COMBINER BOX <br />PER CODE: CEC 690.31(D)(2) <br />ALL INTERIOR AND EXTERIOR DIRECT-CURRENT <br />CONDUIT, RACEWAYS, ENCLOSURES, CABLE <br />ASSEMBLIES, JUNCTION BOXES, COMBINER <br />BOXES AND DISCONNECTS. MARKING SHALL BE <br />PLACED ON ALL DC CONDUIT EVERY 10 FEET, <br />WITHIN 1 FOOT OF TURNS OR BENDS AND WITHIN <br />1 FOOT ABOVE AND BELOW PENETRATIONS OF <br />ROOF/CEILING ASSEMBLIES, WALLS OR <br />BARRIERS <br />WARNING: PHOTOVOLTAIC <br />POWER SOURCE <br />NET GENERATION OUTPUTMETER <br />LABEL LOCATION: <br />ON THE METER PANEL OR ADJACENT TO THE METER <br />SOCKET. ACCEPTABLE METHODS FOR LABELING <br />CUSTOMER NGO METERING SECTIONS OR PANEL(S) <br />SHALL BE EITHER BY PERMANENTLY ATTACHED <br />MACHINE-ENGRAVED LAMINATED PHENOLIC (OR <br />EQUAL) TAGS, OR BY PERMANENT STENCILED PAINT <br />LETTERING. <br />NOTE: <br />1. TEXT HEIGTH: 1/4" MIN <br />10 UTILITY NET GENERATION OUTPUT <br />Scale NTS <br />16 RAPID SHUTDOWN LABEL <br />Scale NTS <br />SOLAR PV SYSTEM EQUIPPED <br />WITH RAPID SHUTDOWN <br />SOLAR ELECTRIC <br />PV PANELS <br />6" <br />3.5"TURN RAPID SHUTDOWN <br />SWITCH TO THE "OFF" <br />POSITION TO SHUT DOWN <br />PV SYSTEM AND REDUCE <br />SHOCK HAZARD IN THE <br />ARRAY. <br />LABEL LOCATION: <br />ON OR NO MORE THAT 1 M (3 FT) FROM THE SERVICE DISCONNECTING <br />MEANS TO WHICH THE PV SYSTEMS ARE CONNECTED. <br />PER CODE(S): CEC 2022: 690.56(C)(1), NEC 2020: 690.56(C)(1); NEC 2017: <br />690.56(C)(1)(a) <br />LABEL LOCATION: <br />INVERTER(S), AC DISCONNECT(S), AC COMBINER PANEL <br />(IF APPLICABLE). <br />PER CODE(S): CEC 2022: 690.13(B), NEC 2020: 690.13(B), <br />NEC 2017: 690.13(B), NEC 2014: 690.17(E), NEC 2011: <br />690.17(4) <br />ELECTRICAL SHOCK HAZARD <br /> TERMINALS ON THE LINE AND <br />LOAD SIDES MAY BE ENERGIZED <br />IN THE OPEN POSITION <br />WARNING!! <br />WARNING! <br />DO NOT RELOCATE THIS <br />OVERCURRENT DEVICE <br />POWER SOURCE OUTPUT CONNECTION <br />LABEL LOCATION: <br />ADJACENT TO PV BREAKER (IF APPLICABLE). <br />PER CODE(S): CEC 2022: 705.12(B)(3)(2), NEC <br />2020: 705.12(B)(3)(2), NEC 2017: <br />705.12(B)(2)(3)(b), NEC 2014: 705.12(D)(2)(3)(b), <br />NEC 2011: 705.12(D)(7) <br />NOTES AND SPECIFICATIONS: <br />·SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE NEC 2020 ARTICLE <br />110.21(B), UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY SECTION 690, OR IF <br />REQUESTED BY THE LOCAL AHJ. <br />·SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE <br />WORDS, COLORS AND SYMBOLS. <br />·LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING METHOD <br />AND SHALL NOT BE HAND WRITTEN. <br />·LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT <br />INVOLVED. <br />·SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011, PRODUCT SAFETY SIGNS <br />AND LABELS, UNLESS OTHERWISE SPECIFIED. <br />·DO NOT COVER EXISTING MANUFACTURER LABELS. <br />MAXIMUM AC OPERATING CURRENT: <br />NOMINAL OPERATING AC VOLTAGE: <br /> AMPS <br /> VAC <br />PHOTOVOLTAIC AC DISCONNECT <br />LABEL LOCATION: <br />AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF <br />INTERCONNECTION. <br />PER CODE(S): CEC 2022: 690.54, NEC 2020: 690.54, NEC <br />2017: 690.54, NEC 2014: 690.54, NEC 2011: 690.54 <br />ELECTRICAL SHOCK HAZARD <br />WARNING! <br />LABEL LOCATION: <br />INVERTER(S), AC DISCONNECT(S), AC <br />COMBINER PANEL (IF APPLICABLE). <br />PER CODE(S): CEC 2022: 690.13(B), NEC <br />2020: 690.13(B), NEC 2017: 690.13(B), <br />NEC 2014: 690.17(E), NEC 2011: <br />690.17(4) <br />TERMINALS ON LINE AND LOAD <br />SIDES MAY BE ENERGIZED IN <br />THE OPEN POSITION <br />INV-1 <br />LABEL LOCATION: <br />INVERTER (1) <br />INV-2 <br />LABEL LOCATION: <br />INVERTER (2) <br />[When applicable] <br />INV-3 <br />LABEL LOCATION: <br />INVERTER (3) <br />[When applicable] <br />INV-4 <br />LABEL LOCATION: <br />INVERTER (4) <br />[When applicable] <br />LABEL LOCATION: <br />INSTALLED WITHIN 3' OF RAPID SHUT DOWN <br />SWITCH PER CODE(S): NEC 2020: 690.56(C)(2), <br />CEC 2022: 690.56(C)(2), IFC 2018: 1204.5.3 <br />RAPID SHUTDOWN SWITCH <br />FOR SOLAR PV SYSTEM <br />11 RAPID SHUTDOWN SWITCH <br />Scale NTS <br />ENERGY STORAGE SYSTEMDISCONNECT <br />LABEL LOCATION: <br />ENERGY STORAGE SYSTEM DISCONNECT <br />PER CODE(S): NEC 2020: 706.15(C), CEC 2022: 706.15(C) <br />WARNING! <br />LABEL LOCATION: <br />UTILITY SERVICE METER AND MAIN <br />SERVICE PANEL. <br />PER CODE(S): CEC 2022: 705.12(C), NEC <br />2020: 705.12(C) <br />SOURCES: UTILITY GRID, <br />BATTERY AND PV SOLAR <br />ELECTRIC SYSTEM <br />THREE POWER SUPPLY <br />14 NOT USED <br />Scale NTS <br />NOT USED <br />C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1233 - TOWNSEND & RAITT I\3 VA - AHJ COMMENTS AND MOD SWAP\1233_TOWNSEND & RAITT I_CAD_V0\TOWNSEND & RAITT I.DWG <br />WARNING LABELS <br />CONTRACTOR: <br />ENGINEERING APPROVAL: <br />600 CALIFORNIA ST #1800, SAN <br />FRANCISCO, CA 94104 <br />CA CL #750184 <br />UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN <br />PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT <br />LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. <br />TOWNSEND & RAITT I <br />817 S TOWNSEND ST, <br />SANTA ANA, CA 92704, USA <br />APN:109-611-20 <br />DEVELOPER: <br />C&C DEVELOPMENT <br />DESCRIPTION DATE REV <br />0ORIGINAL05/14/25 <br />AAHJ COMMENTS 08/08/25 <br />PROJECT DETAILS: <br />PV SYSTEM: <br />·31.16 kW DC <br />·22.8 kW AC <br />·29.035 CEC AC <br />ENERGY STORAGE: <br />·11.4 kW AC <br />·29.1 kWH <br />E800 <br />SHEET SIZE: <br />REVISION: <br />SHEET TITLE: <br />36" X 24" (ARCH D) <br />DESIGNER: FINS_PK <br />A <br />CONTRACT NUMBER: <br />3003197588 <br />PJT #: PROP-001233 <br />A