Laserfiche WebLink
6' <br />- <br />3 <br />" <br /> <br />M <br />A <br />X <br />4' <br />- <br />0 <br />" <br /> <br />M <br />I <br />N <br />FR <br />O <br />M <br /> <br />G <br />R <br />A <br />D <br />E <br />B (N) NGO METER SOCKET ≤ 200A <br />NTS <br />10" <br />MIN. <br />MIN. CLEARANCE <br />TO OBSTRUCTIONS <br />OR SIDE WALLS <br />36" MIN. <br />(N) HOUSEKEEPING PAD <br />THE PAD SHALL BE FLUSH WITH <br />THE BOTTOM OF THE SERVICE EQUIPMENT <br />AND EXTEND A MINIMUM OF THREE FEET. <br />10" <br />MIN. <br />18" MIN. <br />MIN. CLEARANCE TO <br />EDGE OF WINDOW <br />OR DOOR <br />- NGO METER WORKING SPACE <br />TO BE MAINTAINED. <br />- EQUIPMENT ABOVE OR BELOW <br />NGOM WILL NOT EXCEED <br />DEPTH OF NGOM. <br />- NGOM TO BE MOUNTED ON <br />STRUT IF NEEDED TO <br />ACCOUNT FOR ANY DEPTH <br />DIFFERENCES. <br />- CENTER OF METER CAN NOT <br />TO EXCEED 6'-3" MAX, 4'-0" MIN. <br />- EQUIPMENT AND CONDUIT <br />SHOWN IS DIAGRAMMATIC <br />ONLY. SEE LINE DRAWINGS <br />FOR CONDUIT SIZING. <br />NOTES <br />MIN. CLEARANCE TO <br />PLUMBING FIXTURES <br />EXTENDING 6" OUT <br />FROM WALL SURFACE <br />6' <br />- <br />6 <br />" <br /> <br />M <br />I <br />N <br /> <br />H <br />E <br />I <br />G <br />H <br />T <br />CL <br />E <br />A <br />R <br />A <br />N <br />C <br />E <br />FR <br />O <br />M <br /> <br />G <br />R <br />A <br />D <br />E <br />(E) GRADE <br />A (N) AC DISCONNECT <br />(E) GRADE <br />6' <br />- <br />7 <br />" <br /> <br />M <br />A <br />X <br /> <br />H <br />A <br />N <br />D <br />L <br />E <br />HE <br />I <br />G <br />H <br />T <br /> <br />F <br />R <br />O <br />M <br /> <br />G <br />R <br />A <br />D <br />E <br />NOTES <br />- CENTER OF GRIP IN HIGHEST <br />POSITION MUST NOT EXCEED <br />6'-7" MAX. <br />- EQUIPMENT AND CONDUIT <br />SHOWN IS DIAGRAMMATIC <br />ONLY. SEE LINE DRAWINGS <br />FOR CONDUIT SIZING. <br />C INVERTER CLEARANCE - SOLAREDGE HOME HUB <br />MIN. CLEARANCE <br />BACK TO BACK <br />INVERTERS 8" MIN. <br />CLEAR <br />16" MIN. <br />CLEAR <br />8" MIN. <br />CLEAR <br />MIN. CLEARANCE <br />VERTICALLY <br />STACKED INVERTERS <br />8" MIN. <br />CLEAR <br />MIN. CLEARANCE <br />SIDE-BY-SIDE INVERTERS <br />- LISTED MIN. CLEARANCES FOR <br />INVERTER TO OTHER <br />OBJECTS, UNLESS NOTED <br />- MIN. CLEARANCES REQUIRED <br />FOR HEAT DISSIPATION <br />- CONDUIT MAY BE REQUIRE <br />ADDITIONAL CLEARANCE <br />- EQUIPMENT AND CONDUIT <br />SHOWN IS DIAGRAMMATIC <br />ONLY. SEE LINE DRAWINGS <br />FOR CONDUIT SIZING. <br />NOTES8" MIN. <br />CLEAR <br />4" MIN. <br />CLEAR <br />4" MIN. <br />CLEAR <br />4" MIN. <br />CLEAR <br />46.4" <br />9.84" <br />BATTERY WEIGHT: 262LBS <br />31.1" 8" MIN. CLEAR <br />MIN. CLEARANCE <br />BATTERY SHOWN ON <br />OPTIONAL FLOOR STAND <br />KIT <br />SOLAREDGE ENERGY BANK <br />BAT-10K1P <br />D BESS CLEARANCE - SOLAREDGE ENERGY BANK <br />·LISTED MIN. CLEARANCES FOR ENERGY BANK TO OTHER <br />OBJECTS AS REQUIRED BY MANUFACTURER. NEC 110.3(B) <br />·BATTERY CAN BE WALL MOUNTED OR USE MANUFACTURES <br />FLOOR STAND KIT. <br />·8" MIN. CLEARANCES REQUIRED FOR HEAT DISSIPATION <br />·CONDUIT MAY REQUIRE ADDITIONAL CLEARANCE. <br />·EQUIPMENT AND CONDUIT SHOWN IS DIAGRAMMATIC ONLY. <br />·WORKING CLEARANCES SHALL BE IN ACCORDANCE WITH NEC <br />110.26 FOR ANY COMPONENTS THAT ARE LIKELY TO REQUIRE <br />EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE <br />WHILE ENERGIZED. <br />·BATTERIES SHALL NOT BE INSTALLED IN DIRECT SUNLIGHT <br />WITH OUT SHADE COVER <br />NOTES <br />8" MIN. <br />CLEAR <br />8" MIN. <br />CLEAR <br />8" MIN. <br />CLEAR <br />SOLAREDGE ENERGY BANK <br />WITH 4 BATTERIES ON FLOOR STAND KITS <br />53.15" <br />MIN. <br />6.3" <br />13.78" <br />1ST BATTERY FLOOR <br />STAND TO BE ANCHORED <br />TO WALL/RACK <br />SIDE BRACKETS <br />FOR <br />ATTACHING <br />BATTERIES <br />MIN. CLEAR IF <br />WALL MOUNTING <br />DC <br />CONNECTION <br />LOCATION <br />(N) AC DISCONNECT <br />GENERAL NOTES <br />·FIELD VERIFY ALL MEASUREMENTS <br />·ALL WORK SHALL COMPLY WITH ALL STATE AND LOCAL CODES AND ANY OTHER REGULATING AUTHORITIES <br />WHICH HAVE AUTHORITY OVER ANY PORTION OF THE WORK. <br />·DRAWINGS HAVE BEEN DETAILED IN COMPLIANCE WITH UL LISTING REQUIREMENTS, OSFM SOLAR <br />PHOTOVOLTAIC INSTALLATION REQUIREMENTS, AND BUILDING CODES FOR THE MATERIALS SPECIFIED. PRIOR <br />TO COMMENCEMENT OF ANY WORK, THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS AND NOTIFY THE <br />DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE FROM SUNRUN OF ANY DISCREPANCIES. ANY WORK <br />PERFORMED IN CONFLICT WITH THE CONTRACT DOCUMENTS SHALL BE CORRECTED AT THE <br />SUBCONTRACTORS SOLE EXPENSE. <br />·SUBCONTRACTOR INITIATED CHANGES SHALL BE SUBMITTED IN WRITING TO SUNRUN FOR APPROVAL BEFORE <br />MAKING ANY CHANGES OR DEVIATION FROM PLANS BEFORE WRITTEN APPROVAL FROM SUNRUN PLACES <br />LIABILITY ON THE SUBCONTRACTOR. <br />·ALL EQUIPMENT SHALL BE MOUNTED AS SHOWN. WHERE DETAILS ARE NOT PROVIDED, CONTRACTOR SHALL <br />USE STANDARD CONSTRUCTION PRACTICES. <br />·ALL SURFACES SHALL BE PATCHED AND PAINTED AROUND NEW DEVICES AND EQUIPMENT TO MATCH EXISTING <br />FINISHES. ANY METAL SHAVINGS FROM SITE WORK SHALL BE CLEANED FROM ALL SURFACES WHERE OXIDIZED <br />OR CONDUCTIVE METAL SHAVINGS MY CAUSE RUST, ELECTRICAL SHORT CIRCUITS, OR OTHER DAMAGE. <br />·APPROVALS FROM BUILDING INSPECTORS SHALL NOT CONSTITUTE AUTHORITY TO DEVIATE FROM THE <br />DRAWINGS. <br />C:\USERS\THADDEUS.STEERMAN\DESKTOP\WORKING PROJECTS\1233 - TOWNSEND & RAITT I\3 VA - AHJ COMMENTS AND MOD SWAP\1233_TOWNSEND & RAITT I_CAD_V0\TOWNSEND & RAITT I.DWG <br />ELECTRICAL PLAN VIEWS <br />CONTRACTOR: <br />ENGINEERING APPROVAL: <br />600 CALIFORNIA ST #1800, SAN <br />FRANCISCO, CA 94104 <br />CA CL #750184 <br />UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN <br />PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT <br />LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. <br />TOWNSEND & RAITT I <br />817 S TOWNSEND ST, <br />SANTA ANA, CA 92704, USA <br />APN:109-611-20 <br />DEVELOPER: <br />C&C DEVELOPMENT <br />DESCRIPTION DATE REV <br />0ORIGINAL05/14/25 <br />AAHJ COMMENTS 08/08/25 <br />PROJECT DETAILS: <br />PV SYSTEM: <br />·31.16 kW DC <br />·22.8 kW AC <br />·29.035 CEC AC <br />ENERGY STORAGE: <br />·11.4 kW AC <br />·29.1 kWH <br />E200 <br />SHEET SIZE: <br />REVISION: <br />SHEET TITLE: <br />36" X 24" (ARCH D) <br />DESIGNER: FINS_PK <br />A <br />CONTRACT NUMBER: <br />3003197588 <br />PJT #: PROP-001233 <br />A <br />E EQUIPMENT PLAN - POI-1 (BLDG 821) <br />SCALE: 1/4" = 1'-0" <br />(N) PV POINT OF INTERCONNECTION (POI-1) <br />(N) PV PRODUCTION METER SOCKET 821 S TOWNSEND <br />ST SOMAH PV PRODUCTION METER <br />REFERENCE METER NUMBER: 222013-113945 <br />(N) UTILITY AC DISCONNECT (ACDS-1.1) <br />(N) MAINTENANCE AC DISCONNECT (ACDS-1.2) <br />(N) AC LOAD CENTER (LC-1.1) <br />(N) PV INVERTER & ESS AC DISCONNECT (INV-1.1) <br />(N) PV INVERTER & ESS AC DISCONNECT (INV-1.2) <br />(N) SOLAREDGE BAT-10K1P BATTERY <br />(N) SOLAREDGE BAT-10K1P BATTERY <br />MOUNTED ON FLOOR STAND KIT <br />A