Wind (Uplift Check) <br />DCR check= 0.39 CONNECTION PASS <br />Vertical Load Resisting System Design <br />Gravity Load Check <br />Roof Dead Load <br />Roof Dead Load 10.0 psf <br />PV Dead Load 3.0 psf <br />Roof Live Load 20 psf <br />PV Roof Live Load 0 psf <br />Snow Load 0 psf <br />IEBC Check <br />Existing With PV <br />Roof Dead Load (D) 10.0 13.0 psf <br />Roof Live Load (Lr) 18.4 0.0 psf <br />Roof Snow Load (S) 0.0 0.0 psf <br />Cs= 1 0.78 <br />Existing With PV <br />(D + Lr) = 22.7 14.4 psf <br />(D + S) = 8.7 11.3 psf <br />Maximum Gravity Load 22.7 14.4 psf <br />Load Increase (%)-36.4% OK <br />IBC Provision 2021 <br />Siesmic Loads Check <br />Roof Dead Load 10 psf <br />% or Roof with Pv 14.4% <br />Dpv and Racking 3 psf <br />Average Total Dead Load 10.4 psf <br />Increase in Dead Load 2.2%OK <br />Limits of Scope of Work and Liability <br />*The requirements of Section 806.2 of the 2018 IEBC are met and the <br />structure is permitted to remain unaltered. <br />The Existing structure is assumed to have been designed and constructed following appropriate codes and to <br />have appropriate permits. The analysis was according to applicable building codes, professional engineering <br />and design experience, opinions and judgments. This evalution produced for this structure's assessment is only <br />for the proposed solar panel installation referenced in the stamped plan set and were made according to <br />generally recognized structural analysis standards and procedures. Prior to commencement of work, the <br />contractor shall verify the framing sizes, spacings, and spans. Contractor shall also verify that there is framing <br />damage or deficiencies. If observed, the EOR must be notified before install. <br />The increase in seismic Dead weight as a result of the solar system is less than 10% of the existing structure <br />and therefore no further seismic analysis is required. <br />projects@evengineersnet.com <br />http://www.evengineersnet.com