Laserfiche WebLink
CONDUIT SCHEDULE <br />TAG CIRCUIT DESCRIPTION CONDUCTOR NEUTRAL GROUND CONDUIT <br />1 Inverter Input (6) 10 AWG (PV WIRE)N/A 6 AWG (BARE) Open Air <br />2 Inverter Input (6) 10 AWG THWN-2 N/A 8 AWG THWN-2 3/4 EMT <br />3 Inverter Output (2) 6 AWG THWN-2 (1) 6 AWG THWN-2 8 AWG THWN-2 3/4 EMT <br />4 Battery Output (2) 6 AWG THWN-2 (1) 6 AWG THWN-2 8 AWG THWN-2 3/4 EMT <br />5 Battery Load Center <br />Output (2) 1 AWG THWN-2 (1) 1 AWG THWN-2 6 AWG THWN-2 1-1/4 EMT <br />6 agate feeder & backup <br />panel feeder (2) 3 AWG THWN-2 (1) 3 AWG THWN-2 8 AWG THWN-2 1 EMT <br />7 Backup Loads <br />(12) 10 AWG THWN-2 (11) 10 AWG THWN-2 8 AWG THWN-2 <br />1-1/2 EMT <br />(2) 8 AWG THWN-2 (1) 8 AWG THWN-2 8 AWG THWN-2 <br />PAGE <br />REV: B 9/15/2025 <br />JUAN BELTRAN <br />2502 S ARTESIA ST, SANTA ANA, <br />CA, 92704 <br />PROJECT NUMBER: <br /> 109R-502BELT PR-3004162307 <br />SHEET <br />DESIGNER: <br />PRAVEEN <br />CUSTOMER RESIDENCE: <br />TEL. (657) 272-3868 <br />APN: 412-391-11 <br />(415) 580-6920 ex3 <br />PV-4.1 <br />#ESTAMP#SSTAMP <br />2500 WHITE RD. SUITE A, IRVINE CA 92614 <br />PHONE 805.540.7603 <br />FAX 949.215.7778 <br />CA CL #750184 <br />GILBERT CORREIA, C10, C46 <br />ELECTRICAL CONT. <br />MODULE CHARACTERISTICS <br />JA SOLAR: JAM54S31-405/MR 405 W <br />OPEN CIRCUIT VOLTAGE 37.23 V <br />MAX POWER VOLTAGE 31.21 V <br />SHORT CIRCUIT CURRENT 13.96 AINSTALLER MUST CHECK THE CONDITION, <br />INSTALLABILITY AND CODE COMPLIANCE OF <br />EXISTING EQUIPMENT. <br />General Notes: <br />• CITY REQUIRES TWO SOURCES OF GROUND - UFER, TWO GROUNDS RODS OR <br />COLD WATER GAS BOND <br />POWER CONTROL SYSTEM (PCS): <br /> • A PCS IS INSTALLED IN ACCORDANCE WITH CEC 2022 705.13 <br /> • THE PCS SHALL LIMIT GENERATION SOURCE OUTPUT SUCH THAT CURRENT FROM <br />ALL SOURCES OF SUPPLY DOES NOT EXCEED THE RATING OF ANY BUSBAR OR <br />CONDUCTOR SUPPLIED BY THE POWER PRODUCTION SOURCES <br /> • ANY BUSBAR OR CONDUCTOR ON THE LOAD SIDE OF THE SERVICE DISCONNECT <br />NOT MONITORED BY THE PCS SHALL COMPLY WITH ARTICLE 705.12. <br /> • ACCESS TO PCS CONTROLS IS RESTRICTED TO QUALIFIED PERSONS IN <br />ACCORDANCE WITH 240.6(C). <br />ENERGY STORAGE SYSTEM:(2) FRANKLINWH ENERGY STORAGE <br />INC:AGATE <br />ENABLE PCS; SETPOINTS: <br />- 100A - PCS BUSBAR PROTECTION CURRENT <br />- 0A - FAIL SAFE GENERATION BACKFEED CURRENT SUPPLY (120% COMPLIANT) <br />ANY MULTIWIRE BRANCH CIRCUITS RELOCATED ARE TO BE IDENTIFIED, GROUPED, AND EQUIPPED WITH A 2-POLE OCPD BREAKER PER CEC 210.4(B,D). <br />IF THE RELOCATED LOADS EXTEND MORE THAN 6 FEET, AFCI PROTECTION APPLIES PER 2019 CEC 210.12 <br />RELOCATED LOAD CONDUCTORS EXTENDING MORE THAN 2 FEET, AND WITH MORE THAN 3 WIRES, WILL <br />BE UPSIZED TO COMPLY WITH CEC 310.15(C)(1) <br />B <br />B <br />B