Laserfiche WebLink
T <br />GND <br />A <br />(N) UTILITY TRANSFORMER <br />(N) MSB: 3000A, 480/277V, 3PH, 4W, 65kAIC NEMA 3R <br />PLAN NOTES: <br />1.ALL OCPD SHALL BE LOCKED OUT IN <br />AN OPEN POSITION. <br />2.MAIN CIRCUIT BREAKER TO BE <br />PROVIDED WITH GROUND-FAULT <br />PROTECTION OF EQUIPMENT AND <br />SHALL BE PERFORMANCE TESTED <br />PRIOR TO ENERGIZATION VIA THE <br />PRIMARY CURRENT INJECTION <br />PROCCESS. A WRITTEN TEST RECORD <br />SHALL BE PROVIDED TO THE CITY <br />INSPECTOR PRIOR TO APPROVAL AND <br />METER RELEASE PER CEC 230.95. <br />3.SERVICE ADDRESS TO BE VERIFIED <br />WITH CITY PLANNING PRIOR TO <br />METER RELEASE. <br />NEW <br />EXISTING <br />LEGEND <br />1 NUMBER OF CHARGING UNITS:5 <br />NUMBER OF PORTS:10 <br />ELECTRICAL RATING PER POWER CABINET:LEVEL 3: 433A, 480V <br />MAXIMUM CAPACITY PER PORT (DC):300KW MAX (150KW EACH IF SHARED) <br />LOAD SHARING:YES <br />2 ELECTRICAL PANEL RATING:(N) MSB: 3000A, 480/277V, 3PH, 4W, 65kAIC NEMA 3R ENCLOSURE <br />(N) SERVICE <br />METERM <br />(N) 3000A/3P 2 <br />(N) (2) 5/8" x 8'-0" COPPER CLAD GROUND <br />ROD INSTALLATION PER NEC <br />250-62, 250-64, AND 250-68 <br />(2) #1/0 BARE COPPER <br />GROUNDING ELECTRODE <br />CONDUCTOR PER NEC 250-66(A) <br />6'-0" <br />MIN. <br />(N) EVCS #1 <br />DUAL PORT <br />LOOP INFINITY <br />(N) EVCS #2 <br />DUAL PORT <br />LOOP INFINITY <br />(N) EVCS #3 <br />DUAL PORT <br />LOOP INFINITY <br />(N) EVCS #4 <br />DUAL PORT <br />LOOP INFINITY <br />B B <br />(N) 600A/3P <br />(N) POWER <br />CABINET 1 <br />(N) POWER <br />CABINET 2 <br />C C <br />(N) 600A/3P <br />B <br />(N) 600A/3P <br />(N) POWER <br />CABINET 3 <br />C <br />B <br />(N) 600A/3P <br />(N) POWER <br />CABINET 4 <br />C <br />1 1 1 1 <br />(N) EVCS #5 <br />DUAL PORT <br />LOOP INFINITY <br />B <br />(N) 600A/3P <br />(N) POWER <br />CABINET 5 <br />C <br />1 <br />3 <br />SINGLE <br />LINE <br />DIAGRAM <br />E-05 <br />PE <br />R <br />M <br />I <br />T <br /> <br />A <br />P <br />P <br />L <br />I <br />C <br />A <br />T <br />I <br />O <br />N <br />THE DRAWING AND THE <br />DESIGN SHOWN IS <br />PROPERTY OF <br />SITELOGIQ, INC. THE <br />REPRODUCTION, <br />COPYING, OR USE OF <br />THIS DRAWING <br />WITHOUT WRITTEN <br />CONSENT OF SITELOGIQ <br />IS PROHIBITED. ANY <br />INFRINGEMENT WILL BE <br />SUBJECT TO LEGAL <br />ACTION. <br />EVCS DESIGN <br />DOCUMENTS <br />DRAWN BY: <br />CHECKED BY: <br />DATE: <br />REVISION: <br />SHEET: <br />TEMPLATE:5.14.2025 <br />SU <br />N <br />F <br />L <br />O <br />W <br />E <br />R <br /> <br />M <br />E <br />T <br />R <br />O <br />39 <br />4 <br />1 <br /> <br />S <br />O <br />U <br />T <br />H <br /> <br />B <br />R <br />I <br />S <br />T <br />O <br />L <br /> <br />S <br />T <br />R <br />E <br />E <br />T <br />, <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />4 <br />EL <br />ANP <br />10.24.2025 <br />A <br />COMIND009300_42020_RENEWABLE ENERGY PARTNERS_SUNFLOWER METRO SANTA ANA_EV_REV A.DWG <br />A <br />CLARK LONGHURST, PRESIDENT, C&I DIV. <br />SITELOGIQ, INC. LICENSE NO. 1054171 <br />C-10 ELECTRICAL