MAIN GROUND SYSTEM DETAIL <br />WHERE APPLICABLE: GROUNDING ELECTRODE <br />TO METAL UNDERGROUND WATER PIPE WITHIN <br />5' FROM THE MAIN ENTRANCE INTO BLDG PER <br />ART. 250-58-(A)(1) <br />WHERE APPLICABLE: TO EFFECTIVELY <br />GROUND METAL FRAME OF THE BLDG. PER <br />ART. 250-52-(A)(2) <br />WHERE APPLICABLE: TO GAS PIPING <br />PER ART. 250-104(B) <br />WHERE APPLICABLE: TO SPRINKLER PIPING <br />PER ART. 250-104(B) <br />20 FEET OF OF #4 BARE COPPER TO CONCRETE <br />ENCASED GROUNDING ELECTRODE. 250-52-(A)(3) <br />3/0 CU TO EACH SERVICE ENTRANCE SECTION <br />WITHIN THE BUILDING <br />1 #* CU TO GROUNDED CONDUCTOR PER ART.250-28 <br />PROVIDE PERMANENT TAG TO IDENTIFY EACH <br />GROUND <br />FULL WIDTH x 1 <br />2" DEPTH x 2" HIGH BARE COPPER BUS <br />PLATE ATTACHED TO WALL OF ELECTRICAL ROOM <br />WITH 1 <br />2" SPACERS <br />1 <br />2" PORCELAN INSULATORS 6" O.C. <br />BETWEEN WALL AND COPPER <br />GROUND BAR <br />1 #6 CU TO MAIN TELEPHONE <br />BACKBOARD <br />FINISHED FLOOR <br />WHERE APPLICABLE: GROUNDING ELECTRODE <br />CONDUCTOR TO TRANSFORMER(S) SEE <br />ONE-LINE DIAGRAM FOR APPROPRIATE SIZE. <br />WHERE APPLICABLE: BONDING CONDUCTOR TO <br />BUILDING STEEL. NOTE: ISOLATED BUILDING <br />STEEL SECTIONS MUST BE BONDED TOGETHER <br />AS A SYSTEM. <br />1. THE BONDING OF WATER AND SPRINKLER PIPING APPLIES TO METALIC PIPING ONLY. NON-METALLIC WATER AND FIRE <br />SPRINKLER PIPING IS NOT REQUIRED. <br />2. METAL PIPING WITHIN ANY APARTMENT OR TENANT SPACE SHALL BE BONDED TO THE GROUNDING ELECTRODE SYSTEM. <br />ALL CONDUCTORS, THIS DETAIL, SHALL BE <br />ROUTED WITHIN SCHEDULE 80 PVC OR, <br />WHERE INSTALLED IN METALLIC RACEWAYS <br />OR CONDUIT, SHALL BE BONDED TO EACH <br />END OF THE RACEWAY AND CONDUIT USING <br />FITTINGS LISTED FOR THE PURPOSE. <br />GROUNDING ELECTRODE CONDUCTOR SIZE: <br />SERVICE SIZE <br />0 - 200A: <br />201 - 400A: <br />401 - 600A: <br />601 - 1000A: <br />1,200A AND LARGER: <br />G.E.C. SIZE (CU) <br />#4 <br />#2 <br />#1/0 <br />#2/0 <br />#3/0 <br />** GROUNDING ELECTRODE CONDUCTOR <br />SHALL BE SIZED AS FOLLOWS: <br />SERVICE SIZE <br />0-200A <br />201-400A <br />OVER 401A <br />G.E.C. SIZE (CU) <br />#4 <br />#1/0 <br />#3/0 <br />SCALE <br />NONE 1 <br />MAIN BONDING JUMPER SIZE: <br />THE MAIN BONDING JUMPER SUPPLIED WITH <br />EQUIPMENT IS TO BE USED TO PRESERVE THE LISTING <br />OF THE EQUIPMENT. IF THE MBJ IS MISSING, CONTACT <br />THE MANUFACTURER TO SUPPLY THE MAIN BONDING <br />JUMPER. AS THE EQUIPMENT IS LISTED, ANY <br />DEVIATION FROM THIS WILL VIOLATE NEC 110.3(B). <br />2P <br />100A <br />1- <br />1 <br />/ <br />4 <br />" <br />C <br />, <br /> <br />2 <br /># <br />1 <br />, <br /> <br /># <br />1 <br />N <br />, <br /> <br /># <br />8 <br />G <br />3P <br />100A <br />1- <br />1 <br />/ <br />2 <br />" <br />C <br />, <br /> <br />3 <br /># <br />1 <br />, <br /> <br /># <br />1 <br />N <br />, <br /> <br /># <br />8 <br />G <br />2" <br />C <br />, <br /> <br />3 <br /># <br />3 <br />/ <br />0 <br />, <br /> <br /># <br />3 <br />/ <br />0 <br />N <br />, <br /> <br /># <br />4 <br />G <br />3P <br />100A <br />1- <br />1 <br />/ <br />2 <br />" <br />C <br />, <br /> <br />3 <br /># <br />1 <br />/ <br />0 <br />, <br /> <br /># <br />6 <br />G <br />PANEL HB <br />200A <br />MCB <br />3P <br />200A <br />2" <br />C <br />, <br /> <br />3 <br /># <br />3 <br />/ <br />0 <br />, <br /> <br /># <br />3 <br />/ <br />0 <br />N <br />, <br /> <br /># <br />4 <br />G <br />MAIN LV SWITCHBOARD: MSA <br />480Y/277V 3P 4W <br />2000A BUS <br />FRONT ACCESS, TYPE 1 FREE STANDING <br />ALUMINUM BUS 100% SIZED NEUTRAL <br />NEMA TYPE 3 ENCLOSURE <br />EATON TYPE OR EQUAL <br />RATED FOR SEISMIC ZONE 4 <br />75ºC (MIN) RATED TERMINATIONS <br />65,000AIC <br />2000A <br />3P <br />MCB <br />LSIG <br />MMS <br />3P <br />100A <br />1- <br />1 <br />/ <br />4 <br />" <br />C <br />, <br /> <br />3 <br /># <br />2 <br />, <br /> <br /># <br />8 <br />G <br />3P <br />200A <br />2" <br />C <br />, <br /> <br />3 <br /># <br />3 <br />/ <br />0 <br />, <br /> <br /># <br />3 <br />/ <br />0 <br />N <br />, <br /> <br /># <br />6 <br />G <br />3P <br />700A <br />(2 <br />) <br />4 <br />" <br />C <br />, <br /> <br />3 <br /># <br />5 <br />0 <br />0 <br />k <br />c <br />m <br />i <br />l <br />, <br /> <br /># <br />5 <br />0 <br />0 <br />k <br />c <br />m <br />i <br />l <br /> <br />N <br />, <br /> <br /># <br />1 <br />/ <br />0 <br />G <br />3P <br />700A <br />(2 <br />) <br />3 <br />" <br />C <br />, <br /> <br />3 <br /># <br />4 <br />0 <br />0 <br />k <br />c <br />m <br />i <br />l <br />, <br /> <br /># <br />4 <br />0 <br />0 <br />k <br />c <br />m <br />i <br />l <br /> <br />N <br />, <br /> <br /># <br />1 <br />/ <br />0 <br />G <br />T3 <br />75KVA <br />480V 3P 3W <br />208Y/120V 3P 4W <br />N <br />GND <br />3/0 AWG, CU <br />MAIN SECTION DISTRIBUTION SECTIONPULL & METER SECTION <br />M <br />UTILITY: SCE <br />2000A, 480Y/277V, 3Ø, 4W <br />SERVICE. <br />UNDERGROUND <br />SERVICE <br />CONDUCTORS <br />UNDERGROUND <br />SERVICE <br />CONDUCTORS <br />(E) <br />SPARE SPARE <br />(E) <br />SPARE <br />T1 <br />75KVA <br />480V 3P 3W <br />208Y/120V 3P 4W <br />PANEL HA <br />200A <br />MLO <br />PANEL LA <br />200A3P <br />200A <br />PANEL LAA <br />100A <br />MLO <br />PANEL LAA1 <br />100A <br />MLO <br />(E) <br />(E) <br />(E) <br />(E) <br />SPARESPARE <br />PANEL H2 <br />700A <br />MLO <br />PANEL H1 <br />700A <br />MLO <br />(N) (N) <br />(E) <br />4 <br />2 3 <br />- <br />1. GROUNDING ELECTRODE SYSTEM. SEE DETAIL THIS SHEET FOR ADDITIONAL <br />INFORMATION. <br />2. EXISTING MINIMUM #4 GROUNDING ELECTRODE CONDUCTOR TO BUILDING <br />GROUNDING ELECTRODE SYSTEM. <br />3. EXISTING MINIMUM #4 SYSTEM BONDING JUMPER. <br />4. ALL TERMINATIONS OR CONNECTORS TO BE RATED 75 DEGREE CENTIGRADE <br />MINIMUM. <br />5. COORDINATE EXACT LOCATIONS OF UTILITY SOURCES WITH CIVIL SITE UTILITIES <br />PLAN DRAWINGS. <br />6. EXISTING PANEL 'HA', 200A, 480/277V, 3P, 4W. E.C. IS TO INTERCEPT THE EXISTING <br />FEEDERS AND PROVIDE A JUNCTION BOX (SIZE TO MEET MINIMUM CEC <br />REQUIREMENTS) TO TRANSITION AND EXTEND FEEDERS TO RECONNECT TO NEW <br />SWITCHBOARD 'MSA'. <br />7. EXISTING DRY TRANSFORMER 'T3', 75 KVA, E.C. IS TO INTERCEPT THE EXISTING <br />FEEDERS AND PROVIDE A JUNCTION BOX (SIZE TO MEET MINIMUM CEC <br />REQUIREMENTS) TO TRANSITION AND EXTEND FEEDERS TO RECONNECT TO NEW <br />SWITCHBOARD 'MSA'. <br />8. MAXIMUM PERMISSIBLE LOAD IS LIMITED TO 670A. <br />KEYNOTES <br />PANEL ANNOTATION <br />A <br />100A <br />MCCB <br />PANEL REFERENCE <br />BREAKER RATING OR MINIMUM BUS <br />BREAKER (MCCB) OR MAIN LUGS ONLY (MLO) <br />1. DO NOT USE THE CONDUCTOR LENGTHS FOR BIDDING PURPOSES, THESE ARE TO <br />BE USED TO CALCULATE THE AVAILABLE FAULT CURRENT AND VOLTAGE DROP OF <br />CONDUCTORS ONLY. WHERE CONDUCTORS ARE INCREASED IN LENGTH, THE <br />ELECTRICAL CONTRACTOR SHALL VERIFY THE INSTALLATION WILL COMPLY WITH <br />THE CEC AND ENERGY CODE VOLTAGE DROP REQUIRMENTS. <br />2. ALL CONDUCTORS TO BE RATED FOR 600 VOLTS. CONDUCTOR INSULATION SHALL <br />BE THHN/THWN-2 OR XHHW-2. <br />3. WHERE CONDUCTORS ARE INCREASED IN SIZE, FOR ANY REASON, THE <br />ELECTRICAL CONTRACTOR SHALL ENSURE THE OVERCURRENT DEVICES AND <br />TERMINATIONS WILL ACCEPT THE LARGER CONDUCTOR. WHERE THE <br />OVERCURRENT DEVICES OR TERMINATIONS WILL NOT ACCEPT THE LARGER <br />CONDUCTOR, THE ELECTRICAL CONTRACTOR SHALL PROVIDE THE NECESSARY <br />SPLICES AND ACCOMODATIONS TO REDUCE CONDUCTORS TO A SIZE THE DEVICE <br />OR EQUIPMENT MAY ACCEPT. <br />GENERAL NOTES – ONE LINES <br />COMMENCEMENT OF WORK NOTE <br />UPON COMMENCEMENT OF WORK, THE ELECTRICAL CONTRACTOR SHALL IMMEDIATELY <br />VERIFY ALL EXISTING CONDITIONS, AS THEY RELATE TO THE ONE-LINE DIAGRAM(S) AND <br />REPORT ANY AND ALL DISCREPANCIES TO 120 DEGREEZ ENGINEERING. THIS INCLUDES <br />OVERCURRENT PROTECTIVE DEVICE SIZE, TYPE, AND AIC RATINGS; WIRE SIZE, TYPE, <br />INSULATION, AND LENGTH; PANEL AND DISTRIBUTION EQUIPMENT SHORT CIRCUIT <br />CURRENT RATINGS; PANEL AND DISTRIBUTION EQUIPMENT SIZE IN AMPERES; PANEL <br />AND DISTRIBUTION EQUIPMENT PHASE AND VOLTAGE RATINGS; TRANSFORMER SIZE IN <br />KVA AND IMPEDANCE RATINGS; AND TO VERIFY LOCATION OF THE EXISTING <br />EQUIPMENT AND SYSTEMS. <br />THE ELECTRICAL CONTRACTOR IS ADVISED TO COORDINATE <br />WITH THE ENGINEER IN ADVANCE FOR ANY CHANGES FROM <br />THE DESIGN SHOWN HEREIN. ANY EVALUATION OF FIELD <br />CHANGES OR REWORK OF THE DRAWINGS DUE TO FIELD <br />CHANGES BY THE CONTRACTOR WILL BE SUBJECT TO <br />ADDITIONAL SERVICES FEES. APPROVAL BY THE ENGINEER <br />OF FIELD CHANGES MADE WITHOUT PRIOR COORDINATION <br />WILL BE AT THE SOLE DISCRETION OF THE ENGINEER. <br />1. REFER TO ELECTRICAL SHEET E0.00 FOR ADDITIONAL ELECTRICAL NOTES AND <br />ABBREVIATIONS. <br />2. ALL ITEMS SHOWN SHALL BE NEW. <br />3. ALL FEEDER LENGTHS SHOWN ARE FOR VOLTAGE DROP & SHORT CIRCUIT <br />CALCULATIONS ONLY. <br />4. MAIN SWITCHBOARD "MSA" BUS BRACING AND AIC RATING OF ALL DEVICES SHALL <br />BE 65kA. <br />5. DISTRIBUTION SYSTEM SHALL BE FULLY RATED. SERIES RATING IS NOT <br />PERMITTED. <br />6. REFER TO PANEL SCHEDULES FOR AIC RATINGS. <br />7. ALL GROUNDING CONNECTION TO THE COLD WATER PIPE SHALL BE MADE WITHIN <br />THE FIRST FIVE FEET OF THE WATER PIPE ENTRANCE TO THE BUILDING PER N.E.C. <br />ARTICLE 250-50. <br />8. ALL EQUIPMENT MOUNTED ON THE ROOF AND/OR EXTERNALLY TO BE NEMA 3R. <br />9. FURNISH A MINIMUM OF 25% SPARE BREAKERS AND A FURTHER 25% SPACE <br />UNLESS OTHERWISE NOTED ON THE PANEL SCHEDULES. <br />10. FURNISH AN ISOLATED GROUND OF EQUAL SIZE TO GROUND CONDUCTOR WHERE <br />APPLICABLE. <br />11. THIS DRAWING TAKES PRECEDENCE OVER PANEL SCHEDULES FOR PANEL AND <br />TRANSFORMER FEEDER SIZES. <br />12. PROVIDE SURGE PROTECTION IN COMPLIANCE WITH NFPA 780 AND C.E.C. <br />GENERAL NOTES <br />4 <br />2 3 <br />(R <br />E <br />C <br />O <br />N <br />N <br />E <br />C <br />T <br />) <br />(R <br />E <br />C <br />O <br />N <br />N <br />E <br />C <br />T <br /> <br />) <br />5 <br />1 <br />(E) <br />(E) <br />(E <br />) <br />(E <br />) <br />(E <br />) <br />(E <br />) <br />(E <br />) <br />6 <br />7 <br />FEEDER RACEWAY AND CONDUCTORS <br />NOTE <br />VOLTS <br />FED FROM <br />MOUNTING <br />ROOM <br />CBCIRCUIT DESCRIPTION <br />LOAD KVA <br /># <br />CKT BREAKER <br />TRIP/POLES A <br />NEUTRAL <br />BUS AMPS <br />AIC <br />MAIN BKR <br />LUGS <br />480Y/277V 3P 4W <br />FLOOR <br />MSA <br />UTILITY STANDARD <br />2000 <br />65,000 <br />2000 <br />100% <br />(2)3"C,3#400kcmil,#400kcmil N,#1/0G0700/31 0 0 <br />(2)4"C,3#500kcmil,#500kcmil N,#1/0G0700/32 0 0 <br />-0-/33 0 0 <br />-0-/34 0 0 <br />2"C,3#3/0,#3/0N,#6G0200/35 0 0 <br />-0-/36 0 0 <br />1-1/4"C,3#2,#8G0100/37 0 0 <br />-0-/38 0 0 <br />-0-/39 0 0 <br />TOTAL CONNECTED KVA BY PHASE 000 <br />CONN KVA CALC KVACALC KVA <br />FUTURE DEMAND 1,650 1,650 TOTAL LOAD 1,650 <br />BALANCED 3-PHASE LOAD 1,980 A <br />PANEL H1 <br />PANEL H2 <br />SPARE <br />SPARE <br />PANEL HA <br />SPARE <br />XFMR T3 <br />SPARE <br />SPARE <br />MSA 60,000 65,000 277V 60,000 0.004527 0.0009054 (8)#350kcmil 0.005 0.0076 0 0 <br />H1 35,130 50,000 277V 35,130 0.007234 0.003138 MSA 60,000 0.004527 0.0009054 (2)#400kcmil 0.02 0.0165 135' 0.0027 0.0022 <br />H2 25,318 35,000 277V 25,318 0.009911 0.004633 MSA 60,000 0.004527 0.0009054 (2)#500kcmil 0.0195 0.0135 276' 0.0054 0.0037 <br />HA 37,365 50,000 277V 37,365 0.006227 0.004022 MSA 60,000 0.004527 0.0009054 #3/0 0.042 0.077 40' 0.0017 0.0031 <br />T1 10,350 N/A 120V 10,350 0.01118 0.003076 HA 37,365 0.006227 0.004022 #1/0 0.044 0.12 15' 0.0007 0.0018 75 1.75 5 30,607 0.009884 0.001977 <br />LA 9,566 10,000 120V 9,566 0.01181 0.004232 T1 10,350 0.01118 0.003076 #3/0 0.042 0.077 15' 0.0006 0.0012 <br />LAA 8,736 10,000 120V 8,736 0.01235 0.006007 LA 9,566 0.01181 0.004232 #1 0.046 0.15 12' 0.0005 0.0018 <br />LAA1 7,966 10,000 120V 7,966 0.0129 0.007782 LAA 8,736 0.01235 0.006007 #1 0.046 0.15 12' 0.0005 0.0018 <br />T3 9,001 N/A 120V 9,001 0.01173 0.006342 MSA 60,000 0.004527 0.0009054 #2 0.045 0.19 118' 0.0053 0.0224 75 1.75 5 10,971 0.009884 0.001977 <br />HB 8,464 10,000 120V 8,464 0.0122 0.007215 T3 9,001 0.01173 0.006342 #3/0 0.042 0.077 11' 0.0005 0.0009 <br />8 <br />SERVICE ELEVATION DETAIL SCALE 2NONE <br />FENCE FOR SCREENING TRANSFORMER DETAIL SCALE 3NONE <br />NE <br />W <br /> <br />2 <br />0 <br />0 <br />0 <br />A <br /> <br />S <br />E <br />R <br />V <br />I <br />C <br />E <br />10 <br />0 <br />1 <br /> <br />S <br />. <br /> <br />G <br />R <br />A <br />N <br />D <br /> <br />A <br />V <br />E <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />5 <br />ARCHITECT: <br />CONSULTANTS: <br />SEAL & SIGNATURE: <br />ISSUED FOR: <br />DESCRIPTION:DATE: <br />KEY PLAN <br />SHEET NAME: <br />PROJECT NO.: <br />DRAWN BY: <br />CHECKED BY: <br />SCALE: <br />SHEET NO.: <br />Copyright 120DEGREEZ 2019c <br />NORTH <br />San Diego | Los Angeles <br />www.120degreez.com <br />619.323.1515 | 310.364.5228 <br />Mechanical | Electrical | Plumbing <br />MEP Project No.: 25−070