Laserfiche WebLink
DESIGN SPECIFICATIONS: ANSI/AISC 360-16 (15th ED); ACI 318-19; ASCE 7-16; ASTM F2376 (LATEST) <br />GOVERNING BUILDING CODE: 2022 CALIFORNIA BUILDING CODE (2021 IBC) <br />GRAVITY LOADING: <br />WATER SLIDE: <br />DEAD LOAD <br />42" OPEN FLUME = 50 plf <br />WATER LOAD <br />42" OPEN FLUME = 15 plf <br />RIDER (LIVE) LOAD <br />42" OPEN FLUME = 400 lbs <br />SNOW: GROUND SNOW LOAD = 0.0 psf <br /> RISK CATEGORY = II <br /> IMPORTANCE FACTOR = 1.0 <br />STAIRS AND LANDINGS <br /> DEAD LOAD = 15 psf <br /> LIVE LOAD = 100 psf <br />SEISMIC DESIGN FACTORS: <br /> SDS = 0.857g SS = 1.285g <br /> SD1 = 0.846g S1 = 0.460g <br /> SITE CLASS DEFINITION = D <br /> SEISMIC DESIGN CATEGORY E <br /> AMUSEMENT STRUCTURE NON BUILDING <br /> R= 2.0 <br /> RISK CATEGORY = II <br />WIND DESIGN <br /> UNOCCUPIED ULTIMATE WIND VELOCITY (RISK CAT. I) = 89 MPH (3 SECOND GUST) <br /> UNOCCUPIED ASD WIND VELOCITY (RISK CAT. I) = 69 MPH (3 SECOND GUST) <br /> OCCUPIED ULTIMATE WIND VELOCITY (RISK CAT. II) = 95 MPH (3 SECOND GUST) <br /> OCCUPIED ASD WIND VELOCITY (RISK CAT. II) = 74 MPH (3 SECOND GUST) <br /> EXPOSURE CATEGORY = C <br />GENERAL CONSTRUCTION NOTES: <br />1.ALL WORK SHALL COMPLY WITH THE GOVERNING LOCAL BUILDING CODE. <br />2.REFERENCE STANDARD: UNLESS OTHERWISE NOTED (U.O.N.), ALL STANDARDS SHALL BE CURRENT EDITION, WITH <br />LATEST ADDENDA, IF APPLICABLE. <br />3.THE CONTRACTOR SHALL VERIFY ALL CONTRACT DOCUMENTS, SITE ELEVATIONS, DIMENSIONS AND CONDITIONS PRIOR <br />TO STARTING WORK AND SHALL NOTIFY THE ENGINEER OF ANY DISCREPANCIES OR INCONSISTENCIES. <br />4.GROUNDING OF SLIDE STRUCTURE AND SUPPORTS SHALL BE DONE IN ACCORDANCE WITH THE PROJECT <br />SPECIFICATIONS AND THE LOCAL BUILDING CODE. GROUNDING NOT BY SPLASHTACULAR. <br />FOUNDATIONS: <br />1.FOUNDATIONS FOR THIS PROJECT HAVE BEEN DESIGNED IN ACCORDANCE WITH REQUIREMENTS SET FORTH IN THE <br />REPORT BY CONVERSE CONSULTANTS (CONVERSE PROJECT NO. 23-32-142-01, DATED JULY 30, 2024). INDIVIDUAL <br />SPREAD FOOTINGS HAVE BEEN DESIGNED TO BEAR ON TESTED AND APPROVED NATIVE SOIL OR ENGINEER FILL WITH A <br />NET ALLOWABLE BEARING PRESSURE OF 2500 PSF. REFER TO THE SOILS REPORT FOR ADDITIONAL INFORMATION AND <br />REQUIREMENTS. CONTRACTOR SHALL VERIFY THE SOIL BEARING PRESSURE PRIOR TO FOOTING CONSTRUCTION. THE <br />CONTRACTOR SHALL REFER TO THE GEOTECHNICAL REPORT FOR ALL REQUIREMENTS AND RECOMMENDATIONS <br />PERTINENT TO THIS PROJECT. PLEASE ALSO REFER TO SECTION 10.12 FOR GROUND IMPROVEMENT AND LIQUEFACTION <br />MITIGATION MEASURES. <br />2.ANCHOR BOLTS SHALL BE LOCATED BY MEANS OF A TEMPLATE. PROVIDE A NUT ABOVE AND BELOW TEMPLATE TO <br />ASSURE PROPER VERTICAL ALIGNMENT. TEMPLATE PATTERN PROVIDED BY SPLASHTACULAR. <br />3.ALL FOUNDATIONS SHALL BE SQUARE AND LEVEL. <br />4.GROUT BELOW COLUMN BASES PLATES. GROUT SHALL BE DRY AND STIFF TO PREVENT SHRINKAGE, WITH A MINIMUM <br />COMPRESSIVE STRENGTH OF 4000 PSI. THOROUGHLY COMPACT GROUT BENEATH BASE PLATE. CONTRACTOR TO <br />PROVIDE (2) 1 <br />2" Ø WEEP HOLES BETWEEN COLUMN BASE PLATE AND CONCRETE PEDESTAL TO ALLOW FOR DRAINAGE OF <br />COLUMN. (NOT BY SPLASHTACULAR CREWS) <br />EXCAVATION AND BACKFILL NOTES: <br />1.EXCAVATION AND BACKFILL SHALL BE EXECUTED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS. <br />2.BACKFILL AND COMPACTION SHALL BE INSPECTED AND CERTIFIED BY A LICENSED GEOTECHNICAL ENGINEER. <br />3.FOOTING EXCAVATIONS SHALL BE EXCAVATED TO PROPER LINE AND LEVEL TO ENSURE MINIMUM CONCRETE OVER A <br />FOOTING REINFORCEMENT FOR FOOTING DEPTH. <br />CONCRETE AND REINFORCING STEEL: <br />1.CONCRETE CONSTRUCTION SHALL CONFORM TO AMERICAN CONCRETE INSTITUTE (ACI) CODES AND SPECIFICATIONS, <br />LATEST EDITION. <br />ACI 301 "SPECIFICATIONS FOR STRUCTURAL CONCRETE" <br />ACI 315 "DETAILS AND DETAILING OF CONCRETE REINFORCEMENT" <br />ACI 318 "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE" <br />2.ALL CONCRETE FOR FOUNDATIONS SHALL BE NORMAL WEIGHT (150 PCF), 4000 PSI, 28 DAY COMPRESSIVE STRENGTH <br />WITH 5% TO 7% AIR ENTRAINMENT. <br />3.ALL CAST-IN-PLACE CONCRETE SHALL BE TESTED BY AN INDEPENDENT TESTING LABORATORY. SEE PROJECT <br />SPECIFICATIONS FOR REQUIREMENTS. CONTRACTOR SHALL RETAIN TEST RESULTS FOR DURATION OF CONSTRUCTION. <br />4.ALL CAST-IN-PLACE CONCRETE SHALL HAVE REACHED ITS DESIGN COMPRESSIVE STRENGTH PRIOR TO SLIDE STRUCTURE <br />INSTALLATION . CONTRACTOR TO PROVIDE TESTING RESULTS IF REQUESTED BY SPLASHTACULAR. <br />5.ALL REINFORCING STEEL SHALL BE GRADE 60 DEFORMED, BILLET-STEEL ASTM A615. U.O.N. . <br />6.CLEAR CONCRETE COVERAGE FOR ALL REINFORCING STEEL SHALL BE AS FOLLOWS, UNLESS OTHERWISE NOTED ON THE <br />DRAWING: <br />CONCRETE CAST ON SOIL 3" <br />FORMED CONCRETE EXPOSED TO EARTH OR WEATHER 2" <br />7.BARS MARKED CONTINUOUS AND ALL VERTICAL STEEL SHALL BE LAPPED OR EMBEDDED TO DEVELOP THE FULL TENSILE <br />CAPACITY OF THE BAR. LAPS SHALL BE AS SPECIFIED BELOW OR AS NOTED ON THE DESIGN DRAWINGS. <br />#3 25" LAP 8" HOOK <br />#4 25" LAP 8" HOOK <br />#5 25" LAP 10" HOOK <br />#6 37" LAP 12" HOOK <br />#7 54" LAP 14" HOOK <br />8.ALL BARS ARE TO BE SUPPORTED IN FORMS AND SPACED WITH WIRE BAR SUPPORTS PER ACI "MANUAL OF STANDARD <br />PRACTICE FOR DETAILING CONCRETE STRUCTURES" (LATEST EDITION). BARS SHALL BE SECURELY WIRED PER LATEST <br />EDITION OF CRSI RECOMMENDED PRACTICE FOR PLACING REINFORCING BARS. ACCESSORIES FOR EXPOSED CONCRETE <br />SHALL BE PLASTIC OR SHALL HAVE PLASTIC TIPPED FEET. <br />9.CONCRETE PLACE DURING COLD WEATHER SHALL CONFORM TO THE REQUIREMENTS OF ACI 306. COLD WEATHER IS <br />DEFINED AS A PERIOD WHEN, FOR MORE THAN 3 SUCCESSIVE DAYS THE MEAN DAILY TEMPERATURE DROPS BELOW 40 <br />DEGREES FAHRENHEIT. <br />10.CONCRETE PLACED DURING HOT WEATHER SHALL CONFORM TO THE REQUIREMENTS OF ACI 305. <br />11.ALL EDGES OF FORMED CONCRETE SHALL HAVE A 3 <br />4" CHAMFER U.N.O. <br />STRUCTURAL STEEL: <br />1.ALL STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING: <br />W SHAPE STEEL ASTM A992 GRADE 50 <br />CHANNELS, ANGLES, PLATE, & MISC STEEL ASTM A36 <br />STRUCTURAL TUBING RECTANGULAR SECTIONS ASTM A500, GRADE C (FY = 50 KSI) <br />STRUCTURAL TUBING HSS16.00 CIRCULAR ASTM A500, GRADE C (FY = 46 KSI) <br />STEEL PIPE AND 24" DIA x 0.25 ASTM A53, GRADE B (FY = 35 KSI) <br />BOLTS, STEEL TO STEEL A325N (SNUG TIGHT), A307N (SNUG TIGHT) <br />BOLTS, STEEL TO STEEL A325SC (FULLY PRETENSIONED), WHERE NOTED <br />ANCHOR BOLTS ASTM F1554 (FY = 36 KSI) <br />2.BOLT HOLES SHALL BE 1 <br />16" GREATER THAN BOLT SIZE (STANDARD HOLES), UNLESS NOTED OTHERWISE (U.N.O.). ALL BOLT <br />HOLES LARGER THAN THE STANDARD HOLE SHALL BE CONSIDERED OVERSIZED OR SLOTTED AND REQUIRE THE <br />INSTALLATION OF A WASHER. ALL BOLTS, NUTS, WASHERS AND STRUCTURAL STEEL SHALL BE HOT-DIP GALVANISED. <br />3.HARDENED WASHERS SHALL BE INSTALLED OVER ALL OVERSIZED OR SLOTTED HOLES. <br />4.WELDING SHALL CONFORM TO THE LATEST PUBLICATION OF APPLICABLE CODES SET FORTH BY THE AMERICAN <br />WELDING SOCIETY. WELDING ELECTRODES SHALL BE ER70S-6. <br />5.EXPANSION ANCHORS: SHALL BE HILTI "KWIK BOLT TZ" OR APPROVED EQUAL. INSTALL ANCHORS IN CONFORMANCE <br />WITH THE MANUFACTURER'S RECOMMENDATIONS. <br />6.ADHESIVE ANCHORS SHALL BE HILTI "RE 500 V3" OR APPROVED EQUAL. INSTALL ANCHORS IN CONFORMANCE WITH <br />THE MANUFACTURER'S RECOMMENDATIONS. <br />7.ERECTOR AND FABRICATOR SHALL FOLLOW ALL AISC STANDARDS AND PRACTICES WHICH PERTAIN TO THE WORK <br />HEREIN. <br />TREADS, LANDINGS, AND PLATFORM DECKING: <br />1.GRATING/DECKING FOR TREADS, LANDINGS AND PLATFORMS SHALL BE 1 5 <br />8" THICK WITH A NON SLIP WALKING <br />SURFACE. SEE SEPARATE SUBMITTAL FOR ADDITIONAL DETAILS. <br />PLATFORM COVER/CANOPY: (SEE CONTRACT FOR INCLUSION OR EXCLUSION OF THE SLIDE CANOPY) <br />1.CANOPY SHALL BE PROVIDED OVER SLIDE ENTRY PLATFORMS. COVER SHALL BE A PIPE FRAME WITH ACRYLIC FABRIC OR <br />WOVEN VINYL IMPREGNATED POLYESTER YARN. FABRIC SHALL BE ATTACHED TO PIPE FRAME USING WHITE STRAPS <br />AND SPRING CLIPS. <br />2.BOTTOM OF SHADE SHALL BE 7'6" ABOVE THE ENTRY TUB. <br />3.CANOPY LEGS SHALL FIT INTO SLEEVES AT CORNERS OF THE DECK. <br />4.CANOPY DESIGN TO BE IN CONFORMANCE WITH IBC SECTION 3105. <br />5.FABRIC CANOPIES SHALL BE REMOVED DURING WINTER MONTHS. CANOPIES ARE NOT DESIGNED FOR SNOW LOADING. <br />STRUCTUAL STEEL COATING: <br />1.ALL STRUCTURAL STEEL SHALL BE HOT DIPPED GALVANIZED. <br />2.ON ALL PAINTED PROJECTS, THE STRUCTURAL STEEL WILL HAVE A POWDER COATED FINISH. <br />SPECIAL INSPECTIONS: <br />1.THE OWNER, ARCHITECT OR THE ENGINEER OF RECORD ACTING AS THE OWNERS AGENT SHALL EMPLOY ONE OR MORE <br />SPECIAL INSPECTORS TO PROVIDE INSPECTIONS FOR: <br />1.1.CONCRETE <br />1.1.1.CONTINUOUS: ANCHOR BOLT, TEST SAMPLE, SLUMP, TEMPERATURE <br />1.1.2. PERIODIC: REINFORCING STEEL, PLACEMENT, DESIGN MIX, CURING, FORM WORK <br />1.2.STEEL (AS REQUIRED TO MEET STATE/CITY BUILDING CODE AND QUALITY REQUIREMENTS) <br />1.2.1. CONTINUOUS: SLIP CRITICAL CONNECTION, FULL PENETRATION WELD <br />1.2.2.PERIODIC: IDENTIFICATION MARK, MANUFACTURER'S CERTIFICATION, BEARING TYPE CONNECTION, FILLET <br />WELDS <br />1.3.SOIL <br />1.3.1.CONTINUOUS: BEARING CAPACITY <br />1.3.2. PERIODIC: FOUNDATION DEPTH <br />2.THE SPECIAL INSPECTOR SHALL BE A QUALIFIED PERSON WHO SHALL DEMONSTRATE COMPETENCE TO THE <br />SATISFACTION OF THE BUILDING OFFICIAL FOR INSPECTION OF THE ITEMS LISTED ABOVE. <br />3.THE SPECIAL INSPECTOR SHALL FURNISH AND SUBMIT A FINAL INSPECTION REPORT TO THE BUILDING OFFICIAL, THE <br />ENGINEER OR ARCHITECT OF RECORD. <br />4.ANY COST ASSOCIATED WITH PROVIDING THE ABOVE INSPECTIONS INCLUDING SHOP INSPECTIONS AND MATERIAL <br />TESTING SHALL BE BY THE OWNER, ARCHITECT OR ENGINEER ACTING AS THE OWNER'S AGENT. NOT BY <br />SPLASHTACULAR. <br />FIBERGLASS FASTENER SPECIFICATIONS: <br />2. 3/8" x 1 1/2" S.S. FASTENERS AT ALL FLUME SECTION JOINTS <br />3. 1/2" x 3" GALVANIZED FASTENERS AT FLUME ARM MOUNTING PLATES <br />FIBERGLASS FLUME SPECIFICATIONS: <br />1. 20 MILS MIN OF SPRAY LAY-UP ISOPHTHALIC NEOPENTYL GLYCOL (ISO-NPG) GEL COAT W/ UV INHIBITORS, INTERIOR & <br />EXTERIOR <br />2. LAMINATE THICKNESS OF 1/4" NOMINAL SPRAY/CHOP LAY-UP THROUGHOUT ENTIRE BODY <br />3. GLASS-TO-RESIN RATIO OF APPROXIMATELY 35 TO 65 <br />4. FLANGE THICKNESS OF 1/4" NOMINAL <br />5. ONE (1) LAYER OF 18 OZ. WOVEN ROVING THROUGHOUT THE BODY OF FLUME AND BETWEEN LAYERS OF CHOP <br />6. REVERSE SIDES SANDED TO BE FREE OF BURRS AND SPRAYED TO A NON-POROUS FINISH WITH AN ISO-NPG GEL COAT <br />CONTAINING A HI-GLOSS GEL COAT ADDITIVE (DURATEC) <br />7. ALL EDGES WET-TRIMMED AND HAND-SANDED TO DULL, ROUNDED EDGE AND FINISH WITH AN ISO-NPG GEL COAT <br />CONTAINING DURATEC <br />FIBERGLASS STARTER TUB SPECIFICATIONS: <br />1. ALL OF THE ABOVE FLUME SPECIFICATIONS APPLY, EXCEPT AS NOTED <br />2. STARTER TUB LAMINATE THICKNESS IS 1/4" TO 5/16" OF SPRAY/CHOP LAY-UP THROUGHOUT THE ENTIRE BODY <br />3. FLOOR AND RIDING SURFACE ONLY IS REINFORCED WITH A NON-COMPRESSING CORE MATERIAL, OF NOT LESS THAN <br />3/8" THICK TO WITHIN 4" OF THE ATTACHMENT FLANGE, AND COVERED WITH NOT LESS THAN 1/8" SPRAY/CHOP <br />LAMINATE. <br />TITLE: <br />DATE: <br />SCALE: <br />GENERAL NOTES <br />NTS S1.0 <br />The Structural Support System, <br />foundations, decking/treads, <br />fiberglass components including a <br />finite analysis of the ride path <br />depicted on these drawings were <br />designed under the direction of the <br />Professional Engineer who's seal <br />and signature are affixed to this <br />drawing. Any structural design <br />connections of the slide <br />components that are connected to <br />a building are not by Splashtacular. <br />This document is the intellectual <br />property of Splashtacular, LLC, which <br />has exclusive rights to proprietary <br />trade secrets and confidential <br />information contained herein. Receipt <br />of permission to use this document <br />does not convey any rights to use the <br />information contained herein without <br />prior written consent of <br />Splashtacular, LLC. <br />REVISION HISTORYDATEMARK APPROVED <br />04/15/2025 ISSUED FOR APPROVAL <br />1 06/02/2025 ISSUED FOR APPROVAL - REVISE AND RESUBMIT 1 <br />2 07/10/2025 ISSUED FOR APPROVAL - REVISE AND RESUBMIT 2 <br />07/25/2025 ISSUED FOR CONSTRUCTION <br />C <br />PROJECT NUMBER: <br />TITLE: <br />PROJECT: <br />DATE: <br />STATE: <br />COUNTRY: <br />APPROVED:CHECKED:CITY: <br />DESIGNER:SCALE: <br />MEMORIAL PARK <br />11525 USA <br />CA <br />SANTA ANA <br />03/27/2025 <br />GLC <br />DBG/DAR RRR <br />2025 - Splashtacular, LLC - All Rights Reserved. <br />W a t e r s l i d e s a n d W a t e r p a r k A t t r a c t i o n s <br />401 N.East Street • Paola, Kansas 66071 <br />P 800.844.5334 • F 913.294.2496 <br />® <br />GENERAL NOTES <br />08/14/25