ELEVATORS AND CONVEYING SYSTEMS <br />3005.2 Escalators and moving walks. Escalators and mov- <br />ing walks shall be constructed of approved noncombustible <br />and fire-retardant materials. This requirement shall not apply <br />to electrical equipment, wiring, wheels, handrails and the use <br />of 1/28-inch (0.9 mm) wood veneers on balustrades backed up <br />with noncombustible materials. <br />3005.2.1 Enclosure. Escalator floor openings shall be <br />enclosed with shaft enclosures complying with Section <br />713. <br />3006.4 Machine rooms and machinery spaces. Elevator <br />machine rooms and machinery spaces shall be enclosed with <br />fire barriers constructed in accordance with Section 707 or <br />horizontal assemblies constructed in accordance with Section <br />711, or both. The fire-resistance rating shall be not less than <br />the required rating of the hoistway enclosure served by the <br />machinery. Openings in the fire barriers shall be protected <br />with assemblies having a fire protection rating not less than <br />that required for the hoistway enclosure doors. <br />3005.2.2 Escalators. Where provided in below-grade <br />transportation stations, escalators shall have a clear width <br />of not less than 32 inches (815 mm). <br />Exception: The clear width is not required in existing <br />facilities undergoing alterations. <br />3005.3 Conveyors. Conveyors and conveying systems shall <br />comply with ASME B20.1. <br />3005.3.1 Enclosure. Conveyors and related equipment <br />connecting successive floors or levels shall be enclosed <br />with shaft enclosures complying with Section 713. <br />3005.3.2 Conveyor safeties. Power-operated conveyors, <br />belts and other material-moving devices shall be equipped <br />with automatic limit switches which will shut off the <br />power in an emergency and automatically stop all opera- <br />tion of the device. <br />3005.4 Personnel and material hoists. Personnel and mate- <br />Mal hoists shall be designed utilizing an approved method that <br />accounts for the conditions imposed during the intended <br />operation of the hoist device. The design shall include, but is <br />not limited to, anticipated loads, structural stability, impact, <br />vibration, stresses and seismic restraint. The design shall <br />account for the construction, installation, operation and <br />inspection of the hoist tower, car, machinery and control <br />equipment, guide members and hoisting mechanism. Addi- <br />tionally, the design of personnel hoists shall include provi- <br />sions for field testing and maintenance which will <br />demonstrate that the hoist device functions in accordance <br />with the design. Field tests shall be conducted upon the corn- <br />pletion of an installation or following a major alteration of a <br />personnel hoist. <br />SECTION 3006 <br />MACHINE ROOMS <br />3006.1 Access. An approved means of access shall be pro- <br />vided to elevator machine rooms and overhead machinery <br />spaces. <br />3006.2 Venting. Elevator machine rooms that contain solid- <br />state equipment for elevator operation shall be provided with <br />an independent ventilation or air-conditioning system to pro- <br />tect against the overheating of the electrical equipment. The <br />system shall be capable of maintaining temperatures within <br />the range established for the elevator equipment. <br />3006.3 Pressurization. The elevator machine room serving a <br />pressurized elevator hoistway shall be pressurized upon acti- <br />vation of a heat or smoke detector located in the elevator <br />machine room. <br />Exceptions: <br />1. Where machine rooms and machinery spaces do not <br />abut and have no openings to the hoistway enclosure <br />they serve the fire barriers constructed in accordance <br />with Section 707 or horizontal assemblies con- <br />structed in accordance with Section 711, or both, <br />shall be permitted to be reduced to a 1-hour fire- <br />resistance rating. <br />2. In buildings four stories or less above grade plane <br />where machine room and machinery spaces do not <br />abut and have no openings to the hoistway enclosure <br />they serve, the machine room and machinery spaces <br />are not required to be fire-resistance rated. <br />3006.4.1 Automatic sprinkler system. Automatic sprin- <br />klers shall not be required to be installed in the elevator <br />hoistway, elevator machine room, elevator machinery <br />space, elevator control space, or elevator control room <br />where all the following are met: <br />1. Approved smoke detectors shall be installed in the <br />elevator hoistway, elevator machine room, elevator <br />machinery spaces, elevator control spaces, or eleva- <br />tor control rooms and connected to the building fire <br />alarm system in accordance with Section 907. <br />2. Activation of any smoke detector located in the ele- <br />vator hoistway, elevator machine room, elevator <br />machinery space, elevator control space, or elevator <br />control room shall cause the actuation of the build- <br />ing fire alarm notijication appliances in accordance <br />with Section 907. <br />3. Activation of any smoke detector located in the ele- <br />vator hoistway, elevator machine room, elevator <br />machinery space, elevator control space, or elevator <br />control room shall cause all elevators having any <br />equipment located in that elevator hoistway, eleva- <br />tor machine room, elevator machinery space, eleva- <br />tor control space, or elevator control room to recall <br />nonstop to the appropriate designated floor in <br />accordance with CCR Title 8, Division 1, Chapter 4, <br />Subchapter 6, Elevator Safety Orders. <br />4. The elevator machine room, elevator machinery <br />space, elevator control space, or elevator control <br />room shall be enclosed with fire barriers con- <br />structed in accordance with Section 707 or horizon- <br />tal assemblies constructed in accordance with <br />Section 712, or both. The fire-resistance rating shall <br />not be less than the required rating of the hoistway <br />enclosure served by the machinery. Openings in the <br />fire barriers shall be protected with assemblies hav- <br />416 2013 CALIFORNIA BUILDING CODE