E100
<br />MINIMUM
<br />MOUNTED
<br />MIN
<br />MTD
<br /> - M -
<br />MAIN CIRCUIT BREAKER
<br /> - K -
<br />KILOWATT
<br /> - L -
<br />LIGHTING CONTROL PANEL
<br />KILOVOLT AMPERE
<br />MCB
<br />LCP
<br />KW
<br />KVA
<br />VM VOLTMETER
<br />WEATHERPROOF
<br /> - W -
<br />WP
<br />W WATT
<br /> - U -
<br />VOLT AMPERE
<br />VOLT OR VOLTAGE
<br /> - V -
<br />UNLESS OTHERWISE NOTED
<br />V
<br />VA
<br />TYP
<br />UON
<br />TYPICAL
<br />GROUND FAULT INTERRUPTER
<br />INSTRUMENT
<br />INCANDESCENT
<br /> - I -
<br />IC
<br />GROUND
<br />INTERRUPTING CAPACITY
<br />JUNCTION BOX
<br /> - J -
<br />INST
<br />INCAND
<br />JB
<br />SECTION
<br />SINGLE POLE
<br />GRD
<br /> - G -
<br />G, GFI,
<br />GFCI
<br />SECT
<br /> - T -
<br />TRANSF
<br />SPECIFICATION
<br />SWITCHBOARD
<br />TRANSFORMER
<br />TELEVISION
<br />TELEPHONE
<br />SW
<br />SWBD
<br />TEL
<br />TV
<br />SP
<br />SPEC
<br />SWITCH
<br /> - S -
<br />SCHEDULESCHED
<br />FLUSH WALL MOUNTED JUNCTION BOX
<br />TYPE B - UON.
<br />COMBINATION MOTOR CONTROLLER AND
<br />UNFUSED DISCONNECT SWITCH-
<br />MOTOR RATED TOGGLE SWITCH +44" TYP.
<br />TRANSFORMER
<br />MOTOR
<br />3/4" CONDUIT WITH 4#12+1#12EG., U.O.N.
<br />1/2" CONDUIT WITH 3#12+1#12EG., U.O.N.
<br />1/2" CONDUIT WITH 2#12+1#12EG., U.O.N.
<br />FLUSH MOUNTED PANELBOARD
<br />SURFACE MOUNTED PANELBOARD
<br />CONDUIT HOMERUN 3/4"C MIN. (U.N.O.)
<br />GROUND CONNECTION
<br />CEILING MOUNTED JUNCTION BOX.
<br />CIRCUIT BREAKER-100 AMP FRAME/100AMP
<br />TRIP, 3 POLE UON
<br />POWER TRANSFORMER, DISTRIBUTION
<br />GROUND FAULT RELAY
<br />CONCEALED CONDUIT
<br />FLUSH WALL MONTED DUPLEX CONVENIENCE
<br />RECEPTACLE AT +15" TO BOTTOM OF OUTLET.
<br />FLUSH WALL MONTED QUADRUPLEX CONVENIENCE
<br />RECEPTACLE AT +15" TO BOTTOM OF OUTLET.
<br />EXISTING TO REMAIN
<br />(N)
<br />(E)
<br />INDICATES NEW
<br />INDICATES "GROUND FAULT INTERRUPT"
<br />INDICATES "SEPARATE 20 AMP. CIRCUIT"
<br />INDICATES 24-HR NIGHT LIGHT WITH 90 MIN. BACK-UP BATTERY
<br />FUSE, UNFUSED EXCEPT WHERE FUSE SIZE IS
<br />DISCONNECT SWITCH-100A SWITCH, 60A
<br />INDICATED 3 POLE EXCEPT WHERE NOTED
<br />LTG
<br />CABINET
<br />LIGHTING
<br />CONT
<br />CLOS
<br />CLG
<br />CLOSET
<br />CB
<br />CIRCUIT
<br />ABOVE FINISHED FLOOR
<br />C
<br />INDICATES RELOCATED
<br /> - B -
<br />(R)
<br />CAB
<br />ALUMINUM
<br />A
<br />CURRENT TRANSFORMERCT
<br /> - A -
<br />CU
<br />FT
<br />COMM
<br />FL
<br />FEET OR FOOT
<br />CKT
<br />CAT
<br />CONTINUATION
<br />FDR
<br />FIXT
<br />COMMUNICATION
<br />COPPER
<br />EMER
<br />CIRCUIT BREAKER
<br />ELEC
<br />CATALOG
<br />CEILING
<br />FUSE
<br />FIXTURE
<br />AMERICAN WIRE GAUGE
<br />AFF
<br />BLDG.
<br />EQUIPMENT
<br />AL
<br />ELEVATION
<br />AWG
<br />DIAMETER
<br />AH
<br />BUILDING
<br />EG
<br />CONDUIT
<br /> - C -
<br />DN
<br />AMPERE-HOUR
<br />DIST
<br /> - E -
<br />DISC
<br />AMPERE
<br />EQUIPMENT GROUND
<br />ELECTRICAL CLOSET
<br />FLOOR
<br />EACH
<br />DISCONNECT
<br />DISTRIBUTION
<br />EXIST, (E)
<br />DOWN
<br />DRAWING
<br />F
<br />EL
<br />DEGREE
<br />ROOM
<br /> - D -
<br />EQUIP
<br />REQUIRED
<br /> - F -
<br />RECEPTACLERECEPT
<br />FEEDER
<br />REQD
<br />RM
<br />EMERGENCY
<br />ELECTRICAL
<br />OWNER FURNISH AND
<br />POLE
<br />EXISTING
<br />DIA
<br />POWER
<br />PANEL
<br />EA
<br />EC
<br />PNL
<br />DWG PWR
<br />Ø, PH
<br />PB
<br />P
<br />OFOI
<br />NORMALLY CLOSEDNC
<br />NORMALLY OPEN
<br />NON-FUSED
<br />NOT IN CONTRACT
<br /> - O -
<br />DEG
<br />OUTSIDE DIAMETER
<br />NOT TO SCALE
<br />ON CENTER
<br />OD
<br />NTS
<br />OC
<br />NIC
<br />NO
<br /> - R -
<br />NF
<br />OWNER INSTALL
<br />NEUTRAL
<br /> - N -
<br /> - P -
<br />PULL BOX
<br />NL
<br />N
<br />NIGHT LIGHT
<br />PHASE
<br />DEVICE MOUNTING HEIGHT
<br />SCALE:
<br />NONE 1
<br />1. PROVIDE ALL LABOR, MATERIALS, INSURANCE, EQUIPMENT, INSTALLATION,
<br />CONSTRUCTION TOOLS, TRANSPORTATION, ETC. FOR A COMPLETE AND PROPERLY
<br />OPERATING ELECTRICAL SYSTEM.
<br />2. CONSTRUCTION TERMINOLOGY, AND THE STANDARDS AND ACCEPTABLE METHODS OF
<br />INSTALLATION REQUIRED BY THESE CONTRACT DOCUMENTS ARE BASED ON PUBLISHED
<br />STANDARDS OF N.E.C.A. (NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION), NATIONAL
<br />ELECTRICAL SAFETY CODE, AMERICAN NATIONAL STANDARDS INSTITUTE DOCUMENTS,
<br />NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION, UNDERWRITERS LABORATORIES,
<br />AND THE CALIFORNIA ELECTRICAL CODE. SUBMITTAL OF BID INDICATES THE CONTRACTOR
<br />IS COGNIZANT OF THESE STANDARDS AND THE REQUIREMENTS NECESSARY TO PERFORM
<br />ALL THE WORK AS SET FORTH IN THESE CONTRACT DOCUMENTS.
<br />3. SECURE ALL NECESSARY ELECTRICAL PERMITS, UTILITY CHARGES AND PAY FOR SAME.
<br />COORDINATE AND PAY FOR ALL TEMPORARY ELECTRICAL SERVICE, CHARGES WITH THE
<br />SERVING UTILITY, AND OWNER. COORDINATE TEMPORARY CONSTRUCTION
<br />REQUIREMENTS WITH ALL TRADES PRIOR TO CONSTRUCTION.
<br />4. THESE PLANS ARE DIAGRAMMATIC ONLY, FOLLOW AS CLOSELY AS POSSIBLE AND REFER
<br />TO ARCHITECTURAL DRAWINGS FOR DETAILS, EXACT EQUIPMENT AND OUTLETS
<br />LOCATIONS. ALTHOUGH NOT SHOWN, CONTRACTOR SHALL PROVIDE ALL J-BOXES,
<br />PULL-BOXES, ELLS, OFFSETS, ETC., FOR COMPLETE CODE APPROVED INSTALLATION.
<br />FOOTAGE SHOWN ON ELECTRICAL SINGLE LINES AND RISER DIAGRAMS ARE FOR
<br />CALCULATION PURPOSES ONLY AND ARE NOT FOR BIDDING PURPOSES OR MATERIAL
<br />TAKEOFF. ALL LOCATIONS OF EVERY EQUIPMENT, DEVICES, OUTLETS, ETC. SHALL BE
<br />VERIFIED PRIOR TO ROUGH-IN.
<br />5. THE CONNECTION METHOD SHOWN IS FOR BIDDING PURPOSES. THE CONTRACTOR SHALL
<br />COORDINATE AND PROVIDE FROM ACTUAL BUILDING SHOP DRAWING, THE CONNECTION
<br />SHOWN ON THOSE DRAWINGS.
<br />6. ALL MATERIALS SHALL BE NEW (U.O.N.) AND OF THE SAME MANUFACTURER FOR EACH
<br />CLASS OF GROUP OF EQUIPMENT. MATERIALS SHALL BE LISTED AND APPROVED BY
<br />UNDERWRITER'S LABORATORIES FOR THE USE AND ENVIRONMENT, AND SHALL BEAR THE
<br />INSPECTION LABEL WHERE SUBJECT TO SUCH APPROVAL. MATERIALS SHALL MEET WITH
<br />THE APPROVAL OF THE DIVISION OF INDUSTRIAL SAFETY, AND ALL GOVERNING BODIES
<br />HAVING JURISDICTION. MATERIALS SHALL BE MANUFACTURED IN ACCORDANCE WITH
<br />APPLICABLE STANDARDS ESTABLISHED BY A.N.S.I., U.L., AND N.E.M.A. INSTALL PER
<br />MANUFACTURERS' RECOMMENDATIONS. ALL EXTERIOR EQUIPMENT SHALL BE
<br />WEATHERPROOF.
<br />7. ALL CONDUITS SHALL BE CONCEALED WHERE PHYSICALLY POSSIBLE CONNECTIONS
<br />SHALL BE COMPRESSION TYPE ONLY.
<br />8. CONTRACTOR SHALL PERFORM HIS WORK IN ACCORDANCE WITH ALL GOVERNING STATE,
<br />COUNTY, LOCAL CODES, O.S.H.A. AND THE PRESENTLY ADOPTED CALIFORNIA ELECTRICAL
<br />CODE (2022 CEC) . ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN A NEAT AND
<br />WORKMANLIKE MANNER (CEC 2022 SECTION110.12)
<br />9. THE COMPLETE ELECTRICAL SYSTEM SHALL BE GROUNDED IN ACCORDANCE WITH THE
<br />PRESENTLY ADOPTED EDITION OF THE C.E.C. ARTICLE #250, AND SHOWN ON THE
<br />DRAWINGS. AT THE REQUEST OF AND IN THE PRESENCE OF THE AUTHORIZED INSPECTOR,
<br />THE CONTRACTOR SHALL PROVIDE SYSTEM RESISTANCE READINGS.
<br />10. UNLESS NOTES OTHERWISE, CONDUCTORS SHALL BE CODE GRADE, 600 VOLT CLASS,
<br />MARKED 24" ALONG IT'S LENGTH SHOWING MANUFACTURER'S NAME, MAXIMUM
<br />ALLOWABLE VOLTAGE AND SIZE. CONDUCTORS SHALL BE COPPER TYPE "THWN" (WET) OR
<br />"THHN" (DRY). DELIVER THE WIRE TO THE SITE IN UNBROKEN PACKAGES. ALUMINUM
<br />CONDUCTORS ARE NOT ALLOWED.
<br />11. ALL CONDUIT ONLY (C.O.) SHALL INCLUDE A PULL WIRE.
<br />12. ALL FEEDER AND BRANCH HOMERUNS GREATER THAN 100' SHALL BE INCREASED IN SIZE
<br />AS REQUIRED TO COMPENSATE FOR VOLTAGE DROP. VOLTAGE DROP SHALL NOT EXCEED
<br />3%.
<br />13. PROVIDE TYPEWRITTEN PANEL SCHEDULES ON NEW AND REVISED PANELBOARDS.
<br />14. RE-USE EXISTING CIRCUIT BREAKERS IN PANELS. PROVIDE NEW AS REQUIRED BY
<br />SCHEDULES.
<br />15. IDENTIFICATION NAMEPLATES SHALL BE MICARTA 1/8 INCH THICK AND OF APPROVED
<br />SIZE WITH BEVELED EDGES AND ENGRAVED WHITE LETTERS A MINIMUM OF 1/4 INCH
<br />HIGH ON BLACK BACKGROUND. NAMEPLATES SHALL BE PROVIDED FOR ALL CIRCUITS IN
<br />THE SERVICE DISTRIBUTION AND POWER DISTRIBUTION SWITCHBOARDS OR
<br />PANELBOARDS, CENTERS, LIGHTING DISTRIBUTION PANELBOARDS, DISCONNECT
<br />SWITCHES, TRANSFORMERS, TERMINAL CABINETS, ETC. ALL NAMEPLATES SHALL BE
<br />ATTACHED WITH SCREWS. PULL BOXES, JUNCTION BOXES AND DEVICE BOXES SHALL BE
<br />MARKED WITH A PERMANENT MARKER.
<br />16. MAXIMUM NUMBER OF CONDUCTORS IN OUTLET OR JUNCTION BOXES SHALL CONFORM
<br />TO THE CALIFORNIA ELECTRICAL CODE ARTICLE 314.16.
<br />17. WHENEVER A DISCREPANCY IN QUANTITY OR SIZE OF CONDUIT, WIRE, EQUIPMENT
<br />DEVICES, CIRCUIT BREAKERS, GROUND FAULT PROTECTION SYSTEMS, ETC. (ALL
<br />MATERIALS), ARISES ON THE DRAWINGS OR SPECIFICATIONS, THE CONTRACTOR SHALL
<br />BE RESPONSIBLE FOR PROVIDING AND INSTALLING ALL MATERIAL AND SERVICES
<br />REQUIRED BY THE STRICTEST CONDITIONS NOTED ON THE DRAWINGS OR IN THE
<br />SPECIFICATIONS TO ENSURE COMPLETE AND OPERABLE SYSTEMS AS REQUIRED BY THE
<br />OWNER AND ARCHITECT/ENGINEER. EXACT METHOD AND LOCATION OF CONDUIT
<br />PENETRATION AND OPENINGS IN CONCRETE WALLS OR FLOORS OR STRUCTURAL STEEL
<br />MEMBERS SHALL BE AS DIRECTED BY THE STRUCTURAL ENGINEER. PERFORM CORING,
<br />SAWCUTTING, PATCHING, AND REFINISHED OF WALLS AND SURFACES WHEREVER IT IS
<br />NECESSARY TO PENETRATE. OPENINGS SHALL BE SEALED IN AN APPROVED METHOD TO
<br />MEET THE FIRE RATING OF THE PARTICULAR WALL, FLOOR OR CEILING.
<br />18. EXACT METHOD AND LOCATIONS OF CONDUIT PENETRATIONS AND OPENINGS IN
<br />CONCRETE WALLS OR FLOORS SHALL BE UL APPROVED.
<br />19. THE CONTRACTOR SHALL INSTALL EQUIPMENT GREEN GROUNDING CONDUCTOR SIZED
<br />PER CEC TABLE 250.122 IN ALL CONDUITS.
<br />20. THE CONTRACTOR SHALL COORDINATE HIS WORK WITH OTHER TRADES AT THE SITE.
<br />ANY COSTS TO INSTALL WORK TO ACCOMPLISH SAID COORDINATION WHICH DIFFERS
<br />FROM THE WORK AS SHOWN ON THE DRAWINGS SHALL BE INCURRED BY THE
<br />CONTRACTOR. ANY DISCREPANCIES, AMBIGUITIES OR CONFLICTS SHALL BE BROUGHT
<br />TO THE ATTENTION OF THE ARCHITECT DURING BID TIME FOR CLARIFICATION. ANY SUCH
<br />CONFLICTS NOT CLARIFIED PRIOR TO BID SHALL BE SUBJECT TO THE INTERPRETATION
<br />OF THE ARCHITECT AT NO ADDITIONAL COST TO THE OWNER.
<br />21. ROUTE EXPOSED CONDUIT AND CONDUIT AT CEILING SPACES PARALLEL AND
<br />PERPENDICULAR TO WALLS AND ADJACENT PIPING. ARRANGE CONDUIT TO MAINTAIN
<br />HEADROOM AND TO PRESENT A NEAT APPEARANCE.
<br />22. ALL FUSE PROTECTION DEVICES OF ALL EQUIPMENT SHALL CONFORM TO THE LISTING
<br />OF THE NAMEPLATE RATING OF THE EQUIPMENT.
<br />23. ALL EQUIPMENT DISCONNECT SWITCHES AND CONTROLLER LOCATIONS SHALL BE
<br />VERIFIED WITH OWNER'S REPRESENTATIVE PRIOR TO ROUGH-IN.
<br />24. ALL EQUIPMENT, DEVICES, CONDUIT AND WIRING SHOWN ARE NEW UNLESS OTHERWISE
<br />NOTED.
<br />25. PROVIDE PANEL CIRCUIT DIRECTORY AND FEEDER SOURCE IDENTIFICATION AT
<br />PANELBOARDS PER CEC 408.4.
<br />26. EACH CIRCUIT SHALL CONTAIN A DEDICATED NEUTRAL CONDUCTOR.
<br />27. CONDUCTORS OF A MULTI-WIRE BRANCH CIRCUIT SHALL ORIGINATE FROM THE SAME
<br />PANELBOARD. THE BRANCH CIRCUIT SHALL BE PROVIDED WITH A MEANS THAT WILL
<br />SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED CONDUCTORS AT THE POINT WHERE
<br />THE BRANCH CIRCUIT ORIGINATES.
<br />TOTAL
<br />WATTAGE REMARKVOLTLAMP TYPEDESCRIPTION
<br />TYPE
<br />FIXTURE MANUFACTURER/
<br />MODEL NUMBERSYMBOLS
<br />NOTES:
<br />1. ALL LAMPS INCLUDED.
<br />33.22x4 LED DLIGHT FIXTURE RECESSED IN
<br />T-BAR GRID CEILINGA LEDMVOLT
<br />3.7SPEC: (MATCH BUILDING STANDARD)
<br />E100 SYMBOL LIST, GENERAL NOTES AND ABBREVIATIONS
<br />POWER, AND LIGHTING PLANS
<br />E101
<br />E200
<br />SINGLE LINE DIAGRAM AND PANEL SCHEDULES
<br />LED EXIT SIGN WITH 90 MINUTES EMERGENCY
<br />BATTERY BACK-UP
<br />0-10V DIMMING.
<br />CONTROL BOX
<br />3'
<br />-
<br />1
<br />0
<br />"
<br />
<br />M
<br />A
<br />X
<br />.
<br />
<br />P
<br />A
<br />R
<br />A
<br />L
<br />L
<br />E
<br />L
<br />
<br />A
<br />P
<br />P
<br />R
<br />O
<br />A
<br />C
<br />H
<br />2'
<br />-
<br />1
<br />0
<br />"
<br />
<br />M
<br />A
<br />X
<br />.
<br />3'
<br />-
<br />6
<br />"
<br />SWITCH, OUTLET,
<br />THERMOSTAT,2'-0"
<br />MAX.
<br />3'
<br />-
<br />8
<br />"
<br />
<br />M
<br />A
<br />X
<br />.
<br />
<br />P
<br />E
<br />R
<br />P
<br />E
<br />N
<br />D
<br />I
<br />C
<br />U
<br />L
<br />A
<br />R
<br />
<br />A
<br />P
<br />P
<br />R
<br />O
<br />A
<br />C
<br />H
<br />TOP OF
<br />2022 CBC 11B-308.2.1
<br />2022 CBC 11B-308.3.1
<br />2022 CBC 11B-308.2.2
<br />2022 CBC 11B-308.3.2
<br />SWITCH, OUTLET,
<br />THERMOSTAT,
<br />TOP OF
<br />CONTROL BOX
<br />TO BOTTOM
<br />15"MIN
<br />OF BOX
<br />(4
<br />'
<br />-
<br />0
<br />"
<br />
<br />M
<br />A
<br />X
<br />.
<br />)
<br />LIGHTING NOTES:
<br />CONTRACTOR TO INSTALL EXTRA HOT WIRE ALL THE WAY TO THE
<br />SOURCE FOR THE UNSWITCHED LEG, WHEREVER A LIGHT FIXTURE
<br />EQUIPPED WITH AN EMERGENCY BATTERY OCCURS.
<br />THE CONTRACTOR SHALL PROVIDE ALL LOW VOLTAGE CONTROL CABLE
<br />AS REQUIRED FOR COMPLETE INSTALLATION AND OPERATION.
<br />TELEPHONE AND DATA SYSTEM NOTES:
<br />TELEPHONE SYSTEM AND DATA NETWORKING AND CABLING
<br />SYSTEM IS AN OWNER FURNISHED SYSTEM. CONTRACTOR
<br />TO PROVIDE CONDUIT ONLY WITH PULL CORD.
<br />NOTE:
<br />SYMBOLS SHOWN ARE NOT
<br />NECCESARILY USED FOR
<br />THIS PROJECT.
<br />SAME AS TYPE "A" EXCEPT WITH 90 MINUTES
<br />EMERGENCY BATTERY BACK-UP
<br />AE
<br />LED277
<br />SPEC: LITHONIA "STAK"
<br />#2x4-4000L-80CRI-35K-COL-MIN10-MVOLT
<br />(OR SIMILAR TO MATCH EXISTING)
<br />ET24 TITLE 24 LIGHTING AND MANDATORY MEASURES
<br />Sheet Title
<br />Sheet Number
<br />Project Number
<br />TOWER 1851
<br />1851 E. First
<br />St.
<br />Santa Ana, Ca. 92705
<br />DGC
<br />EXPANSION
<br />SUITE 640
<br />TENANT
<br />PROJECT
<br />REVISIONS
<br />DESCRIPTION DATENO.
<br />DATE
<br />CHECKED
<br />DRAWN
<br />1316 W. Norwood Street
<br />Rialto, CA 92377
<br />Tel. (562) 299-4490
<br />www.jps-electric.com
<br />JPS ELECTRIC, INC.
<br />These drawings and ideas are not to be
<br />reproduced, in whole, or in part, without
<br />the express written permission of
<br />9/24/2025
<br />XFMR TRANSFORMER
<br /> - X -
<br />J
<br />J
<br />WALL MOUNTED COMBINATION TELEPHONE AND DATA
<br />DATA OUTLET, 15" TO BOTTOM OF DEVICE CONTRACTOR
<br />TO PROVIDE 1"C.O. STUB-UP TO CEILING SPACE. (PROVIDE
<br />1"C.O. TO TELEPHONE BACKBOARD AND NETWORK
<br />CABINET WHERE EXPOSED CEILING OCCURRED.)
<br />WALL MOUNTED TELEPHONE 15" TO BOTTOM OF DEVICE
<br />WITH 3/4"C.O STUB-UP TO ACCESSIBLE CEILING SPACE.
<br />(PROVIDE 3/4"C.O. TO TELEPHONE BACKBOARD AND
<br />NETWORK CABINET WHERE EXPOSED CEILING
<br />OCCURRED.)
|