1.PROVIDE VACANCY SENSOR/DIMMER TO ALL LUMINAIRES REQUIRED BY SECTION <br />150.0 OF 2022 TITLE 24 PART 6. <br />2.THIS DRAWING IS FOR REFERENCE ONLY. WIRE CKT 20 ON THE PLAN TO ALL <br />DETECTORS FOR A COMPLETE AND OPERATIONAL SYSTEM. VERIFY W/LOCAL <br />JURISDICTION FOR ALARM DETECTOR REQUIREMENT BEFORE ROUGH-IN. <br />3.IN DWELLING AREA SPECIFIED IN CEC 2022 SECTION 210.52; (A) WALL SPACE, (B) <br />SMALL-APPLIANCE CIRCUIT, (C) COUNTERTOP SPACE, (D) BATHROOM AREA, (E) <br />OUTDOORS, (F) LAUNDRY AREA, (G) GARAGE, AND (H) HALLWAYS; ALL 125-VOLT, 15- <br />AND 20- AMPERE RECEPTACLES SHALL BE LISTED TAMPER-RESISTANT <br />RECEPTACLES. <br />4.OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, LIVING ROOMS, PARLORS, <br />LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, <br />HALLWAYS, LAUNDRY AREAS OR SIMILAR ROOMS OR AREAS WILL BE PROTECTED BY <br />A LISTED ARC-FAULT CIRCUIT INTERRUPTER, COMBINATION-TYPE, INSTALLED TO <br />PROVIDE PROTECTION OF THE BRANCH CIRCUIT. <br />5.ALL NEW CARBON MONOXIDE ALARM ARE 120V HARD-WIRED WITH BATTERY BACKUP, <br />INTERCONNECTED WITH OC SENSOR, AND ARE AUDIBLE IN ALL SLEEPING ROOMS. <br />6.ELECTRICAL CONTRACTOR MUST VERIFY MECHANICAL EQUIPMENT INFORMATION <br />FOR MECHANICAL DRAWING BEFORE ISSUING ANY BID. NOTIFY ENGINEER <br />IMMEDIATELY IF ANY DISCREPANCY OCCUR. <br />7.THE HEIGHT OF THE OUTLETS AND SWITCHES ARE NOT NOTED ON THE LEGEND OR <br />IN THE UNIT PLANS. REFER TO "TYPICAL ELECTRICAL DEVICE HEIGHT ON E-0.3" <br />8.ALL DWELLING UNIT LUMINAIRES SHALL BE HIGH EFFICACY IN ACCORDANCE WITH <br />TABLE 150.0 OF 2022 BUILDING ENERGY EFFICIENCY STANDARDS, TITLE 24 PART 6. <br />9.A DEDICATED 125-VOLT (V) ELECTRICAL RECEPTACLE THAT IS WITHIN 3 FEET OF THE <br />WATER HEATER AND ACCESSIBLE TO THE WATER HEATER WITH NO OBSTRUCTIONS, <br />AND BE CONNECTED TO A THREE CONDUCTOR, 10 AWG BRANCH CIRCUIT. IN <br />ADDITION, THE UNUSED CONDUCTOR MUST BE LABELED AS "SPARE" AND <br />ELECTRICALLY ISOLATED AND HAVE RESERVED CIRCUIT BREAKER SPACE. <br />10.GFCI NOTES FOR DWELLING UNITS PER 210.8(A) ALL 125-VOLT THROUGH 250-VOLT <br />RECEPTACLES INSTALLED IN THE LOCATIONS BELOW THAT SPECIFIED IN 210.8(A)(1) <br />THROUGH (A)(11) AND SUPPLIED BY SINGLE-PHASE BRANCH CIRCUITS RATED 150 <br />VOLTS OR LESS TO GROUND SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER <br />PROTECTION FOR PERSONNEL. (1) BATHROOMS (2) GARAGES (3) OUTDOORS (4) <br />CRAWL SPACES OR BELOW GRADE LEVEL (5) BASEMENTS (6) KITCHENS — WHERE <br />THE RECEPTACLES ARE INSTALLED TO SERVE THE COUNTERTOP SURFACES (7) <br />SINKS — WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 M (6 FT) FROM THE TOP <br />INSIDE EDGE OF THE BOWL OF THE SINK (8) BOATHOUSES (9) BATHTUBS OR <br />SHOWER STALLS — WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 M (6 FT) OF <br />THE OUTSIDE EDGE OF THE BATHTUB OR SHOWER STALL (10) LAUNDRY AREAS (11) <br />INDOOR DAMP AND WET LOCATIONS. <br />11.AFCI NOTES FOR DWELLING UNITS PER 210.12(A) ALL 120-VOLT, SINGLE-PHASE, 15- <br />AND 20-AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS OR DEVICES INSTALLED IN <br />DWELLING UNIT KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, <br />PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, <br />CLOSETS, HALLWAYS, LAUNDRY AREAS, OR SIMILAR ROOMS OR AREAS SHALL BE <br />PROTECTED BY ANY OF THE MEANS DESCRIBED IN 210.12(A)(1) THROUGH (6). <br />12.ELECTRICAL RECEPTACLE OUTLETS, SWITCHES AND CONTROLS INTENDED TO BE <br />USED BY OCCUPANTS SHALL BE LOCATED NO MORE THAN 48" MEASURED FROM THE <br />TOP OF THE OUTLET BOX AND NOT LESS THAN 15" MEASURED FROM THE BOTTOM <br />OF THE OUTLET BOX ABOVE THE FINISH FLOOR. <br />CEILING FAN OR LED LIGHTING FIXTURE TO BE DETERMINED. VERIFY W/ OWNER FOR <br />ACTUAL TO LOCATION. OUTLET BOX/SYSTEMS SHALL BE LISTED AND MARKED BY THE <br />OEM AS SUITABLE FOR THIS PURPOSE. CEILING -SUSPENDED (PADDLE) FANS SHALL <br />NOT WEIGH MORE THAN 70 LBS. FOR OUTLET BOX/SYSTEMS DESIGNED TO SUPPORT <br />CEILING-SUSPENDED FANS THAT WEIGH MORE THAN 35 LBS, THE REQUIRED <br />MARKING SHALL INCLUDE THE MAXIMUM WEIGHT TO BE SUPPORTED. <br />DENOTES THE CONTROL FOR THE CEILING FAN CONNECTED TO THE J-BOX PER NOTE <br />#1. <br />DENOTES HALF-HOT RECEPTACLE ON SWITCH LEG 'b' IN THIS AREA. <br />SPLIT CIRCUITED HALF-SWITCHED DUPLEX RECEPTACLE FOR GARBAGE DISPOSER <br />AND DISHWASHER BELOW KITCHEN SINK. CONNECT THE SWITCHED SIDE OF THE <br />RECEPTACLE TO A MOTOR RATED WALL SWITCH AND PROVIDE A DEDICATED <br />CIRCUIT FOR EACH APPLIANCE WITH A COMMON TRIP DEVICE AT THE CIRCUIT <br />BREAKER. <br />DENOTES APPROXIMATE LOCATION OF FC/FAU UNIT. VERIFY WITH MECHANICAL <br />DRAWINGS FOR EXACT LOCATION. <br />REFRIGERATOR RECEPTACLE CONNECTED TO LINE SIDE OF KITCHEN SMALL <br />APPLIANCE GFI PROTECTED COUNTER MOUNTED RECEPTACLE TO COMPLY WITH <br />NEC SECTION 210.52(B)(1). <br />PROVIDE 15A/1P MOTOR RATED SWITCH FOR CONNECT TO THE EXHAUST FAN. <br />REFER TO MECHANICAL PLAN FOR DETAIL. <br />PROVIDE GFCI PROTECTED RECEPTACLE OUTLET WITH ENCLOSURE THAT IS <br />WEATHERPROOF (WP) WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. <br />AN OUTLET BOX HOOD SHALL BE LISTED AND SHALL BE IDENTIFIED AS "EXTRA DUTY". <br />RECEPTACLE SHALL BE LISTED AND SO IDENTIFIED AS WEATHER-RESISTANT (WR) <br />TYPE. <br />PER SECTION 150.0(K)(3) ALL OUTDOOR LIGHTING SHALL BE HIGH EFFICACY AND <br />CONTROLLED BY MANUAL ON/OFF SWITCH AND ONE OF THE CHOICES BELOW: <br />1.PHOTOCELL AND MOTION SENSOR <br />2.PHOTOCELL AND AUTOMATIC TIME SWITCH <br />3.ASTRONOMIC TIME CLOCK <br />PROVIDE POWER, LIGHTING, AND OCCUPANCY SENSOR TO ATTIC SPACE. <br />CHIME UNIT WITH INTERGRAL TRANSFORMER MOUNTED AT +7'-0" A.F.F. TO BOTTOM <br />OF CHIME. <br />PROVIDE 15A/2P MOTOR RATED SWITCH FOR CONNECTION TO THE FC. <br />DINING RECEPTACLE CONNECTED TO LINE SIDE OF KITCHEN SMALL APPLIANCE GFI <br />PROTECTED COUNTER MOUNTED RECEPTACLE TO COMPLY WITH NEC SECTION <br />210.52(B)(1). <br />LIGHTED ADDRESS SIGN @ 5'-0" ABOVE FINISH GRADE. <br />DOORBELL CONTROLS SHALL NOT EXCEED 48" ABOVE EXTERIOR FLOOR, MEASURED <br />FROM THE TOP OF THE DOORBELL BUTTON ASSEMBLY. <br />REFER TO SPEC SHEET FOR GUIDANCE ON WHETHER A PLUG-IN CORD INSTALLATION <br />OR HARDWIRING IS REQUIRED. IF PERMANENTLY CONNECTED, PROVIDE A <br />DISCONNECTING MEANS WITHIN SIGHT OF THE APPLIANCE OR A CIRCUIT BREAKER <br />LOCKOUT COMPLYING WITH 110.25, PER CEC 422.31. <br />1 <br />2 <br />3 <br />4 <br />5 <br />6 <br />7 <br />8 <br />9 <br />10 <br />11 <br />12 <br />13 <br />16 <br />GENERAL NOTES <br />KEYED NOTES <br />14 <br />15 <br />LIGHTING LUMINAIRE SCHEDULE <br />MARK VOLT DESCRIPTION MANUFACTURERMOUNT MODEL NUMBER LAMPS NOTESINPUT <br />WATTSLEGEND <br />NOTES: <br />1) VERIFY WITH OWNER OR ARCHITECT BEFORE PURCHASING THE LIGHTING FIXTURES. <br />2) ALL THE RESIDENTIAL LUMINAIRES SHOULD BE JA8 LABEL AND COMPLIED WITH TITLE 24. <br />120 LED 18LED DOWNLIGHTRECESS <br />120 WALL LED LIGHT (WALL)LED 48 <br />A SELECT BY OWNER SELECT BY OWNER <br />SELECT BY OWNER SELECT BY OWNERB <br />120 SURFACE 50LED TRIP LIGHT SELECT BY OWNER SELECT BY OWNER LEDC <br />1.SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE LOCATED WHERE AMBIENT <br />CONDITION, INCLUDING HUMIDITY AND TEMPERATURE, ARE OUTSIDE THE LIMITS <br />SPECIFIED BY THE MANUFACTURER'S PUBLISHED INSTRUCTIONS. <br />2.SMOKE ALARMS OR SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF 20 <br />FOOT HORIZONTAL DISTANCE FROM A PERMANENTLY INSTALLED COOKING <br />APPLIANCE, EXCEPTION IONIZATION SMOKE ALARMS OR PHOTOELECTRIC SMOKE <br />ALARMS PER CODE. <br />3.INSTALLATION NEAR BATHROOMS. SMOKE ALARMS SHALL BE INSTALLED NOT LESS <br />THAN A 3 FOOT HORIZONTAL DISTANCE FROM THE DOOR OR OPENING OF A <br />BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS WOULD PREVENT <br />PLACEMENT OF A SMOKE ALARM REQUIRED BY OTHER SECTION OF THE CODE. <br />4.SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE INSTALLED WITH A 36 INCH <br />HORIZONTAL PATH FROM THE SUPPLY REGISTERS OF A FORCED AIR HEATING OR <br />COOLING SYSTEM AND SHLLE BE INSTALLED OUTSIDE OF THE DIRECT AIR FLOW <br />FROM THOSE REGISTERS. <br />5.CARBON MONOXIDE/ SMOKE DETECTORS SHALL BE PERMANENTLY WIRED AND <br />PROVIDED WITH BATTERY BACK-UP. SMOKE DETECTORS ARE TO BE <br />INTERCONNECTED WITH-IN EACH UNIT SO THAT ALL DETECTORS WITH-IN THE UNIT <br />WILL SOUND THEIR ALARMS ON ACTIVATION OF ANY DETECTOR IN THE UNIT. <br />6.WHERE THE HIGHEST POINT OF A CEILING IN A ROOM THAT OPENS TO THE <br />HALLWAY SERVING THE BEDROOMS EXCEEDS THAT OF THE OPENING INTO THE <br />HALLWAY BE 24 INCHES OR MORE, SMOKE DETECTORS SHALL BE INSTALLED IN THE <br />HALLWAY AND IN THE ADJACENT ROOM WITHIN 12 INCHES FROM THE HIGHEST <br />POINT OF THE CEILING. <br />7.CARBON MONOXIDE/ SMOKE DETECTORS INTERCONNECTED SHALL BE INSTALLED <br />WITHIN EACH DWELLING UNIT BEFORE APPROVAL BY THE FIRE DEPARTMENT. <br />SMOKE DETECTORS NOTES <br />GFCI NOTES FOR DWELING UNITS <br />PER 210.8(A) ALL 125-VOLT THROUGH 250-VOLT RECEPTACLES INSTALLED IN THE <br />LOCATIONS BELOW THAT SPECIFIED IN 210.8(A)(1) THROUGH (A)(11) AND SUPPLIED BY <br />SINGLE-PHASE BRANCH CIRCUITS RATED 150 VOLTS OR LESS TO GROUND SHALL HAVE <br />GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. <br />(1)BATHROOMS <br />(2)GARAGES <br />(3)OUTDOORS <br />(4)CRAWL SPACES OR BELOW GRADE LEVEL <br />(5)BASEMENTS <br />(6)KITCHENS — WHERE THE RECEPTACLES ARE INSTALLED TO SERVE THE <br />COUNTERTOP SURFACES <br />(7)SINKS — WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 M (6 FT) FROM THE TOP <br />INSIDE EDGE OF THE BOWL OF THE SINK <br />(8)BOATHOUSES <br />(9)BATHTUBS OR SHOWER STALLS — WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 <br />M (6 FT) OF THE OUTSIDE EDGE OF THE BATHTUB OR SHOWER STALL <br />(10)LAUNDRY AREAS <br />(11)INDOOR DAMP AND WET LOCATIONS <br />AFCI NOTES FOR DWELING UNITS <br />PER 210.12(A) ALL 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE BRANCH CIRCUITS <br />SUPPLYING OUTLETS OR DEVICES INSTALLED IN DWELLING UNIT KITCHENS, FAMILY <br />ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, <br />SUNROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS, OR SIMILAR <br />ROOMS OR AREAS SHALL BE PROTECTED BY ANY OF THE MEANS DESCRIBED IN <br />210.12(A)(1) THROUGH (6) <br />DS <br />DS <br />103 <br />ALIGN <br />E <br />E <br />KITCHEN <br />DINING <br />BEDROOM 2 <br />BATH <br />BEDROOM 1 <br />LIVING <br />CL <br />O <br />S <br />E <br />T <br />2 <br />CLOSET 1COAT <br />J <br />TV <br />3 <br />D <br />J <br />1 <br />2 <br />J <br />D <br />TV <br />VS <br />WP <br />1 <br />3 <br />3 <br />1 <br />D 7 <br />D.W. <br />G.D. <br />MIC. <br />RAN. <br />D <br />6 <br />REF. <br />TV <br />LOW VOLTAGE BOX <br />13 <br />A1 <br />B <br />EF <br />18 <br />FC <br />5 <br />EF <br />M <br />A <br />TYP. <br />DOOR BELL <br />11 <br />D <br />WH <br />1 <br />WH <br />1 <br />16 <br />16 <br />SD CO <br />SD <br />SD <br />A1-LV2-26,28 <br />1 <br />1a <br />1b <br />1 <br />1 <br />2a <br />2b <br />2 <br />2 <br />2 <br />2d <br />2e 2e <br />2e <br />3 <br />3 <br />3 <br />3a <br />3 <br />3 <br />3e <br />3s <br />3s <br />3s <br />5 <br />5 <br />5 <br />5 <br />7 <br />7 <br />7 <br />9 <br />11 <br />13 <br />15 <br />A1-26,28 <br />18,20 <br />12 <br />a <br />b <br />a <br />b <br />d <br />e <br />e <br />s <br />D <br />D <br />D <br />a <br />1c <br />1c1c <br />1c <br />3b <br />3b3b <br />3b <br />3n 3n <br />3n <br />2i <br />2i <br />2i <br />2i <br />c <br />3n <br />3n <br />b <br />i <br />e <br />1e <br />C <br />TYP. <br />M2 <br />12 <br />2 <br />2 POWERED BY <br />OUTDOOR UNIT <br />DS <br />DS <br />203 <br />A <br />E <br />E <br />KITCHEN <br />DINING <br />BEDROOM 2 <br />BATH <br />BEDROOM 1 <br />LIVING <br />CL <br />O <br />S <br />E <br />T <br />2 <br />CLOSET 1COAT <br />J <br />TV <br />3 <br />D <br />J <br />1 <br />2 <br />J <br />D <br />TV <br />VS <br />WP <br />1 <br />2 <br />3 <br />3 <br />1 <br />D <br />2 <br />7 <br />D.W. <br />G.D. <br />MIC. <br />RAN. <br />D <br />6 <br />REF. <br />TV <br />LOW VOLTAGE BOX <br />13 <br />A1-LV2 <br />B <br />EF <br />12 <br />5 <br />EF <br />M <br />A <br />TYP. <br />DOOR BELL <br />11 <br />SD <br />SD <br />SD CO <br />1a <br />1 <br />1 <br />1b <br />1 <br />3 <br />3 <br />3b <br />3 <br />2a <br />2b2 <br />2 <br />2 <br />2e <br />2d <br />2e <br />2e <br />3 <br />3d <br />3d <br />3 <br />3c <br />5 <br />5 <br />5 <br />5 <br />7 <br />7 <br />7 <br />9 <br />11 <br />13 <br />15 <br />12 <br />18,20 <br />a <br />b <br />b <br />c <br />d <br />a <br />b <br />d <br />e <br />D <br />D <br />D <br />D <br />3d <br />1i <br />1i <br />1i <br />1i <br />2i <br />2i2i <br />2i <br />3o 3o <br />3o <br />3s 3s <br />3s 3s <br />3o <br />3o <br />s <br />i <br />i <br />18 <br />FC <br />10 <br />VS <br />1z <br />1z z <br />M2 <br />POWERED BY <br />OUTDOOR UNIT <br />DRYER <br />DRYER <br />WASHER / <br />DRYER <br />WASHERWASHER <br />FOLDING TABLE <br />LAUNDRY <br />CONFERENCE <br />ROOM <br />COMMUNITY <br />ROOM <br />JAN. <br />ALL-GENDER <br />RESTROOM <br />KITCHEN <br />(RESIDENCE USE ONLY) <br />60"x54"48"x48" <br />60"x54"48"x48" <br />60"x54"48"x36" <br />60"x54" <br />48"x36" <br />3 A500 <br />TV <br />WP <br />5 <br />D.W. <br />G.D. <br />MIC. <br />RAN. <br />REF. <br />TV <br />LOW VOLTAGE BOX <br />HP1 <br />EF <br />B <br />FC <br />18 <br />2 <br />EF <br />M <br />BA <br />TYP. <br />WH <br />2 <br />WH <br />1 <br />7 <br />7 <br />C <br />TYP. <br />M 2 <br />6 <br />POWERED BY <br />OUTDOOR UNIT <br />$D <br />LD <br />OS <br />4 <br />4b 4b <br />4b 4b <br />44 <br />4 <br />2 <br />2a 2a <br />2a 2a <br />2 <br />2e <br />4d <br />4e <br />4f <br />4e <br />6b6b <br />6 6 <br />6 <br />6b6b <br />6n6n <br />6n <br />6 <br />6 <br />14 <br />14 <br />14 <br />14 <br />12 <br />14 <br />9 <br />11 <br />8 <br />29 <br />10 <br />34,36 <br />a <br />b <br />3ns <br />6s <br />6s <br />6s <br />e <br />d <br />b <br />e <br />D. <br />D. <br />W. <br />W.W. <br />GFCI <br />GFCI <br />17,19 <br />21,23 <br />33 <br />35 37 <br />HP1-26,28 <br />A1-LV2-26,28 <br />L <br />EF <br />EF <br />5 <br />M f <br />2f <br />LD LD <br />LD <br />3n <br />LD <br />$D <br />D.25,27 <br />GFCI <br />OS <br />OS <br />6 <br />1 <br />TYP. <br />2 <br />6 <br />6 <br />6 <br />6n <br />4 <br />4 <br />6 <br />BE <br />TYP. <br />BD <br />TYP. <br />$D f <br />1 <br />2 <br />3 <br />4 <br />5 <br />6 <br />CIRCUIT FOR HALF (SPLITWIRED) OF DUPLEX OR QUADFLEX CONTROLLED <br />RECEPTACLES ARE SWITCH/CONTROLLED VIA ROOM/AREA LIGHTING CONTROL PER <br />TITLE-24 REQUIREMENT. <br />DENOTES APPROXIMATE LOCATION OF FC UNIT. VERIFY WITH MECHANICAL <br />DRAWINGS FOR EXACT LOCATION. POWERED BY OUTDOOR UNIT. <br />PROVIDE GFCI PROTECTED RECEPTACLE OUTLET WITH ENCLOSURE THAT IS <br />WEATHERPROOF (WP) WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. <br />AN OUTLET BOX HOOD SHALL BE LISTED AND SHALL BE IDENTIFIED AS "EXTRA <br />DUTY". RECEPTACLE SHALL BE LISTED AND SO IDENTIFIED AS WEATHER-RESISTANT <br />(WR) TYPE. <br />PROVIDE MOTOR RATED SWITCH FOR CONNECTION TO THE FC UNIT. PER <br />MECHANICAL PLANS. <br />PROVIDE 15A/1P MOTOR RATED SWITCH FOR CONNECT TO THE EXHAUST FAN. <br />REFER TO MECHANICAL PLAN FOR DETAIL. <br />FC POWERED BY OUTDOOR HP UNIT <br />REFER TO SPEC SHEET FOR GUIDANCE ON WHETHER A PLUG-IN CORD INSTALLATION <br />OR HARDWIRING IS REQUIRED. IF PERMANENTLY CONNECTED, PROVIDE A <br />DISCONNECTING MEANS WITHIN SIGHT OF THE APPLIANCE OR A CIRCUIT BREAKER <br />LOCKOUT COMPLYING WITH 110.25, PER CEC 422.31. <br />KEY NOTES <br />7 <br />PC COMMENTS RESPONSE #1 01/29/2025A <br />al <br />l <br /> <br />i <br />d <br />e <br />a <br />s <br />, <br /> <br />d <br />e <br />s <br />i <br />g <br />n <br />s <br /> <br />a <br />n <br />d <br /> <br />p <br />l <br />a <br />n <br />s <br /> <br />r <br />e <br />p <br />r <br />e <br />s <br />e <br />n <br />t <br />e <br />d <br /> <br />b <br />y <br /> <br />t <br />h <br />i <br />s <br /> <br />d <br />r <br />a <br />w <br />i <br />n <br />g <br /> <br />a <br />r <br />e <br /> <br />t <br />h <br />e <br /> <br />e <br />x <br />c <br />l <br />u <br />s <br />i <br />v <br />e <br /> <br />p <br />r <br />o <br />p <br />e <br />r <br />t <br />y <br /> <br />o <br />f <br />Go <br />u <br />v <br />i <br />s <br /> <br />E <br />n <br />g <br />i <br />n <br />e <br />e <br />r <br />i <br />n <br />g <br /> <br />a <br />n <br />d <br /> <br />s <br />h <br />a <br />l <br />l <br /> <br />n <br />o <br />t <br /> <br />b <br />e <br /> <br />r <br />e <br />p <br />r <br />o <br />d <br />u <br />c <br />e <br />d <br /> <br />i <br />n <br /> <br />w <br />h <br />o <br />l <br />e <br /> <br />o <br />r <br /> <br />i <br />n <br /> <br />p <br />a <br />r <br />t <br /> <br />w <br />i <br />t <br />h <br />o <br />u <br />t <br /> <br />t <br />h <br />e <br /> <br />e <br />x <br />p <br />r <br />e <br />s <br />s <br /> <br />p <br />r <br />i <br />o <br />r <br /> <br />w <br />r <br />i <br />t <br />t <br />e <br />n <br /> <br />p <br />e <br />r <br />m <br />i <br />s <br />s <br />i <br />o <br />n <br /> <br />o <br />f <br /> <br />s <br />a <br />i <br />d <br /> <br />e <br />n <br />g <br />i <br />n <br />e <br />e <br />r <br />s <br />, <br /> <br />a <br />n <br />y <br /> <br />u <br />n <br />a <br />u <br />t <br />h <br />o <br />r <br />i <br />z <br />e <br />d <br /> <br />r <br />e <br />u <br />s <br />e <br /> <br />o <br />f <br /> <br />t <br />h <br />e <br />s <br />e <br /> <br />p <br />l <br />a <br />n <br />s <br /> <br />o <br />t <br />h <br />e <br />r <br /> <br />t <br />h <br />a <br />n <br /> <br />f <br />o <br />r <br /> <br />t <br />h <br />e <br /> <br />p <br />r <br />o <br />j <br />e <br />c <br />t <br /> <br />a <br />n <br />d <br /> <br />l <br />o <br />c <br />a <br />t <br />i <br />o <br />n <br /> <br />s <br />h <br />o <br />w <br />n <br /> <br />i <br />s <br /> <br />p <br />r <br />o <br />h <br />i <br />b <br />i <br />t <br />e <br />d <br />. <br />JOB NO. <br />SUBMITTAL <br />DATE <br />SHEET TITLE <br />SHEET NO. <br />CLIENT: <br />REVISION <br />DATE <br />21 <br />3 <br />0 <br /> <br />E <br /> <br />4 <br />T <br />H <br /> <br />S <br />T <br /> <br /># <br />2 <br />0 <br />0 <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />5 <br />BSB: MR230056; Gouvis: 66467 <br />WATER REVISIONS <br />09/12/2025 <br />1ST PLAN CHECK SUBMITTAL 08/20/2024 <br />2ND PLAN CHECK SUBMITTAL 1/29/2025 <br />PC COMMENTS RESPONSE #2 04/17/2025B <br />3RD PLAN CHECK SUBMITTAL 04/17/2025 <br />PC COMMENTS RESPONSE #3 07/10/2025C <br />4TH PLAN CHECK SUBMITTAL 07/10/2025 <br />WATER REVISIONS 09/12/2025D <br />WATER REVISIONS 09/12/2025 <br />PC COMMENTS RESPONSE #4 10/10/2025E <br />CLIENT REVISIONS 10/10/20251 <br />OL <br />I <br />V <br />E <br /> <br />C <br />R <br />E <br />S <br />T <br /> <br />R <br />E <br />S <br />I <br />D <br />E <br />N <br />T <br />I <br />A <br />L <br />21 <br />5 <br />0 <br /> <br />E <br />. <br /> <br />F <br />O <br />U <br />R <br />T <br />H <br /> <br />A <br />N <br />D <br /> <br />2 <br />1 <br />6 <br />0 <br /> <br />E <br />. <br /> <br />F <br />O <br />U <br />R <br />T <br />H <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />5 <br />OL <br />I <br />V <br />E <br /> <br />C <br />R <br />E <br />S <br />T <br />DATE SIGNED: 7/8/25 <br />E-3.1 <br />UNIT PLANS <br />12' <br /> 1/4" = 1'-0" <br />2'8'4'0 <br />UNIT A-1 LEVEL 2 2 1UNIT A-1 LEVEL 1 <br />12' <br /> 1/4" = 1'-0" <br />2'8'4'0 <br />UNIT A-1 LEVEL 1 - LAUNDRY PARTIAL (BLDG A1)3 <br />12' <br /> 1/4" = 1'-0" <br />2'8'4'0 <br />11