Laserfiche WebLink
Component <br />Fastener <br />For z = hr: <br />Wind Load Tabulation for Roof Components & Cladding <br />z Kh qh p = Net Design Pressures (psf) <br />m )(psf)Zohe 1,2,3 (49 Zone 1 (-) Zone 2 (-)Zone 3 (-) <br />0 0.85 22.35 10.73 -21.90 -30.84 -48.72 <br />14.85 0.85 22.35 10.73 -21.90 -30.84 -48.72 <br />For z = he:9.00 0.85 22.35 10.73 -21.90 -30.84 -48.72 <br />For z = h:11.93 0.85 22.35 10.73 -21.90 -30.84 -48.72 <br />Notes: 1. (+) and (-) signs signify wind pressures acting toward & away from respective surfaces. <br />2. Width of Zone 2 (edge), 'a' = -3.30 Ift <br />3. Width of Zone 3 (comer), 'a' =-535-Ift. <br />4. For monoslope roofs with 0 <= 3 degrees, use Fig. 30.4-2A for'GCp' values with 'qh'. <br />5. For buildings with h > 60' and 0 > 10 degrees, use Fig. 30.6-1 for 'Gepi' values with 'qh'. <br />6. For all buildings with overhangs, use Fig. 30.4-28 for 'GCp' values per Sect. 30.10. <br />7. If a parapet >= 3' in height is provided around perimeter of roof with 0 <= 10 degrees, <br />Zone 3 shall be treated as Zone 2. <br />8. Per Code Section 30.2.2, the minimum wind load for C&C shall not be less than 16 psf. <br />9. References a. ASCE 7-02, "Minimum Design Loads for Buildings and Other Structures". <br />b. "Guide to the Use of the Wind Load Provisions of ASCE 7-02" <br />by- Kishor C. Mehta and James M. Delahay (2004). <br />8 3 <br />11