GROUNDING NOTES <br />I A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH [NEC 690-471 AND [NEC <br />250-50] THROUGH INEC 60 250-166] SHALL BE PROVIDED. PER NEC, GROUNDING <br />ELECTRODE SYSTEM OF EXISTING BUILDING MAY BE USED AND BONDED TO AT THE <br />SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, OR <br />IS ONLY METALLIC WATER PIPING, A SUPPLEMENTAL GROUNDING ELECTRODE WILL <br />BE USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT GROUND <br />ROD WITH ACORN CLAMP, <br />11 GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN #8 AWG AND NO <br />GREATER THAN #6 AWG COPPER AND BONDED TO THE EXISTING GROUNDING <br />ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. <br />Ill PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO [NEC 250.21] [NEC TABLE <br />250.122] AND All METAL PARTS OR MODULE FRAMES ACCORDING TO [NEC 690.43]. <br />IV MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO [NEC <br />690.421. <br />V THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT <br />THE REMOVAL OF A MODULE DOES NOTINTERRUPT A GROUNDED CONDUCTOR TO <br />ANOTHER MODULE. <br />VI EACH MODULE WILL BE GROUNDED USJNG THE SUPPLIED CONNECTIONS POINTS <br />IDENTIFIED IN THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. <br />VII ENCLOSURES SHALL BE PRORERLY PREPARED WITH REMOVAL OF PAINT/FINISH AS <br />APPROPRIATE WHEN GROUNDING ,EQUIPMENT WITH TERMINATION GROUNDING <br />LUGS. <br />VI11 GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND <br />GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL BE RATED F.OR DIRECT <br />BURIAL. <br />IX GROUNDING :AND BONDING CONDUCTORS SHALL BE COPPER, SOLID OR <br />STRANDED, AND BARE WHEN EXPOSED. <br />X EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZE ACCORDING TO [NEC <br />690.451 AND BE A MINIMUM OF #10AWG WHEN NOT EXPOSED TO DAMAGE (#6AWG <br />SHALL BE USED WHEN EXPOSED TO DAMAGE). <br />XI GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLOR CODED <br />GREEN (OR MARKED GREEN IF #4 AWG OR LARGER) <br />XII ALL CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF <br />CONNECTION SHALL HAVE GROUNDED BUSHINGS AT BOTH ENDS. <br />XIII AC SYSTEM GEC SIZED ACCORDING TO INEC 690.471 [NEC TABLE 250.661 DC <br />SYSTEM GEC SIZED ACCORDING TO [NEC 250.1661 MINIMUM #8AWG WHEN <br />INSULATED, #6AWG WHEN EXPOSED TO DAMAGE. <br />XIV EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES; <br />EQUIPMENTS, AND CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN <br />ACCORDANCE WITH 250.134 OR 250.136(A) REGARDLESS OFVOLTAGE. <br />INTERCONNECTION NOTES <br />1 PV DEDICATED BACKFEED BREAKERS MUST BE LOCATED,AT THE'OPPOSITE <br />END OF THE BUS FROM THE MAIN SERVICE BREAKER OR TRANSFORMER INPUT <br />FEEDER INACCORDANCE WITH [NEC 690.64(B)(7)1 <br />Il :SUM OF BREAKER RATINGS SUPPLYING THE BOS MAY NOT EXCEED 120% OF <br />THE THE BUSBAR RATING PER [NEC 690.64(B)(2)] AND/OR [NEC 705.12(D)(D· <br />Ill GROUND'FAULT PROTECTION IN ACCORDANCE WITH [NEC 215.91 & [NEC 230.95] <br />ALL EQUIPMENT TO BE RATED FOR BACKFEEDING. <br />IV SUPPLY SIDE INTERCONNECTION ACCORDING TO [NEC 690.64(A)] AND/OR [NEC <br />705.12(A)] WITH SERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH <br />INEC 230.4203)] <br />V MICROINVERTER BRANCHES SHALL BE CONNECTED TO A;SINGLE BREAKER <br />OCPD IN:ACCORDANCE WITH [NEC 110.3(B)]. <br />DISCONNECT NOTES <br />1 DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE iSWITCH IS <br />OPENED THE CONDUCTORS REMAINING LIVE ARE CONNECTEDTO THE TERMINALS <br />MARKED 'LINE SIDE' (TYPICALLY THE UPPER TERMINALS) <br />11 AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE <br />LOCKABLE, AND BE A VISIBLE-BREAK SWITCH <br />111 DC CURRENT CONDUCTORS ARE TO ,REMAIN OUTSIDE OF BUILDING PRIOR IO <br />EITHER A FUSEABLE SOURCE CIRCUIT COMBINER BOX OR A LOAD-BREAK <br />DISCONNECTING DEVICE <br />EQUIPMENT LOCATIONS <br />I ALL EQUIPMENT SHALL MEET MINIMUMSETBACKS AS REQUIRED BY [NEC 110.26]. <br />11 EQUIPMENT INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERAIING <br />TEMPERATURE AS SPECIFIED BY [NEC 690.31 (A)-(8)1 AND [NEC TABLE 310.15 (B)(2)(C) 1 <br />111 ADDITIONAL AC DISCONNECTS SHALL BE PROVIDED WHERE THE INVERTER IS NOT <br />ADJACENT TO THE UTILITY AC DISCONNECT. OR NOT WITHIN SIGHT OF THE UTILITY AC <br />DISCONNECT. <br />IV ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING <br />TO NEC APPLICABLE CODES. <br />V ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED. FOR OUTDOOR USAGE <br />WHEN APPROPRIATE. <br />WIRING & CONDUIT NOTES <br />1 -ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND <br />APPROVED FOR THE SITE APPLICATIONS <br />Il ALL PV CABLES AND HOMERUN WIRES BE #10AWG 'USE-2, PV WIRE, OR <br />PROPRIETARY SOLAR CABLING SPECIFIED BY MFR, OR EQUIVALENT; ROUTED <br />TO SOURCE CIRCUIT COMBINER BOXES AS REQUIRED <br />111 ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO <br />[NIC 690.9 (A)(1) & (B)(1)] [NEC 240) MEG 690.7] FOR MULTIPLE CONDUCTORS <br />IV ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE <br />DERATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(C)! BLACK ONLY** <br />V EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2,90°C RATED, WET AND <br />UV RESISTANT, AND UL LISTED RATED FOR 600V, UV RATED SPIRAL WRAP <br />SHALL BE USED TO PROTECT WIRE FROM SHARP EDGES <br />VI PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2 <br />INSULATED, 90°C RATED, WET AND UV RESISTANT, RATED FOR 600V PER NEC <br />2008 OR 1000V PER NEC 2011 <br />VII 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER <br />VOLTAGE TO GROUND MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE <br />MEANS <br />Vlll ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION <br />IX VOLTAGE DROP LIMITED TO 2% FOR DC CIRCUITS AND 1% FOR AC CIRCUITS <br />X NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED <br />AS FOLLOWS: <br />DC POSITIVE- RED (OR MARKEDERED) <br />DC NEGATIVE- GREY (GR MARKED GREY) <br />XI POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED: <br />DC POSITIVE- GREY (OR MARKED.GREY) <br />DC NEGATIVE- BLACK (OR MARKED BLACK) <br />XII AC CONDUCTORS >4AWG COLOR CODED OR MARKED: <br />PHASE A OR Ll- BLACK <br />PHASE B OR 12- RED <br />PHASE C ORL3- BLUE <br />NEUTRAL-WHITE/GRAY <br />*USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY <br />BEUSED INSIDE <br />** USE-2 IS AVAILABLE AS UV WHITE <br />SITE NOTES <br />1 A LADDER SHALL BE IN: PLACE FOR INSPECTION IN:=COMPLIANCE WITH OSHA <br />REGULATIONS. <br />11 THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS: SYSTEM IS <br />AN UTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES. <br />111 THE SOLAR PV INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING, <br />MECHANICAL, OR BUILDING ROOF VENTS, <br />IV PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND <br />PROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION [NEC <br />110.26] <br />V ALTERNATE POWER SOURCE PLACARD SHALL BE: PLASTIC, ENGRAVED IN A <br />CONTRASTING COLOR TO THE PLAQUE. THIS PLAQUE WILL BE ATTACHED <br />USING AN APPROVED METHOD. IF EXPOSED TO SUNLIGHT, IT SHALL BE UV <br />RESISTANI ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS REQUIRED 'BY <br />THE NEC. <br />VI THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM <br />PHYSICAL DAMAGE BETWEEN THE GROUNDING ELECTRODE AND THE PANEL <br />(OR INVERTER) IF SMALLER THAN #6 AWG COPPER WIRE PER NEC 250-64B. THE <br />GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR <br />SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER [NEC <br />250.64€.1 <br />VII ALL EXTERIOR CONDUIT SHALL BE PAINTED TO MATCH ADJACENT SURFACES. <br />VI11 ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN <br />ACCORDANCE WITH THIS CODE AND THE APPROVED MANUFACTURER'S <br />INSTRUCTIONS SUCH THAT THE ROOF COVERING SHALL SERVE TO PROTECT <br />THE BUILDING OR STRUCTURE. <br />IX RIGID CONDUIT (AND/OR NIPPLES) MUST HAVE A PULL BUSHING IO PROTECT <br />WIRES. <br />X BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE <br />GROUNDED CONDUCTOR (USE POLARIS BLOCK OR NEUTRAL BAR) <br />XI ANY :CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHL REDUCING <br />WASHERS DISALLOWED ABOVE LIVE PARTS, MEYERS HUBS RECOMMENDED <br />SOLAR CONTRACTOR <br />I) MODULE CERTIFICATIONS=WILL. INCLUDE UL1703, 2061646, IEC61730. <br />11) IF APPLICABLE, MODULE GROUNDING LUGS MUST BE INSTALLED AT THE MARKED <br />GROUNDING LUG HOLES PER THE MANUFACTURERS' INSTALLATION <br />REQUIREMENTS. <br />111) AS INDICATED BY DESIGN, OTHER NRTL LISTED MODULE GROUNDING DEVICES MAY <br />BE USED IN PLACE OF STANDARD GROUNDING LUGS AS SHOWN IN <br />MANUFACTURERDOCUMENTATIONAND APPROVED BY THE AHJ. <br />IV) CONDUIT AND WIRE SPECIFICATIONS ARE ,BASED ON MINIMUM CODE <br />REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD <br />CONDITIONS. <br />V) CONDUIT POINT OF PENETRATION FROM EXTERIORTO INTERIOR TO BE INSTALLED <br />AND SEALED WITH A SUITABLE SEALING COMPOUND. <br />VI) DC WIRING LIMITED TO MODULE FOOTPRINT W/ ENPHASEACSYSTEM. <br />VII) ENPHASE WIRING SYSTEMS: SHALL BE LOCATED ANb SECURED UNDER THE ARRAY <br />W/'SUITABLE WIRING CLIPS. <br />VI) MAx DC VOLTAGE CALCULATED USING ,MANUFACTURER PROVIDED; TEMP <br />COEFFICIENT FOR VOC UNLESS NOTAVAILABLE. <br />1)<) ALL INVERTERS, MOTOR GENERATORS, PHOTOVOLTAIC:MODULES, PHOTOVOLTAIC <br />PANELS, AC PHOTOVOLTAIC MODULES, SOURCE CIRCUIT COMBINERS, AND <br />CHARGE CONTROLLERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER SYSTEM <br />WILL BE IDENTIFIED AND LISTED FOR THE APPLICATION PER 690.4 (D). <br />X) ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. <br />. <br />.k* TRUE POWER <br />SOLAR <br />. <br />CONTRACTOR <br />TRUEPOWER SOLAR <br />PHONE: (888) 908-8947 <br />LIC. No.: CSLB #970591 <br />UNAUTHORIZED USE OF THIS <br />DRAWING SETWITHOUT WRITTEN <br />PERMISSION FROM CONTRACTOR IS IN <br />VIOLATION OF U.S. COPYRIGHT LAWS <br />AND WILL NE SUBJECT TO CIVIL <br />DAMAGES AND PROSECUTIONS. <br />LU <br />0 LO <br />0 <br />2 1,u W % /- <br />09 O U) a) 10 <br />U) LE 0 OLUU| 0 -9 <br />- Z co0 2co N ILI k *t*111%<f <br />*05 Ok-<LU = OV <br />ENGINEER OF RECORD <br />COVER PAGE <br />DATE:06.12.14 <br />" DESIGN BY: PM <br />CHECKED BY: GG <br />CD <br />Ul <br />ro <br />B C D E F G H <br />a