CEC 2022 PV NOTES <br />1.SOLAR CONTRACTOR <br />1.1.THE SOLAR PV INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDING ROOF VENTS. <br />1.2.PV MODULE MUST BE UL1703 CERTIFIED. <br />1.3.INVERTERS, MOTOR GENERATORS, PV MODULES, PV PANELS, AC MODULES, DC COMBINERS, DC-TO-DC CONVERTERS, AND CHARGE CONTROLLERS <br />INTENDED FOR USE IN PV SYSTEMS SHALL BE LISTED OR FIELD LABELED FOR THE PV APPLICATION. (CEC 690.4 (B)) <br />1.4.CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY <br />FIELD CONDITIONS. <br />1.5.MAX DC VOLTAGE IS CALCULATED USING MANUFACTURER PROVIDED TEMP COEFFICIENT FOR VOC, UNLESS NOT AVAILABLE. <br />1.6.ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. <br />1.7.CONDUIT POINT OF PENETRATION FROM EXTERIOR TO INTERIOR TO BE INSTALLED AND SEALED WITH A SUITABLE SEALING COMPOUND. <br />2.EQUIPMENT LOCATIONS <br />2.1.CONDUCTORS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING TEMPERATURE AS SPECIFIED BY CEC 690.31 (A) AND CEC <br />310.15 (B)(2). <br />2.2.ADDITIONAL AC DISCONNECTS SHALL BE PROVIDED WHERE THE INVERTER IS NOT ADJACENT TO THE UTILITY AC DISCONNECT, OR NOT WITHIN SIGHT <br />OF THE UTILITY AC DISCONNECT. <br />2.3.ALL INSTALLED EQUIPMENT SHALL BE ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO CEC APPLICABLE CODES. <br />2.4.PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT SHALL BE PROVIDED AS PER SECTION CEC <br />110.26, CEC 110.31 AND CEC 110.34. <br />2.5.ALL COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE AND SHALL BE RATED FOR OUTDOOR USAGE WHERE REQUIRED. <br />3.DC SYSTEM VOLTAGE PER 690.7 <br />3.1.PV SYSTEM DC CIRCUITS ON OR IN ONE- AND TWO-FAMILY DWELLINGS SHALL BE PERMITTED TO HAVE A MAXIMUM VOLTAGE OF 600 VOLTS OR LESS. <br />3.2.PV SYSTEM DC CIRCUITS ON OR IN OTHER TYPES OF BUILDINGS SHALL BE PERMITTED TO HAVE A MAXIMUM VOLTAGE OF 1000 VOLTS OR LESS. <br />3.3.WHERE NOT LOCATED ON OR IN BUILDINGS, MAXIMUM VOLTAGE OF 1500 VOLTS IS PERMITTED. <br />4.WIRING METHODS <br />4.1.NONMETALLIC-SHEATHED CABLE SHALL BE SECURED BY STAPLES, CABLE TIES, STRAPS, HANGERS OR SIMILAR FITTINGS AT INTERVALS THAT DO NOT <br />EXCEED 4.5 FEET. (CEC334.30) <br />4.2.CABLES SHALL BE SECURED WITHIN 12 INCHES OF EVERY CABLE ENTRY INTO ENCLOSURES SUCH AS OUTLET BOXES, JUNCTION BOXES, CABINETS, OR <br />FITTINGS. (CEC334.30) <br />4.3.EXPOSED SINGLE CONDUCTORS, WHERE SUBJECT TO PHYSICAL DAMAGE, MUST BE PROTECTED. (CEC300.4 & CEC690.31(A)) <br />4.4.CONDUCTORS INSTALLED NEAR MODULES SHALL BE RATED FOR 90°C . (CEC310.15(A)) <br />4.5.PV CIRCUIT AND PREMISES WIRING SHALL BE SEPARATED. <br />4.6.PV SYSTEM CONDUCTORS SHALL BE SEPARATED, IDENTIFIED AND GROUPED PER CEC690.31(B). <br />4.7.DC CONDUCTORS INSIDE A BUILDING SHALL BE IN A METAL RACEWAY OR MC METAL-CLAD CABLE THAT COMPLIES WITH 250.118(10), OR METAL <br />ENCLOSURES. (CEC690.31(D)) <br />4.8.WHERE RACEWAYS OR CABLES ARE EXPOSED TO DIRECT SUNLIGHT ON OR ABOVE ROOFTOPS, RACEWAYS OR CABLES SHALL BE AT MINIMUM HEIGHT <br />OF 7/8 IN. (CEC310.15(B)(2). <br />4.9.ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE APPLICATIONS. <br />4.10.RIGID CONDUIT (AND/OR NIPPLES) MUST HAVE A PULL BUSHING TO PROTECT WIRES. <br />4.11.FOR DC SINGLE-CONDUCTOR CABLE TYPE USE-2 AND SINGLE CONDUCTOR CABLE LISTED AND IDENTIFIED AS PHOTOVOLTAIC (PV) WIRE SHALL BE <br />PERMITTED IN EXPOSED OUTDOOR LOCATIONS IN PV SOURCE CIRCUITS WITHIN THE PV ARRAY. PV WIRE SHALL BE INSTALLED IN ACCORDANCE WITH <br />CEC 338.10(B)(4)(b) AND CEC 334.30. (CEC 690.31(C)(1)) <br />4.12.USE-2 IS NOT INDOOR RATED PER CEC 338.12(B)(1). <br />4.13.ALL CONDUCTORS ARE SIZED PER CEC 690.8 AND OCPDs ARE SIZED PER CEC 690.9. <br />4.14.PV SYSTEM DC CIRCUIT AND INVERTER OUTPUT CONDUCTORS AND EQUIPMENT SHALL BE PROTECTED AGAINST OVERCURRENT. EXCEPT WHEN THE <br />SHORT-CIRCUIT CURRENTS FROM ALL SOURCES DO NOT EXCEED THE AMPACITY OF THE CONDUCTORS AND THE MAXIMUM OCPD SIZE RATING <br />SPECIFIED FOR THE PV MODULE OR DC-TO-DC CONVERTER. (CEC690.9(A)) <br />4.15.FOR UNDERGROUND CONDUCTOR INSTALLATIONS, THE BURIAL DEPTH SHALL BE SELECTED PER CECTABLE 300.5. WARNING TAPE SHALL BE PLACED <br />ABOVE UNDERGROUND CONDUIT AND CONDUCTORS IN TRENCH. <br />4.16.UNGROUNDED PV SYSTEM SHOULD NOT HAVE WHITE OR GRAY COLORED DC PV CONDUCTORS. ONLY SOLIDLY GROUNDED PV SYSTEM CIRCUIT <br />CONDUCTORS, IN ACCORDANCE WITH 690.41(A)(5), SHALL BE MARKED IN ACCORDANCE WITH CEC200.6 & CEC690.31(B)(1). <br />4.17.ALUMINUM AND COPPER-CLAD ALUMINUM CONDUCTORS SHOULD NOT BE PLACED IN DIRECT CONTACT WITH CONCRETE OR EARTH. <br />(CEC250.120(B)) <br />4.18.TOP CONDUIT ENTRY FOR OUTDOOR ENCLOSURES MUST BE AVOIDED. IF NECESSARY, CONNECTION ABOVE LIVE PARTS MUST BE MADE WATERTIGHT <br />AND BE LISTED FOR THE PURPOSE. <br />5. BONDING AND GROUNDING <br />5.1.SYSTEMS WITH A GROUND-FAULT PROTECTIVE DEVICE IN ACCORDANCE WITH CEC690.41(B) SHALL HAVE ANY CURRENT-CARRYING <br />CONDUCTOR-TO-GROUND CONNECTION MADE BY THE GROUND-FAULT PROTECTIVE DEVICE. FOR SOLIDLY GROUNDED PV SYSTEMS, THE DC CIRCUIT <br />GROUNDING CONNECTION SHALL BE MADE AT ANY SINGLE POINT ON THE PV OUTPUT CIRCUIT. (CEC690.42) <br />5.2.RACKING SYSTEMS SHALL BE LISTED FOR THE PURPOSE. BONDING AND GROUNDING MUST BE IN ACCORDANCE WITH THE MANUFACTURER'S <br />INSTALLATION INSTRUCTIONS, THAT ARE LISTED AND APPROVED, USING THE SUPPLIED HARDWARE OR LISTED EQUIPMENT SPECIFIED IN THE <br />INSTRUCTIONS AND IDENTIFIED FOR THE ENVIRONMENT. (CEC690.43 & CEC110.3(B)) <br />5.3.EQUIPMENT GROUNDING CONDUCTORS FOR PV SOURCE CIRCUITS SHALL BE SIZED ACCORDING TO TABLE 250.122 AND SHALL NOT BE SMALLER THAN <br />#14 AWG WHEN NOT EXPOSED TO PHYSICAL DAMAGE. IF EXPOSED TO PHYSICAL DAMAGE THEN EGC SHALL NOT BE SMALLER THAN #6 AWG. <br />(CEC690.45 & CEC250.120(C)) <br />5.4.AC AND DC GROUNDING ELECTRODE CONDUCTORS SHALL BE PROPERLY CONNECTED AS REQUIRED BY CODE. SEPARATE ELECTRODES, IF USED, SHALL <br />BE BONDED TOGETHER. (CEC690.47, CEC250.50 & CEC250.58) <br />5.5.A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH CEC690.47, CEC250.52 AND CEC250.166 SHALL BE PROVIDED. <br />5.6.PROPERLY SIZED EQUIPMENT GROUNDING CONDUCTOR SHALL BE ROUTED WITH THE CIRCUIT CONDUCTORS. <br />(CEC690.45, CEC250.134(2) & CEC300.3(B)) <br />5.7.THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN THE GROUNDING ELECTRODE AND THE PANEL <br />(OR INVERTER) IF SMALLER THAN #6 AWG COPPER WIRE PER CEC250.64(B). <br />5.8.THE GROUNDING ELECTRODE CONDUCTOR SHALL BE CONTINUOUS PER CEC250.64(C). <br />5.9.BONDING FITTINGS SHALL BE USED ON CONCENTRIC/ECCENTRIC KNOCKOUTS WITH METAL CONDUITS FOR CIRCUITS OVER 250 VOLTS. (CEC250.97) <br />(SEE ALSO EXCEPTIONS 1 THROUGH 4) <br />5.10.BONDING FITTINGS SHALL BE USED FOR FERROUS METAL CONDUITS ENCLOSING GROUNDING ELECTRODE CONDUCTORS. (CEC250.64(E)) <br />5.11.ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH AS APPROPRIATE WHEN GROUNDING EQUIPMENT WITH <br />TERMINATION GROUNDING LUGS. <br />5.12.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THE PURPOSE, AND GROUNDING DEVICES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR <br />DIRECT BURIAL. <br />5.13.ALL CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE GROUNDED BUSHINGS AT BOTH ENDS. <br />5.14.EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN <br />ACCORDANCE WITH 250.134 OR 250.136(A) REGARDLESS OF VOLTAGE. (CEC690.43) <br />5.15.MODULES SHALL BE LISTED FOR THE PURPOSE. BONDING AND GROUNDING MUST BE IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION <br />INSTRUCTIONS, USING THE SUPPLIED HARDWARE OR LISTED EQUIPMENT SPECIFIED IN THE INSTRUCTIONS AND IDENTIFIED FOR THE ENVIRONMENT. <br />(CEC690.43 & 110.3(B)) <br />5.16.THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDED <br />CONDUCTOR TO ANOTHER MODULE. <br />6.OVERCURRENT PROTECTION <br />6.1.OVERCURRENT PROTECTION DEVICES (OCPD) IN THE DC CIRCUITS SHALL BE LISTED FOR DC OPERATION. (CEC110.3(A), (B) & 690.9(C)) <br />6.2.UNGROUNDED PV SYSTEM REQUIRES OCPD ON ONLY ONE POLARITY. OCPD TO BE USED ON EITHER POSITIVE TERMINALS OR NEGATIVE TERMINALS <br />PER CEC690.9(C). <br />6.3.WHEN INSTALLING A NEW BREAKER AND MATCH EXISTING PANEL CIRCUIT BREAKER, MAKE, MODEL, STYLE AND AIC RATING. <br />7.ELECTRICAL CONNECTIONS <br />7.1.CRIMP TERMINALS SHALL BE LISTED AND INSTALLED USING A LISTED TOOL SPECIFIED FOR USE IN CRIMPING THOSE SPECIFIC CRIMPS. (CEC110.3(B) & <br />110.14) <br />7.2.PRESSURE TERMINALS SHALL BE LISTED FOR THE ENVIRONMENT AND TIGHTENED TO MANUFACTURER RECOMMENDED TORQUE SPECIFICATIONS. <br />(CEC110.11, 110.3(B) & 110.14) <br />7.3.CONNECTORS MUST BE LISTED FOR THE VOLTAGE OF THE SYSTEM AND HAVE APPROPRIATE TEMPERATURE AND AMPACITY. (CEC110.3(B) & 110.14) <br />7.4.POWER DISTRIBUTION BLOCKS SHALL BE LISTED. (CEC690.4(B) & CEC314.28(E)) <br />7.5.TERMINALS CONTAINING MORE THAN ONE CONDUCTOR SHALL BE LISTED FOR MULTIPLE CONDUCTORS. (CEC110.14(A) & 110.3(B)) <br />7.6.CONNECTORS AND TERMINALS USED OTHER THAN CLASS B AND C STRANDED CONDUCTORS (FINE STRANDED CONDUCTORS) SHALL BE LISTED AND <br />IDENTIFIED FOR USE WITH SPECIFIC CONDUCTOR CLASS OR CLASSES. (CEC110.14(A) & 110.3(B)) <br />7.7.CONNECTORS THAT ARE READILY ACCESSIBLE AND OPERATING AT OVER 30 VOLTS REQUIRE A TOOL FOR OPENING. (CEC690.33(C)) <br />8.INVERTERS <br />8.1.INVERTERS SHALL BE LISTED TO UL 1741. (CEC690.4(B)) NOTE: GRID-TIED SYSTEM INVERTERS NEED TO BE IDENTIFIED FOR USE IN INTERACTIVE POWER <br />SYSTEMS. <br />8.2.PHOTOVOLTAIC INVERTERS SHALL BE EQUIPPED WITH DC GROUND FAULT PROTECTION AND ARC FAULT CIRCUIT PROTECTION TO REDUCE FIRE <br />HAZARDS. (CEC690.41, CEC690.11) <br />8.3.GRID INTERACTIVE INVERTERS SHALL BE EQUIPPED WITH ANTI-ISLANDING CIRCUITRY.(CEC705.40) <br />9.SIGNS AND LABELS <br />9.1.ALL INTERIOR AND EXTERIOR DC CONDUIT, ENCLOSURES, RACEWAYS, CABLE ASSEMBLIES, JUNCTION BOXES, COMBINER BOXES AND DISCONNECTS <br />SHALL BE MARKED ACCORDING TO CEC690.31(G)(3), & 690.53. <br />9.2.THE MARKINGS ON THE CONDUITS, RACEWAYS AND CABLE ASSEMBLIES SHALL BE AT EVERY 10 FEET, WITHIN ONE FOOT OF ALL TURNS OR BENDS AND <br />WITHIN ONE FOOT ABOVE AND BELOW ALL PENETRATIONS OF ROOF/CEILING ASSEMBLIES, WALLS AND BARRIERS. (CEC690.31(G)(4)) <br />9.3.THE MARKINGS SAY ''WARNING: PHOTOVOLTAIC POWER SOURCE" AND HAVE 3/8-INCH (9.5 MM) MINIMUM-SIZED WHITE LETTERS ON A RED <br />BACKGROUND. THE SIGNS SHALL BE MADE OF REFLECTIVE WEATHER RESISTANT MATERIAL. (CEC690.31 (G)(3) & (CEC690.31(G)(4)) <br />9.4.WHERE PV CIRCUITS ARE EMBEDDED IN BUILT-UP, LAMINATE OR MEMBRANE ROOFING MATERIALS IN ROOF AREAS NOT COVERED BY PV MODULES <br />AND ASSOCIATED EQUIPMENT, THE LOCATION OF CIRCUITS SHALL BE CLEARLY MARKED. (CEC690.31(G)(1)) <br />9.5.ALTERNATE POWER SOURCE PLACARD SHALL BE PLASTIC, ENGRAVED IN A CONTRASTING COLOR TO THE PLAQUE. THIS PLAQUE WILL BE ATTACHED <br />USING AN APPROVED METHOD. IF EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS REQUIRED <br />BY THE NEC. <br />10.DISCONNECT NOTES <br />10.1.AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH. <br />10.2.DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING LIVE ARE CONNECTED TO THE <br />TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS). <br />10.3.THE PV SYSTEM DISCONNECTING MEANS SHALL BE INSTALLED AT A READILY ACCESSIBLE LOCATION PER (CEC690.13(A)). <br />10.4.FOR DC SIDE OF UNGROUNDED PV SYSTEM, DISCONNECTING MEANS ARE REQUIRED ON BOTH LEGS OF PV CIRCUIT FOR UNGROUNDED SYSTEM PER <br />CEC690.15. <br />10.5.DISCONNECTS USED IN DC CIRCUITS SHALL BE LISTED FOR DC OPERATION AND LOCATED AS ALLOWED BY THE AHJ. (CEC110.3) <br />11.TERMINAL NOTES <br />11.1.ALL TERMINALS SHALL BE RATED FOR AT LEAST 75C. <br />11.2.ALL TERMINALS SHALL BE DUAL RATED FOR USE WITH COPPER AND ALUMINUM. <br />12.MODULE CONNECTORS NOTES: <br />12.1.IDENTICAL CONNECTORS FROM THE SAME MANUFACTURER AND OF THE SAME TYPE MUST BE USED ON MODULE AND ON THE OTHER SIDE OF THE <br />CONNECTION. CROSS-MATING ANY CONNECTOR MUST BE A UL APPROVED CONNECTION. <br />13.PROTECTION NOTES <br />13.1.GROUND FAULT PROTECTION IN ACCORDANCE WITH CEC230.95 AND CEC705.32 <br />13.2.ALL EQUIPMENT TO BE RATED FOR BACKFEEDING. CIRCUIT BREAKERS WHICH ARE CLEARLY MARKED “LINE” AND “LOAD” ARE NOT SUITABLE FOR <br />BACKFEED. <br />13.3.INSTALLER SHALL BE RESPONSIBLE FOR VERIFYING THAT ALL BREAKERS ARE SUITABLE FOR BACKFEED AND THAT IF GFP IS PRESENT ON MAIN SERVICE <br />DISCONNECT THAN ALL SOLAR FEEDERS, CONNECTED TO MAIN BUS, SHALL HAVE GFP PER CEC215.10 & CEC705.32 EXCEPTION. <br />13.4.ARC-FAULT CIRCUIT PROTECTION:PHOTOVOLTAIC SYSTEMS OPERATING AT 80 VOLTS DC OR GREATER BETWEEN ANY TWO CONDUCTORS SHALL BE <br />PROTECTED BY A LISTED PV ARC-FAULT CIRCUIT INTERRUPTER OR OTHER SYSTEM COMPONENTS LISTED TO PROVIDE EQUIVALENT PROTECTION. FOR <br />PV SYSTEMS NOT INSTALLED ON OR IN BUILDINGS, PV OUTPUT CIRCUITS AND DC-TO-DC CONVERTER OUTPUT CIRCUITS THAT ARE DIRECT BURIED OR <br />INSTALLED IN METALLIC RACEWAYS ARE PERMITTED WITHOUT ARC-FAULT CIRCUIT PROTECTION. (CEC690.11) <br />13.5.RAPID SHUTDOWN: PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A RAPID SHUTDOWN FUNCTION TO REDUCE SHOCK HAZARD <br />FOR EMERGENCY RESPONDERS IN ACCORDANCE WITH 690.12(A) THROUGH (D). <br />13.6.WHERE THE SOLAR SERVICE SWITCH OVERCURRENT PROTECTION IS LOCATED MORE THAN 10 FT FROM THE POINT OF UTILITY SERVICE CONNECTION, <br />CABLE LIMITERS FOR EACH UNGROUNDED CONDUCTOR SHALL BE INSTALLED AT THE POINT OF SERVICE INTERCONNECTION. <br />13.7.FOR ARC ENERGY REDUCTION FOR BREAKERS WITH TRIPS OF 1200A OR HIGHER, ONE OF THE METHODS MENTIONED IN NEC 240.87(B) SHALL BE USED. <br />14.DATA MONITORING NOTES <br />14.1.INVERTERS MAY HAVE DATA ACQUISITION SYSTEM BUILT INTO THEM OR IT CAN BE ADDED VIA OPTIONAL COMPONENTS. PLEASE CHECK WHILE <br />ORDERING IF OPTIONAL DAS COMPONENTS NEEDS TO BE ORDERED SEPARATELY. <br />705.11 SUPPLY SIDE CONNECTIONS <br />AN ELECTRIC POWER PRODUCTION SOURCE, WHERE CONNECTED ON THE SUPPLY SIDE OF THE SERVICE DISCONNECTING MEANS AS PERMITTED IN <br />230.82(6), SHALL COMPLY WITH 705.11(A) THROUGH (E). <br />(A) OUTPUT RATING <br />THE SUM OF THE POWER SOURCE CONTINUOUS CURRENT OUTPUT RATINGS ON A SERVICE, OTHER THAN THOSE CONTROLLED IN ACCORDANCE WITH <br />705.13, SHALL NOT EXCEED THE AMPACITY OF THE SERVICE CONDUCTORS. <br />(B) CONDUCTORS <br />THE POWER SOURCE OUTPUT CIRCUIT CONDUCTORS FROM THE SERVICE CONDUCTORS POINT OF CONNECTION TO THE FIRST OVERCURRENT <br />PROTECTION DEVICE SHALL BE SIZED IN ACCORDANCE WITH 705.28 AND IN NO CASE SIZED SMALLER THAN 6 AWG COPPER OR 4 AWG ALUMINUM. <br />THESE CONDUCTORS SHALL BE INSTALLED IN ACCORDANCE WITH 230.30 OR 230.43. <br />(C) OVERCURRENT PROTECTION <br />THE POWER SOURCE OUTPUT CIRCUIT CONDUCTORS SHALL BE PROTECTED FROM OVERCURRENT IN ACCORDANCE WITH 705.30. IF FUSES ARE NOT <br />INTEGRAL WITH THE DISCONNECTING MEANS, THE DISCONNECTING MEANS SHALL BE LOCATED ON THE SERVICE SIDE OF THE FUSES. WHERE THE <br />POWER SOURCE OUTPUT CIRCUIT CONDUCTORS MAKE THEIR CONNECTION TO THE SERVICE OUTSIDE OF A BUILDING, THEY SHALL BE PROTECTED BY <br />OVERCURRENT DEVICES IN A READILY ACCESSIBLE LOCATION OUTSIDE THE BUILDING OR AT THE FIRST READILY ACCESSIBLE LOCATION WHERE THE <br />POWER SOURCE CONDUCTORS ENTER THE BUILDING. WHERE THE POWER SOURCE OUTPUT CIRCUIT CONDUCTORS MAKE THEIR CONNECTION TO THE <br />SERVICE INSIDE A BUILDING, THEY SHALL BE PROTECTED WITH ONE OF THE FOLLOWING METHODS: <br />(1)WITH AN OVERCURRENT DEVICE LOCATED WITHIN 3 M (10 FT) OF CONDUCTOR LENGTH IN DWELLING UNITS AND 5 M (16.5 FT) IN OTHER THAN <br /> DWELLING UNITS FROM THE POINT OF CONNECTION TO THE SERVICE <br />(2)IN OTHER THAN A DWELLING UNIT, WITH AN OVERCURRENT DEVICE LOCATED WITHIN 20 M (71 FT) OF CONDUCTOR LENGTH FROM THE POINT <br />OF CONNECTION TO THE SERVICE, PROVIDED THAT CABLE LIMITERS INSTALLED IN ALL UNGROUNDED CONDUCTORS ARE LOCATED WITHIN 5 M <br />(16.5 FT) OF CONDUCTOR LENGTH FROM THE POINT OF CONNECTION TO THE SERVICE <br />(D) CONNECTIONS <br />THE CONNECTION OF POWER SOURCE OUTPUT CIRCUIT CONDUCTORS TO THE SERVICE CONDUCTORS SHALL BE MADE USING LISTED CONNECTORS AS <br />DESCRIBED IN 110.14 AND COMPLY WITH ALL ENCLOSURE FILL REQUIREMENTS ANY MODIFICATIONS TO EXISTING EQUIPMENT SHALL BE MADE IN <br />ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS OR THE MODIFICATION MUST BE EVALUATED FOR THE APPLICATION AND HAVE A FIELD <br />LABEL APPLIED. FOR METER SOCKET ENCLOSURES OR OTHER EQUIPMENT UNDER THE EXCLUSIVE CONTROL OF THE ELECTRIC UTILITY, ONLY <br />CONNECTIONS APPROVED BY THE ELECTRIC UTILITY SHALL BE PERMITTED. <br />(E) GROUND-FAULT PROTECTION <br />FOR CONNECTIONS RATED 1000 AMPERES OR MORE TO SOLIDLY GROUNDED WYE SERVICES EXCEEDING 150 VOLTS TO GROUND BUT NOT EXCEEDING <br />1000 VOLTS, PHASE-TO-PHASE, GROUND-FAULT PROTECTION MEETING THE REQUIREMENTS OF 230.95 SHALL BE PROVIDED. <br />CAUTION: <br />1.CHECK THAT YOU HAVE SPACE BETWEEN MAIN BREAKER AND UTILITY METER TO MAKE LINE SIDE TAP. <br />2.CABLE LIMITERS MAY BE REQUIRED PER NOTE 13.6 OF PROTECTION NOTES. <br />FIRE SAFETY REQUIREMENTS <br />CBC 1505.9 ROOFTOP MOUNTED PHOTOVOLTAIC PANEL SYSTEMS. <br />ROOFTOP RACK-MOUNTED PHOTOVOLTAIC PANEL SYSTEMS SHALL BE TESTED, LISTED AND IDENTIFIED WITH A FIRE CLASSIFICATION IN ACCORDANCE WITH <br />UL 2703. LISTED SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS AND THEIR LISTING. THE FIRE <br />CLASSIFICATION SHALL COMPLY WITH TABLE 1505.1 BASED ON THE TYPE OF CONSTRUCTION OF THE BUILDING. <br />CFC 1205.2 ACCESS AND PATHWAYS. <br />ROOF ACCESS, PATHWAYS, AND SPACING REQUIREMENTS SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS CFC 1205.2.1 THROUGH CFC 1205.3.3. <br />PATHWAYS SHALL BE OVER AREAS CAPABLE OF SUPPORTING FIRE FIGHTERS ACCESSING THE ROOF. PATHWAYS SHALL BE LOCATED IN AREAS WITH <br />MINIMAL OBSTRUCTIONS, SUCH AS VENT PIPES, CONDUIT OR MECHANICAL EQUIPMENT. <br />CFC 1205.3 OTHER THAN GROUP R-3 BUILDINGS. <br />ACCESS TO SYSTEMS FOR BUILDINGS, OTHER THAN THOSE CONTAINING GROUP R-3 OCCUPANCIES, SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS <br />CFC 1205.3.1 THROUGH CFC 1205.3.3. <br />CFC 1205.3.1 PERIMETER PATHWAYS. <br />THERE SHALL BE A MINIMUM 6-FOOT-WIDE (1829 MM) CLEAR PERIMETER AROUND THE EDGES OF THE ROOF. <br />EXCEPTION: WHERE EITHER AXIS OF THE BUILDING IS 250 FEET (76 200 MM) OR LESS, THE CLEAR PERIMETER AROUND THE EDGES OF THE ROOF SHALL BE <br />PERMITTED TO BE REDUCED TO A MINIMUM WIDTH OF 4 FEET (1219 MM). <br />CFC 1205.3.2 INTERIOR PATHWAYS. <br />INTERIOR PATHWAYS SHALL BE PROVIDED BETWEEN ARRAY SECTIONS TO MEET THE FOLLOWING REQUIREMENTS: <br />1.PATHWAYS SHALL BE PROVIDED AT INTERVALS NOT GREATER THAN 150 FEET (45 720 MM) THROUGHOUT THE LENGTH AND WIDTH OF THE ROOF. <br />2.A PATHWAY NOT LESS THAN 4 FEET (1219 MM) WIDE IN A STRAIGHT LINE TO ROOF STANDPIPES OR VENTILATION HATCHES. <br />3.A PATHWAY NOT LESS THAN 4 FEET (1219 MM) WIDE AROUND ROOF ACCESS HATCHES, WITH NOT FEWER THAN ONE SUCH PATHWAY TO A PARAPET <br />OR ROOF EDGE. <br />CFC 1205.3.3 SMOKE VENTILATION. <br />THE SOLAR INSTALLATION SHALL BE DESIGNED TO MEET THE FOLLOWING REQUIREMENTS: <br />1.WHERE NONGRAVITY-OPERATED SMOKE AND HEAT VENTS OCCUR, A PATHWAY NOT LESS THAN 4 FEET (1219 MM) WIDE SHALL BE PROVIDED <br />BORDERING ALL SIDES. <br />2.WHERE GRAVITY-OPERATED DROPOUT SMOKE AND HEAT VENTS OCCUR, A PATHWAY NOT LESS THAN 4 FEET (1219 MM) WIDE ON NOT FEWER THAN <br />ONE SIDE. <br />3.SMOKE VENTILATION OPTIONS BETWEEN ARRAY SECTIONS SHALL BE ONE OF THE FOLLOWING: <br />3.1.A PATHWAY NOT LESS THAN 8 FEET (2438 MM) WIDE. <br />3.2.WHERE GRAVITY-OPERATED DROPOUT SMOKE AND HEAT VENTS OCCUR, A PATHWAY NOT LESS THAN 4 FEET (1219 MM) WIDE ON NOT <br />FEWER THAN ONE SIDE. <br />3.3.A PATHWAY NOT LESS THAN 4 FEET (1219 MM) WIDE BORDERING 4-FOOT BY 8-FOOT (1219 MM BY 2438 MM) VENTING CUTOUTS EVERY <br />20 FEET (6096 MM) ON ALTERNATING SIDES OF THE PATHWAY. <br />CFC 1205.4 BUILDINGS WITH RAPID SHUTDOWN. <br />BUILDINGS WITH RAPID SHUTDOWN SOLAR PHOTOVOLTAIC SYSTEMS SHALL HAVE PERMANENT <br />LABELS IN ACCORDANCE WITH SECTIONS CFC 1205.4.1 THROUGH CFC 1205.4.3. <br />NOTE TO CONTRACTOR: <br />CONTRACTOR HAS THE FULL RESPONSIBILITY TO CHECK AND VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS. ANY <br />DISCREPANCIES SHALL BE REPORTED TO THE ENGINEER BEFORE PROCEEDING WITH THE WORK. ANY WORK STARTED <br />BEFORE CONSULTATION AND ACCEPTANCE BY THE ENGINEER SHALL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR AND <br />SHALL BE SUBJECT TO CORRECTION BY THEM WITHOUT ADDITIONAL COMPENSATION. <br />STANDARD SYMBOL LEGEND <br />(N)NEW <br />(E)EXISTING <br />PROVIDING FIREPROOFING OF INTERIOR PENETRATIONS TO MAINTAIN EXISITNG FIRE RATING OF SPACES AND ROOMS. <br />GENERAL ELECTRICAL NOTES FOR PHOTOVOLTAIC SYSTEM <br />THIS PHOTOVOLTAIC INSTALLATION SHALL BE IN ACCORDANCE WITH THE 2022 EDITION OF THE CALIFORNIA ELECTRICAL CODE (CEC) CURRENTLY <br />BEING ENFORCED BY THE AUTHORITY HAVING JURISDICTION (AHJ), PARTICULARLY ARTICLE 690, SOLAR PHOTOVOLTAIC (DC) SYSTEMS. <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br /> <br />D <br />O <br />W <br />T <br />O <br />W <br />N <br /> <br />P <br />L <br />A <br />Z <br />A <br />40 <br />7 <br /> <br />E <br /> <br />1 <br />s <br />t <br /> <br />S <br />T <br />. <br />, <br /> <br />S <br />A <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br /> <br />9 <br />2 <br />7 <br />0 <br />1 <br />JO <br />B <br /> <br />N <br />U <br />M <br />B <br />E <br />R <br />: <br />AP <br />N <br />: <br /> <br />3 <br />9 <br />8 <br />- <br />5 <br />1 <br />6 <br />- <br />1 <br />9 <br />SP <br />R <br />E <br />C <br />K <br /> <br />S <br />O <br />L <br />A <br />R <br /> <br />& <br /> <br />D <br />E <br />S <br />I <br />G <br />N <br />30 <br />0 <br />0 <br /> <br />F <br /> <br />D <br />A <br />N <br />V <br />I <br />L <br />L <br />E <br /> <br />B <br />L <br />V <br />D <br />. <br />, <br /> <br />S <br />U <br />I <br />T <br />E <br /> <br />4 <br />2 <br />2 <br />AL <br />A <br />M <br />O <br />, <br /> <br />C <br />A <br /> <br /> <br />9 <br />4 <br />5 <br />0 <br />7 <br />41 <br />9 <br /> <br />E <br /> <br />1 <br />s <br />t <br /> <br />S <br />T <br />. <br />, <br /> <br />S <br />A <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br /> <br />9 <br />2 <br />7 <br />0 <br />1