<br /> <br /> <br /> <br /> <br /> <br /> <br /> <br />This document is a Property of BTCPower Inc. and shall not be <br />copied, reproduced, or used as the basis for sale or manufacture <br />of apparatus without written permission. <br />23-Sep-22 Rev D <br />360kW High Power DC Charger <br />INSTALLATION AND USER’S MANUAL <br />Page 33 of 89 <br />INSTALLATION <br /> <br />TOWER AC Input – Input Terminal Lug and Ground Lug <br />Terminal Lug P/N Opening per Pole Wire Range Torque Requirement <br />2-600L2 2 600kcmil – 2AWG <br />(copper or aluminum) <br />46 lb-ft <br /> <br />Ground Lug P/N Opening per Pole Wire Range Torque Requirement <br />600TP 6 600kcmil – 2AWG <br />(copper or aluminum) <br />46 lb-ft <br /> <br />• Use 90°C Wire. <br />• Copper: 2 wires of 350 kcmil - 600 kcmil per Input Phase <br />• Aluminum: 2 wires of 500 kcmil - 600 kcmil per Input Phase <br />• Termination Lugs are rated to +90°C <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br />DANGER – HIGH VOLTAGE <br />Installer shall put “DANGER – HIGH VOLTAGE” label in clearly visible area near the grid wiring. <br /> <br />NOTE <br />The system is not phase rotation sensitive, thus there is no concern over the phasing of <br />the termination of the AC Lines.