PART 1 - GENERAL CONDITIONS <br />1.01 SUMMARY <br />A.Work Included: All labor, materials, appliances, tools, equipment, facilities, transportation and <br />services necessary for and incidental to performing all operations in connection with furnishing, <br />delivery and installation of the work of this Division, complete, as shown on the drawings and/or <br />specified herein. The work includes, but is not limited to: <br />1.Examine all divisions for related work required to be included as work under this Division. <br />2.General provisions and requirements for electrical work. <br />1.02 REFERENCES <br />A.Drawings and general provisions of the Contract, including General and Supplementary Conditions <br />and Division 01, apply to these Specifications. <br />B.In addition, the products covered in this Specification, except as noted, shall be designed, <br />manufactured, and tested in accordance with the latest revisions of the applicable standards of: <br />1.ANS - American National Standards Institute <br />2.ASTM - American Society for Testing and Materials <br />3.IEEE - Institute of Electrical and Electronics Engineers <br />4.NEC - National Electrical Code (NFPA 70) <br />5.NECA - National Electrical Contractors Association: "Standard of Installation" <br />6.NEMA - National Electrical Manufacturers Association <br />7.NFPA - National Fire Protection Association <br />8.UL - Underwriters Laboratories, Inc. <br />1.03 SUBMITTALS (ADDITIONAL REQUIREMENTS) <br />A.General: Submit the following in accordance with the Conditions of the Contract and Division 01 <br />Specification Sections, and these Specifications. <br />B.Product Data: Submit product data for each type of product specified. <br />C.Shop Drawings: Submit shop drawings for the following: <br />1.Switchboards. <br />2.Transformers. <br />3.Panelboards. <br />4.Lighting fixtures, supports, and controls. <br />1.04 QUALITY ASSURANCE <br />A.Qualifications of Manufacturer: Company specializing in manufacturing products specified in these <br />Specifications with minimum five years documented experience. <br />B.Electrical Component Standard: Components and installation shall comply with NFPA 70, "National <br />Electrical Code." <br />C.NEMA and UL Compliance: Products shall comply with applicable requirements of NEMA and UL <br />standards. Provide products and components listed and labeled by UL. <br />D.NECA Installation Standards: Perform work in accordance with NECA "Standard of Installation." <br />E.Source Quality Control: Quality control testing shall meet applicable Underwriters' Laboratories Inc. <br />Standards. <br />F.Electrical contractor shall perform all work in strict accordance with all local, state, and national <br />governing codes. <br />1.05 DELIVERY, STORAGE AND HANDLING <br />A.General: Deliver, store, protect, and handle products to the site in accordance with the General and <br />Supplementary Conditions, Division 01 Specification Sections, and these Specifications. <br />B.Store and protect product in accordance with manufacturer's instructions, and in a manner to prevent <br />damage from the elements, personnel, equipment, and moisture. <br />1.06 PROJECT CONDITIONS OR SITE CONDITIONS <br />A.Verify that field measurements are as shown prior to commencing the work. <br />PART 2 - PRODUCTS <br />2.01 MATERIALS AND EQUIPMENT <br />A.Materials, equipment, and devices shall, as a minimum, meet requirements of UL, where UL <br />standards are established for those items, and requirements of NFPA 70. <br />2.02 RACEWAYS <br />A.Metal Conduit and Tubing: <br />1.Rigid Metal Conduit: Steel, hot-dipped galvanized including the threads, with an outer coating of <br />zinc bichromate, complete with one coupling and one end thread protector, manufactured in <br />accordance with ANSI C80.1 and UL 6. Fittings: threaded, hot-dipped galvanized, manufactured <br />in accordance with ANSI C80.4. <br />a.Where indicated, provide galvanized rigid steel conduit and fittings with polyvinyl chloride <br />(PVC) coating of nominal .020 inch (20 mil ) thickness conforming to NEMA RN-1, Type A, <br />Robroy Industries, or equal. <br />2.Intermediate Metal Conduit: Hot-dipped galvanized steel including the threads, manufactured in <br />accordance with UL 1242. <br />3.Electrical Metallic Tubing: Welded, electro-galvanized thin wall steel tubing, manufactured in <br />accordance with ANSI C80.3 and UL 797. Maximum size: 2". Fittings: compression type <br />(indenter or setscrew type not allowed); gland compression type, zinc plated steel body, <br />cadmium plated malleable iron nut, O-Z/Gedney. <br />4.Flexible Metal Conduit: Hot-dipped galvanized steel interlocking, single strip type manufactured <br />in accordance with UL1. Connectors: squeeze type, malleable iron, cadmium plated, straight and <br />angle connectors for all sizes and twist-in connectors for 1/2" and 3/4" flexible metal conduit. <br />5.Liquidtight Flexible Conduit: Hot-dipped galvanized steel strip core with extruded liquid-tight <br />polyvinyl jacket. Use O-Z/Gedney Type UAG, or equal. Liquid-tight fittings. ANSI/NEMA FB 1. <br />Connectors: Cadmium plated malleable iron body and nut, cadmium plated steel ferrule, <br />insulated throat, integral cast external ground lug, O-Z/Gedney. <br />B.Nonmetallic Conduits: <br />1.Rigid Nonmetallic Conduit: NEMA TC 2 and UL 651, Schedule 40. Polyvinyl chloride (PVC) <br />heavy-wall conduit, with tapered sleeve couplings, rated and labeled for use with 90°C rated <br />conductors, manufactured in accordance with ANSI C33.91. Fittings: NEMA TC-3, cemented <br />type, from the same manufacturer as the conduit. <br />2.PVC and ABS Plastic Fittings: NEMA TC 9-1. Match to conduit type and material. <br />3.Conduit, Tubing, and Duct Accessories: Types, sizes, and materials complying with <br />manufacturer's published product information. Mate and match accessories with raceway. <br />C.Conduit Bodies: Provide types, shapes, and sizes as required to suit individual applications and NEC <br />requirements. Provide matching gasketed covers secured with corrosion resistant screws. For <br />metallic conduit and tubing, use metallic conduit bodies. Use bodies with threaded hubs for threaded <br />raceways. <br />D.Wireways and Auxiliary Gutters: Provided electrical wireways and gutters shall be of types, sizes, and <br />number of channels as indicated. Fittings and accessories including but not limited to couplings, <br />offsets, elbows, expansion joints, adapters, hold-down straps, and end caps shall match and mate <br />with wireway or gutter as required for complete system. Where specifications are not indicated, select <br />to fulfill wiring requirements compling with applicable provisions of NEC. Use sheet steel wireways <br />with screw-on covers and corrosion resistant hardware. For dry locations coat with rust inhibitor and <br />finish with gray baked enamel. For wet locations use hot-dipped galvanized material finished with <br />gray baked enamel, provide gaskets for covers. <br />E.Surface Raceway: <br />1.Provide sizes and channels as indicated. Provide fittings that match and mate with raceway. <br />2.Surface metal raceway: Construct of galvanized steel with snap-on covers, with 1/8" mounting <br />screw knockouts in base approximately 8" O.C.. Finish with manufacturer's standard prime <br />coating suitable for painting. Provide raceways of types suitable for each application required. <br />Provided by Hoffman Engineering Co., the Wiremold Co., or approved equal. <br />3.Surface Nonmetallic Raceway: Two-piece construction, manufactured of rigid PVC compound <br />with matte texture and manufacturer's standard color. Raceway and system components shall <br />meet UL 94 requirements for nonflammable, self-extinguishing characteristics. Provided by <br />Hubbell, Inc., Panduit Corp., The Wiremold Co., or approved equal. <br />F.Accessories: <br />1.General: Reducers, bushings, washers, etc., shall be cadmium plated malleable iron of the <br />shape and dimension best suited for the application. <br />2.Seals for Walls and Floor Penetrations: Malleable iron body, oversize sleeve, sealing ring, <br />pressure clamp and rings and sealing grommet, hex head cap screws, O-Z/Gedney Type FSK, <br />or equal. <br />3.Fire Seals: Heat activated intumescent material, elastomeric sealing ring, socket head cap <br />screws, steel pressure discs and flange, O-Z/Gedney Type CFSF, Nelson Flame Seal, or equal. <br />4.End bells: Hot-dipped galvanized, threaded malleable iron, O-Z/Gedney Type THS, or equal. <br />5.Bushings 1-1/4" and smaller: High-impact thermo-setting phenolic, 150°C, O-Z/Gedney Type <br />"A", or equal. Bushings 1-1/2" and larger: Hot-dipped galvanized with thermosetting phenolic <br />insulation, 150°C, O-Z/Gedney Type "B", or equal. <br />6.Locknuts 1-1/2" and smaller: Zinc plated heavy stock steel, O-Z/Gedney, or equal. Locknuts 2" <br />and larger: Cadmium plated malleable iron, O-Z/Gedney, or equal. <br />7.Hubs: Cadmium plated malleable iron, tapered threads, neoprene "O" ring, insulated throat, <br />O-Z/Gedney, or equal. <br />8.Expansion Fittings: Hot-dipped galvanized malleable iron with bonding jumpers. Linear: <br />O-Z/Gedney Type AX and TX, or equal. Linear, with deflection: O-Z/Gedney Type AXDX, or <br />equal. <br />9.Escutcheons: Chrome plated sectional floor and ceiling plates, Crane No. 10, or equal. <br />2.03 WIRE AND CABLE <br />A.Provide wire and cable suitable for the temperature, conditions, and location where installed, except <br />as otherwise indicated. <br />1.Conductor: Copper. Provide solid conductor for #10 AWG and smaller. Provide stranded <br />conductors for sizes #8 AWG and larger. <br />a.Use stranded conductors at motors and other applications where subject to vibration, and for <br />control circuits. <br />2.Minimum Size Conductor: #12 AWG, except as otherwise indicated. <br />a.Control circuits: #14 AWG. <br />3.Insulation voltage rating: 600 volts. <br />B.Building wire and cable: Single conductor insulated wire. Insulation: ANSI/NFPA 70, Type <br />THHN/THWN, rated 75°C or Type XHHW, rated 90°C. <br />C.Connectors: Provide UL Listed factory fabricated, solderless metal connectors of sizes, ampacity <br />ratings, materials, types and classes for applications and for services indicated. Use connectors with <br />temperature ratings equal to or greater than those of the wires upon which used. <br />D.Pull Cord: 1/8" polypropylene or nylon. <br />2.04 BOXES AND FITTINGS <br />A.Provide indicated types, sizes, and NEMA enclosure classes. Where not indicated, provide units of <br />types, sizes, and classes appropriate for the use and location. Provide all items complete with covers <br />and accessories required for the intended use. Provide gaskets for units in damp or wet locations. <br />1.Materials and Finishes: <br />a.Sheet steel: Flat rolled, code gauge, galvanized steel. <br />b.Fasteners for general use: Corrosion resistant screws and hardware, including cadmium and <br />zinc plated items. <br />c.Fasteners for wet or damp locations: Stainless steel screws and hardware. <br />d.Cast metal for boxes, enclosures and covers: Copper-free aluminum except as otherwise <br />indicated. <br />e.Exterior finish: Gray-baked enamel for items exposed in finished locations except as <br />otherwise indicated. <br />f.Painted interior finish: Where indicated, white baked enamel. <br />g.Fittings for boxes, cabinets, and enclosures: Conform to UL 514B. Malleable iron or <br />zinc-plated steel for conduit hubs, bushings and box connectors. <br />B.Metal outlet, device, and small wiring boxes: <br />1.General: Conform to UL 514A and UL 514B. Boxes shall be of type, shape, size, and depth to <br />suit each location and application. <br />2.Steel Boxes: NEMA OS 1. Boxes shall be sheet steel with stamped knockouts, threaded screw <br />holes and accessories suitable for each location including mounting brackets and straps, cable <br />clamps, exterior rings and fixture studs. <br />3.Cast Aluminum Boxes: Copper-free aluminum with gasketed covers, threaded raceway entries, <br />and features and accessories suitable for each location including mounting ears, threaded screw <br />holes for devices and closure plugs. <br />C.Pull and junction boxes: <br />1.General: Conform to UL 50, for boxes over 100 cubic inches in volume. Boxes shall have <br />bolted-on covers of material same as box, and shall be of the size and shape to suit the <br />application. <br />2.Steel Boxes: Sheet steel with welded seams. Where necessary to provide a rigid assembly, <br />construct with internal structural steel bracing. <br />3.Hot-Dip Galvanized Steel Boxes: Sheet steel with welded seams. Where necessary to provide a <br />rigid assembly, construct with internal structural steel bracing. Hot-dip galvanize after fabrication. <br />Cover shall be gasketed. <br />2.05 WIRING DEVICES <br />A.General: Provide wiring devices, in types, characteristics, grades, colors, and electrical ratings for <br />applications indicated which are UL listed and which comply with NEMA WD 1 and other applicable <br />UL and NEMA standards. Coordinate color selection, prior to ordering materials, with <br />Architect/Engineer. <br />B.Receptacles: UL 498 and NEMA WD 6. Straight blade, two-pole, three-wire grounding type, as <br />indicated below: <br />1.Duplex: 20Amps, 125V, NEMA 5-20R, Heavy Duty - Hubbell #5362 <br />2.Duplex, GFCI [1]: 20Amps, 125V, NEMA 5-20R, Heavy Duty - Hubbell #GF5362 <br />3.Simplex: 20Amps, 125V, NEMA 5-20R, Heavy Duty - Hubbell #5361 <br />4.Simplex: 20Amps, 250V, NEMA 6-20R, Heavy Duty - Hubbell #5461 <br />5.Simplex, Locking [2]: 20Amps, 125V, NEMA L5-20R, Heavy Duty - Hubbell #2310 <br />Notes: <br />1.GFCI receptacles shall protect downstream receptacles on same circuit. <br />2.Provide locking receptacle with black nylon face, except as indicated otherwise. <br />C.Switches: UL20 and NEMA WD 1. Quiet toggle type AC switch. Rating and type as indicated below: <br />1.Single Pole: 20Amps, 120/277V, Heavy Duty - Hubbell #HBL-1221 <br />2.Double Pole: 20Amps, 120/277V, Heavy Duty - Hubbell #HBL-1222 <br />3.Three Way: 20Amps, 120/277V, Heavy Duty - Hubbell #HBL-1223 <br />4.Single Pole w/Pilot Light [1]: 20Amps, 120/277V, Heavy Duty - Hubbell #HBL-1221-PL7 <br />5.Single Pole w/Keyed Switch: 20Amps, 120/277V, Heavy Duty - Hubbell #HBL-1221-L <br />6.Momentary Contact [2]: 20Amps, 120/277V, Heavy Duty - Hubbell #HBL-1557 <br />Notes: <br />1.For switch with pilot light, the light is "ON" when the load is "ON". <br />2.For momentary contact type switch, operation is three position - two circuit momentary contact <br />and center off. <br />D.Wall Plates: Single and combination, of types, sizes, and with ganging and cutouts as indicated. <br />Provide plates which mate and match with wiring devices to which they are attached, and are from <br />the same manufacturer. Provide metal screws for securing plates to devices with screw heads <br />colored to match finish of plates. Provide wall plate color to match wiring devices except as otherwise <br />indicated. Provide wall plates with engraved legend where indicated. Conform to requirements for <br />electrical identification. <br />1.Interior Areas: Smooth, high-impact resistant plastic, of the same manufacturer as the device. <br />a.Voice, data, or video communications system outlets: Same as for wiring devices except with <br />3/8" or 1" rubber grommets as required. <br />b.Surface mounted outlet boxes: Zinc coated sheet steel rounded edges, same size as outlet <br />box. <br />c.Kitchen and food preparation areas: Polished stainless steel type, 0.04 inches thick. <br />2.Exterior areas: Weatherproof, corrosion-resistant type, die cast aluminum with self-closing <br />gasketed cover. For duplex receptacles, use Hubbell 5206-WO or equal; for wall switches, use <br />Hubbell 7420 or equal; for GFI receptacles, use manufacturer's listed plate. <br />2.06 GROUNDING AND BONDING <br />A.Materials: All materials shall be copper. Provide types indicated and sizes and ratings required to <br />comply with NEC. Where types, sizes, ratings, and quantities indicated are in excess of NEC <br />requirements, the more stringent requirements and the greater size, rating, and quantity indications <br />govern. <br />B.Wire and cable conductors shall be as follows, except as otherwise indicated: <br />1.Equipment grounding conductor: Green insulated copper. <br />2.Grounding electrode conductor: Stranded copper cable. <br />3.Bare copper conductors: Shall conform to the following: <br />a.Solid Conductors: ASTM B 3. <br />b.Assembly of Stranded Conductors: ASTM B 8. <br />c.Tinned Conductors: ASTM B 33. <br />C.Connector products: <br />1.General: Listed and labeled as grounding connectors for the materials used. <br />2.Pressure Connectors: High-conductivity plated units. <br />3.Bolted Clamps: Heavy-duty units listed for the application. <br />4.Exothermic Welded Connections: Provided in kit form and selected for the specific types, sizes, <br />and combinations of conductors and other items to be connected. <br />D.Grounding electrodes: <br />1.Ground Rods: Copper-clad steel with high-strength steel core and electrolytic-grade copper <br />outer sheath, molten-welded to core. Size: 3/4" diameter by 10 feet long. <br />2.Plate Electrodes: Copper plates, minimum 0.10 inch thick, size as indicated. <br />E.Test (ground) wells: Precast concrete, 12" round x 18" deep open bottom valve box, with cast iron <br />grate cover plate marked "GROUND". <br />2.07 SUPPORTING DEVICES <br />A.Supports: Individual conduits shall be rigidly supported and clamped with one hole malleable iron <br />conduit clamps, conduit beam clamps, conduit hangers, or wall brackets, as necessary for the type of <br />construction and as indicated. The use of perforated flat steel straps or wire for supporting conduits <br />will not be permitted. <br />B.Support Attachments: Kwik-bolt, sleeve anchors, wedge anchors, toggle bolts, and hollow all <br />anchors, as manufactured by Hilti or Red Head. <br />C.Light steel framing: Light steel framing members for conduit hangers and other supports shall be <br />formed from 12 gauge (minimum) steel, unless otherwise indicated. <br />1.Finish: Hot-dipped galvanized steel for light steel framing members and fittings and all hardware, <br />such as hanger rods, couplings, bolts, nuts, etc., shall be electro-galvanized, unless otherwise <br />indicated. <br />2.Acceptable manufacturers: B-Line, Superstrut, Unistrut, or equal. <br />2.08 ELECTRICAL IDENTIFICATION <br />A.Manufacturers: Brady, Ideal Industries, Markal, Panduit, Thomas & Betts. <br />B.Electrical identification products: <br />1.Adhesive Marking Labels for Raceway and Metal-clad Cable: Pre-printed, flexible, self-adhesive <br />labels with legend indicating voltage and service (Emergency, Power, Lighting, Air Conditioning, <br />Voice and Data Communications, Control, Fire Alarm and Detection, Public Address (Paging), <br />Electronic Security). <br />2.Label Size, as follows: <br />a.Raceways 1" and Smaller: 1-1/8" high by 4" long. <br />b.Raceways Larger than 1": 1-1/8" high by 8" long. <br />3.Color: Black legend on orange background. <br />4.Colored Adhesive Marking Tape for Raceways, Wires, and Cables: Self-adhesive vinyl tape not <br />less than 3 mils thick by 1" to 2" in width. <br />5.Pretensioned Flexible Wraparound Colored Plastic Sleeves for Raceway and Cable <br />Identification: Flexible acrylic bands sized to suit the raceway diameter and arranged to stay in <br />place by pre- tensioned gripping action when coiled around the raceway or cable. <br />6.Underground line marking tape: Permanent, bright-colored, continuous printed, plastic tape <br />compounded for direct burial service not less than 6" wide by 4 mils thick. Printed legend <br />indicative of general type of underground line below. <br />7.Wire/cable designation tape markers: Vinyl or vinyl-cloth, self-adhesive, wraparound, <br />cable/conductor markers with preprinted numbers and letters <br />8.Aluminum, wraparound, cable marker bands: Bands cut from 0.014" thick, aluminum sheet, fitted <br />with slots or ears for securing permanently around wire or cable jacket or around groups of <br />conductors. Provide for legend application with stamped letters or numbers. <br />9.Plasticized card stock tags: Vinyl cloth with preprinted and field printed legends to suit the <br />application. Orange background, except as otherwise indicated, with eyelet for fastener. <br />10.Aluminum-faced card stock tags: Weather-resistant, 18-point minimum card stock faced on both <br />sides with embossable aluminum sheet, 0.002" thick, and laminated with moisture-resistant <br />acrylic adhesive. Pre-print legend to suit the application, and punch for tie fastener. <br />11.Brass or aluminum tags: Metal tags with tamped legend, punched for fastener. Dimensions: 2" <br />by 2" by 19 gauge. <br />12.Engraved, plastic-laminated labels, signs, and instruction plates: Engraving stock melamine <br />plastic laminate, 1/16" minimum thick for signs up to 20 square inches, or 8" in length; 1/8" thick <br />for larger sizes. Engraved legend in white letter on black face and punched for mechanical <br />fasteners. <br />13.Warning and caution signs for indoor use: Shall be minimum 18 gauge steel, white porcelain <br />enamel finish, with red lettering, punched for fasteners, with colors, legend, and size appropriate <br />to the location. Lettering to read, "Danger - High Voltage", unless otherwise indicated. <br />14.Exterior metal-backed butyrate warning and caution signs: Weather-resistant, nonfading, <br />preprinted cellulose acetate butyrate signs with 20-gauge, galvanized steel backing, with colors, <br />legend, and size appropriate to the location. Provide 1/4" grommets in corners for mounting. <br />15.Fasteners for plastic-laminated and metal signs: Self-tapping stainless steel screws or #10-32 <br />stainless steel machine screws with nuts and flat lock washers. <br />16.Cable ties: Fungus-inert, self-extinguishing, one-piece, self-locking nylon cable ties, 0.18" <br />minimum width, 50 lb minimum tensile strength, and suitable for a temperature range from minus <br />50°f to 350°f. Provide ties in specified colors when used for color coding. <br />2.09 SWITCHBOARDS <br />A.Manufacturers: Eaton, General Electric, Siemens or Square D. <br />B.Materials: <br />1.Main Switchboard: Provide a totally enclosed, dead front, safety type switchboard designed for <br />voltage and service ampacity as indicated on drawings and mounted on 2-1/2" thick concrete <br />pad. <br />2.Provide a switchboard consisting of the required number of vertical sections bolted together to <br />form one metal enclosed, rigid switchboard with the following features: <br />a.The sides, top and rear covered with removable screw-on code gauge steel plates. <br />b.Include all protective devices and equipment as listed on drawings with necessary <br />interconnections. <br />c.Bus bars mounted on supports of high impact nontracking insulation material braced to <br />withstand mechanical forces exerted during 100,000 AMPS RMS symmetrical short circuit <br />conditions, or as required by serving utility. <br />3.Chemically clean steel surfaces and treat to aid bonding between paint and metal surfaces. <br />Provide high tensile strength hardware on conductors and suitable protective finish. <br />4.Provide full length copper ground bus. Secure a ground bus to each vertical section of structures <br />and extend it the entire length of the switchboard. <br />5.Provide switchboard with adequate lifting means, capable of being rolled or moved into <br />installation position and bolted directly to the floor without the use of floor sills. <br />6.Use A-B-C type bus arrangement, left-to-right, top-to-bottom and front-to-rear throughout. <br />Switchboard shall be entirely accessible from the front, including cable and bus connections, <br />unless specifically noted otherwise. <br />7.Provide group mounted, quick-break protective devices with bar connection straps, with device <br />line and load connections accessible from the front. Where "spaces" are scheduled furnish <br />entire bus except device connecting straps. Provide full height wiring gutter covers for quick <br />access to wiring terminals. <br />8.The switchboard frame work shall be made of formed steel angles securely bolted or riveted <br />together. Adjacent to each switch unit provide a lamacoid plastic name plate engraved with <br />proper circuit designation, screw-on type only. <br />9.At top of switchboard and supported on the frame, there shall be provided a pull box for <br />termination of the conduits to the board. It shall not be less than 12" in height and shall be built <br />as an integral part of the switchboard. The front of the pull box shall be removable. The entire <br />exterior of the switchboard and pull box enclosures shall be light gray per ANS -61 . <br />10.Switches shall be quick-make, quick-break of capacity and number of poles indicated. <br />11.Main busses shall be silver or tin plated copper sized on the basis of a current density to hold <br />temperature rise to 50°c above 40°c ambient. The bus structure shall be braced to withstand the <br />mechanical forces exerted during a fault as shown on the drawings. <br />12.The switchboard shall bear the label of approval of the underwriter's laboratories and shall be <br />built to NEMA and IEEE standards. Shop drawings of the proposed board shall be furnished to <br />comply with these specifications. <br />13.Circuit Breakers: <br />a.Resettable, quick-make, quick-break, bolt-in place type, trip-free, with separate trip position <br />from on and off positions. <br />b.Multiple pole breakers with common trip and one operation handle. <br />c.Wire with sequence phasing. <br />14.Furnish record drawings providing the following information; <br />a.Complete rating. <br />b.Short circuit withstand-ability of bus and lowest rated device. <br />c.Overall outline dimensions including space available for conduits. <br />d.Circuit schedule showing circuit number. <br />e.Device description. <br />f.Feeder circuit identification. <br />g.Conductor ratings and one-line diagram with each circuit device numbered. <br />15.Provide switchboards meeting U.L. Standard #UL891 and NEMA Standard PB-2. The U.L. label <br />shall appear on all switchboard sections which contain U.L. listed devices. <br />16.Provide ground fault protection on each main devices, rated 480/277 ground wye, 1000 amps or <br />larger, as follows: <br />a.U.L. listed ground sensor relay system equal to General Electric GSR. Provide ground break <br />components for each system with coordinated ground sensor (CR) and integral test winding. <br />Provide with solid state relay to operate shunt trip circuit on the switch and monitor panel. <br />b.Use time relay with the following features: <br />1)Continuously adjustable current pick-up settings of 100 to 1200 amperes. <br />2)Continuously adjustable time delay setting from instantaneous (.03 seconds) to one <br />second. <br />3)Memory function to recognize and initiate tripping on intermittent ground faults. <br />c.Install panel which: <br />1)Indicates relay operation. <br />2)Provides means for testing the system with or without interruption of electrical service. <br />3)Does not permit the ground fault system to be inadvertently left in an inactive or "off" state. <br />d.Use ground sensor for zero sequence arrangement on the main service entrance devices. <br />17.Provisions for padlocking the circuit breakers or disconnect in the "on" and "off" positions. <br />18.Provide full rated bussing (no cascading). <br />2.10 DISCONNECT (SAFETY) SWITCHES <br />A.Disconnect switches shall be rated 600 volts A.C., NEMA Type HD heavy duty, horsepower-rated, <br />quick-make/quick-break, non-fusible or fusible, Class "R", with the number of poles and ampere <br />rating as shown. Enclosure shall be NEMA Type 1, lockable. Maximum voltage, current and <br />horsepower rating shall be clearly marked on the switch enclosure. Switches equipped with <br />dual-element time-delay fuses shall be permanently labeled with fuse type and rating. <br />1.For outdoor locations, or shown as "WP" (weatherproof), the enclosure shall be NEMA Type 3R, <br />unless otherwise indicated. <br />2.11 TRANSFORMERS <br />A.Manufacturers: Eaton, General Electric, International Transformer Company, Siemens or Square D. <br />B.Material and Construction: <br />1.Dry type, rated as shown. Provide transformer cooled by natural convection of air with: <br />a.Steel enclosure. <br />b.Class H insulation. <br />c.Transformers 25 kVA or Smaller: Insulation temperature rise over 40°C ambient not to <br />exceed 115°C at full load for 185°C insulation system. <br />d.Transformers 30 kVA or Larger: Insulation temperature rise above 40°C ambient not to <br />exceed 150°C at full load for 220°C insulation system. <br />e.Suitable for indoor or outdoor installation as required or indicated on the drawings. <br />f.Compartment located where primary and secondary connections can be made. <br />g.Secure cover plates secured with captive type hardware. <br />h.Transformer coils shall be of the continuous wound construction and shall be impregnated <br />with non-hygroscopic, thermosetting varnish. <br />i.The entire transformer enclosure shall be degreased, cleaned, phosphatized, primed, and <br />finished with a GRAY, baked enamel. <br />j.The maximum temperature of the top of the enclosure shall not exceed 50°C rise above a <br />40°C ambient. <br />k.The core of the transformer shall be visibly grounded to the enclosure by means of a flexible <br />grounding conductor sized in accordance with applicable NEMA, IEEE, and ANSI standards. <br />l.Provide transformer rated 30 kVA and less with two 5 percent full capacity taps below rated <br />voltage in primary. <br />m.Provide transformers rated greater than 30 kVA with four 2-1/2 percent full capacity taps <br />below and two 2-1/2 percent above rated voltage in primary. <br />2.The average audible sound level shall not exceed 45 DB for transformers rated at 75 kVA and <br />below, nor 55 DB for transformers rated above 75 kVA, when measured in accordance with <br />NEMA Standard TRI-2.068. <br />2.12 PANELBOARDS <br />A.Manufacturers: Eaton, Siemens, General Electric, or Square D. <br />B.Materials: <br />1.Branch circuit panelboards: <br />a.Provide factory assembled, enclosed panelboards in dead front cabinets, with doors, <br />surfaced mounted or recessed as indicated, not less than 20" wide and 5-3/4" deep. Height <br />will depend on the number of breakers and spaces. <br />b.Where a control compartment is indicated, provide an integral compartment with a separate <br />hinged lockable door held with captive screws. <br />c.Provide feeder terminal lugs for both main lugs only and main breakers rated for use with <br />copper or aluminum conductors. <br />d.Provide three phase, 4 wire, solid neutral design with sequence bussing, full capacity neutral <br />and full length copper bussing including areas indicated as space only. Bussing shall be <br />braced for maximum available fault. <br />e.Provide copper neutral bus where neutral bus is indicated. Neutral bus shall be sized for <br />minimum twice the current carrying capacity of line bus. <br />f.Key all door locks alike. Provide a type written directory of circuit index card holder mounted <br />behind the door in framed card slot with plastic see through window. <br />g.Provide full size copper equipment ground bus. <br />h.All breakers shall be bolt-on type molded case. No tie handle is accepted for multi-pole <br />breaker. <br />i.Provide pad lock off devices on all breakers serving appliances, motor operated equipment, <br />HVAC equipment and other circuit as indicated on panel schedules. <br />j.120/208V, 3 Phase, 4 Wire Panelboards: General Electric Co. type NLAB, Square D Co. type <br />NQOB, or Cutler-Hammer type POW-R-LINE1. <br />k.277/480V, 3 Phase, 4 Wire Panelboards: General Electric Co. type NHB, Square D Co. type <br />NEHB, ITE, Inc. type NHB, Sylvania Co. type NH1B or Cutler-Hammer type POW-R-LINE2. <br />l.All equipment shall be listed to meet or exceed the available fault current indicated on <br />drawings. <br />m.Provide main lugs only unless scheduled otherwise. <br />n.Construct in accordance with U.L. and NEMA Standards. <br />2.Distribution Panelboards: <br />a.Provide circuit breaker type distribution panelboards with fully rated copper bus, lockable <br />molded case breakers for mains and feeders. Provide nameplates for all circuit breakers. <br />b.Busing shall be braced to withstand maximum available fault current indicated on drawings. <br />c.Provide copper neutral bus where indicated. Neutral bus shall be sized for minimum twice the <br />current carrying capacity of line bus. <br />d.Provide full size copper ground bus adequate for number of grounded circuits. <br />e.General Electric Co. type NCP and type CCB, or Square D Co. types HCN and HCM, or <br />Cutler-Hammer type POW-R-LINE3 and POW-R-LINE4B. <br />3.Circuit breakers: <br />a.Resettable, quick-make, quick-break, bolt-in place type, trip-free, with separate trip position <br />from on and off positions. <br />b.Multiple pole breakers with common trip and one operation handle. <br />c.If handle ties are required, install only handle ties provided by circuit breaker Manufacturer. <br />d.Wire with sequence phasing. <br />e.Circuit breakers shall be rated to meet or exceed the available fault current indicated on <br />drawings. <br />2.13 OVERCURRENT PROTECTIVE DEVICES <br />A.Manufacturers: <br />1.Circuit Breakers: <br />a.General Electric <br />b.Square D <br />c.Siemens <br />d.Eaton <br />2.Fuses: Bussmann only. <br />B.Materials and fabrication: <br />1.Circuit Breakers: Molded case, quick-make, quick-break, thermal-magnetic, trip-free with <br />individual inverse time tripping mechanism on each pole. Terminal lugs rated for copper and <br />aluminum conductors. Minimum 10,000 amperes interrupting capacity, RMS symmetrical short <br />circuit rating shall be as required. All breakers shall meet or exceed the maximum available fault <br />current as indicated on single line diagram. <br />a.Use magnetic-only circuit breakers for motor applications. <br />b.Provide Class A (5ma sensitivity) breakers where GFI type breakers are required. <br />c.Provide "HACR" type circuit breakers for HVAC loads. Ratings shall be as indicated on the <br />drawings. <br />d.No tie handle on multi-pole circuit breaker is accepted. <br />e.Provide ambient compensated type breaker where the breaker is installed in the ambient in <br />excess of 40°C (104°F). <br />2.13 OVERCURRENT PROTECTIVE DEVICES <br />1.Fuses, as follows, unless otherwise indicated: <br />a.Class RK1: <br />1)250V; LPN-RK, Lowpeak <br />2)600V; LPS-RK <br />b.Class L: KRP-C, Hi-Cap <br />2.14 MOTOR CONTROLLERS <br />A.Manual motor controllers: NEMA ICS 6. AC general purpose Class A manually operated, full voltage <br />controller with thermal overload element. Also provide red pilot light, auxiliary contacts: 2 N.O. and 2 <br />N.C., and push button operator. Enclosure: NEMA ICS 6, Type 1 except as otherwise shown. <br />B.Magnetic motor controllers: Provide full voltage, non-reversing, across the line, magnetic controller, <br />except where another type is indicated. <br />1.Control Circuit: Control circuit shall be 120 volts, except as otherwise indicated. Provide control <br />power transformer integral with controller where no other supply of 120 volt control power is <br />indicated. Provide control power transformer with adequate capacity to operate connected pilot, <br />indicating and control devices, plus 100 percent spare capacity. <br />2.Combination Controller: <br />a.Circuit Breaker Type: NEMA AB 1. Motor circuit protector; molded-case circuit breaker type <br />with magnetic only trip element calibrated to coordinate with the actual locked rotor current of <br />the connected motor and the controller overload relays. Provide breakers that are factory <br />assembled with the controller, interlocked with unit cover or door, and arranged to disconnect <br />the controller. Provide motor circuit protectors with field adjustable trip elements as specified <br />in "Overcurrent Protective Devices." <br />b.Fuse Type: NEMA KS 1. Enclosed knife switch with externally operable handle. Fuse <br />interrupting rating: 200,000 rms amperes. Fused or non-fused as indicated; quick-make, <br />quick-break switch; factory assembled with controller and arranged to disconnect it. For <br />fused switches, provide rejection-type fuse clips and fuses rated as indicated. Interlock switch <br />with unit cover or door. <br />A.Multispeed motor controllers: Match controller to motor type, application, and to number of speeds. <br />Conform to the requirements for magnetic motor controllers. Provide auxiliary devices as indicated. <br />Provide auxiliary switches, 2 N.O. and 2 N.O., except as otherwise indicated. Provide all required <br />relays factory installed in controller enclosure. <br />2.15 LIGHTING <br />A.Manufacturers: As indicated herein, and as shown on the Lighting Fixture Schedule. <br />B.Lighting Fixtures, General: <br />1.Work covered includes manufacturing, equipping, wiring, and assembling of all lighting fixtures. <br />Provide lighting fixtures complete for each and every light outlet in the type, quality, and size of <br />fixture indicated in lighting fixture schedule. <br />2.The lighting fixtures shown on fixture schedule are marked with the corresponding type letter, <br />indicating thereby the particular type of fixture to be installed on the respective outlets. <br />3.Include a lighting fixture on every light outlet shown, unless otherwise indicated to be omitted. If <br />the type of lighting fixture is not specifically noted, provide without extra cost to the Owner, a <br />lighting fixture of the same type called for under a similar condition elsewhere on the Contract <br />Drawings. <br />4.Catalog number on the lighting fixture schedule are for the purpose of indicating the general <br />type, quality, and size of fixtures that will be required. The use of Catalog Numbers for a lighting <br />fixture does not necessarily include all accessories that may be required for a complete and <br />operational installation. <br />5.All luminaries and other lighting equipment delivered to the job complete, wired and including all <br />supporting means, such as plaster frames, supports, hangers, canopies, sockets, holds, all <br />current or voltage modifiers, such as ballasts, starters, all light control materials; specifically <br />diffusers, louvers, lenses, reflectors and refractors. <br />6.All lighting fixtures constructed and installed in accordance with local building codes and <br />directives by the NFPA and shall bear the label of approval of the U.L. All materials new and of <br />best grade of approved manufacturing standards. Workmanship of highest order to assure <br />trouble-free operation and durability of equipment. Lighting fixtures constructed by labor <br />agreeable with that employed on the project. <br />7.Lighting fixtures to be designed for highest relative efficiency and service. Maintenance to be <br />simple and re-lamping possible without use of special tools. <br />8.Provide all light-sources, lamps and other light-producing media called for and suitable for <br />specified equipment and functions. <br />C.Lighting fixtures: <br />1.Luminaries to use not less than #16 gauge SF-2 wire. No splice or tap located within a fixture <br />arm, stem or chain. Wire continuous from lamp socket, or from internally mounted ballast or <br />driver, to splice with building wire whether splice box is mounted on fixture or attached to <br />building. <br />2.Lighting fixture body parts, comprising the lighting fixture housing, reflectors, wire channels, end <br />plates, ballast housing, and similar body parts, to be made of extruded aluminum, galvanized <br />stampings, or bonderized steel, as indicated in the lighting fixture schedule. Wireways to have <br />adequate wiring space, accessible after fixture installation. Housing adequately ventilated where <br />required. All screws and nuts have rust-proof finish. <br />3.Where recessed lighting fixtures are installed in ceiling finished with acoustical tile or grid <br />system, the lighting fixture shall conform to the patterns indicated on the Architectural Reflected <br />Ceiling Plan. <br />4.The final installation must present a symmetrical appearance, with all lighting fixtures free of any <br />damage and thoroughly clean. <br />5.Provide all additional means necessary to support lighting fixtures that would put excessive <br />stress on the ceiling system. <br />6.Lighting fixtures mounted end-to-end and used as a raceway to be mechanically bonded <br />together to insure continuity of ground. Lighting fixtures used as "feed through" to have wireways <br />of adequate size. <br />7.All plastic lens of shielding for fluorescent lighting fixtures to be made from 100% virgin acrylic <br />unless otherwise specified. <br />D.Additional Fixture Related Requirements: <br />1.Recessed lighting fixtures in plaster or drywall ceilings to be furnished with plaster frames. <br />2.Lighting fixtures recessed in furred ceiling installed so that they can be removed from below the <br />ceiling without damage to the ceiling. <br />3.Recessed lighting fixtures to be installed with metal bar hangers for attaching to ceiling supports. <br />Lighting fixtures not supported directly from ceiling, provide galvanized steel wire as required for <br />supporting lighting fixture from structure. No wood or other combustible material to be used for <br />supporting fixtures. <br />4.Provide stems with swivel joints and canopies for all suspended lighting fixtures. Finish of all <br />exposed parts to match that of the associated fixture, unless otherwise noted. Design to conform <br />to Drawings. Wiring to pendant fixtures contained within stems. Wire entry by means of heavy <br />malleable iron hickeys. <br />5.A canopy to be furnished for each stem and all canopies to match for each fixture type, as <br />shown. <br />6.Ascertain type of ceiling construction for each fixture and provide suitable frames and fixture <br />accessories to suit. Furnish substantial mounting frames or plaster rings for all recessed and <br />semi-recessed lighting fixtures indicated or required. All frames made of galvanized steel with <br />extra cross members where required to insure maintenance or proper opening dimensions <br />during installation. <br />E.Accessories: <br />1.Provide manufacturer's standard mounting rings, trim flanges, hanger bars, spacers, supports, <br />plaster frames of nonferrous material or cadmium plated steel. Do not use painted steel plaster <br />frames. <br />DISCLAIMER <br />This plan is for illustrative purposes only and shall not be used for construction <br />or procurement of furniture. Existing conditions and access compliance have <br />not been field verified; Hendy is not responsible for any conditions that differ <br />from plan or that are out of compliance as a result. Furniture dealer shall <br />verify that the final layout of furniture meets clearances required for egress as <br />required by the authority having jurisdiction. <br />NORTH <br />HHENDY.COM <br />T (949) 851-3080 <br />4770 Campus Dr., Suite 100 <br />Newport Beach, CA 92660 <br />H <br />ISSUES AND REVISIONS <br />JOB NUMBER <br />SCALE <br />PROJECT <br />TEAM <br />All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute <br />unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written <br />consent of H. Hendy Associates. <br /> 2023 H.HendyAssociatesc <br />DATE <br />salasobrien.com <br />Project No.: <br />Irvine <br />8825 Research Drive <br />Irvine, CA 92618 <br />949.753.1553 <br />2491-60812-00 <br /> 1/8" = 1'-0" <br />04463.0000.24 <br />3080 S. HARBOR BLVD. <br />SANTA ANA, CA 92704 <br />MCGUFF <br />AB/CD <br />NO.DESCRIPTION DATE <br />PLAN CHECK SUBMITTAL 03/17/25 <br />PLAN CHECK RE-SUBMITTAL 06/06/251 <br />ELECTRICAL <br />SPECIFICATIONS <br />IE-0.03