Laserfiche WebLink
Round 1 Bowling and Amusement 12/09/2024 Paradigm Design <br />Main Place Mall Expansion Grand Rapids, MI <br />Santa Ana, California <br />Project #2309147GR <br />SECTION 23 0548 - VIBRATION AND SEISMIC CONTROLS FOR HVAC <br />PART 1 - GENERAL <br />1.1 RELATED DOCUMENTS <br />A.Drawings and general provisions of the Contract, including General and Supplementary <br />Conditions and Division 01 Specification Sections, apply to this Section. <br />1.2 SUMMARY <br />A.Section Includes: <br />1.Elastomeric isolation pads. <br />2.Elastomeric isolation mounts. <br />3.Restrained elastomeric isolation mounts. <br />4.Open-spring isolators. <br />5.Housed-spring isolators. <br />6.Restrained-spring isolators. <br />7.Housed-restrained-spring isolators. <br />8.Pipe-riser resilient supports. <br />9.Resilient pipe guides. <br />10.Air-spring isolators. <br />11.Restrained-air-spring isolators. <br />12.Elastomeric hangers. <br />13.Spring hangers. <br />14.Snubbers. <br />15.Restraint channel bracings. <br />16.Restraint cables. <br />17.Seismic-restraint accessories. <br />18.Mechanical anchor bolts. <br />19.Adhesive anchor bolts. <br />20.Vibration isolation equipment bases. <br />21.Restrained isolation roof-curb rails. <br />B.Related Requirements: <br />1.Section 210548 "Vibration and Seismic Controls for Fire Suppression" for devices for <br />fire-suppression equipment and systems. <br />2.Section 220548 "Vibration and Seismic Controls for Plumbing" for devices for plumbing <br />equipment and systems. <br />3.Structural Design Documents, Sheet S000, General Design Notes: D. Seismic Loading. <br />1.3 DEFINITIONS <br />A.IBC: International Building Code. <br />B.ICC-ES: ICC-Evaluation Service.