Laserfiche WebLink
ISSUE AND REVISIONS <br />CLIENT <br />PROJECT DESIGNER: <br />- <br />SHEET NUMBER <br />JURISDICTION APPROVAL <br />120 NEWPORT CENTER DR. <br />NEWPORT BEACH, CA 92660 <br />infojeanprescott@gmail.com <br />www.jean-prescott.com <br />714.588.0029 <br />Copyright-2023 <br />Expressly reserves its common law copyright and other <br />property rights in these plans. <br />These plans are not to be reproduced, changed or <br />copied in any form or manner whatsoever, nor are they <br />to be assigned to any third party, without first obtaining <br />the written permission and consent of Jeannice Carrillo <br />PR <br />O <br />J <br />E <br />C <br />T <br /> <br />F <br />O <br />R <br />: <br />26 <br />2 <br />2 <br /> <br />R <br />A <br />M <br />O <br />N <br />A <br /> <br />D <br />R <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />7 <br />JEANNICE CARRILLO <br />DON WALKER <br />ADDITIONAL NOTES <br />GEN1-0 <br />·All kitchen countertop outlets shall be gfci protected. cec 210.8(a)(6) <br />·12” or wider countertops require an outlet. cec 210.52(c)(1) <br />·Outlets are required within 24” of any location along the counterto. <br />·Kitchen outlets must be positioned a maximum 20” above counter top. <br />·Appliances and sinks break up the countertop run, requiring each side to comply <br />individually. cec 210.52(c). <br />·The electrical outlet requirements include islands, peninsulas, kitchen desktops, wet bars, <br />and serving bars. a large window across the back of a sink or lack of a back splash does <br />not exempt the countertop from the outlet requirements. these outlets may be in a drop <br />front cabinet face, under cabinet plug strip, pop up or tombstone type receptacle. cec <br />210.52(c)(2), (3), (4). <br />·2 – small appliance branch circuits are required for kitchens. the loads shall be balanced <br />and have no other outlets. s. cec 210.52(b)(1), (2). <br />·Individual dedicated circuits are required for all major appliances. cec 210.11(c)(1) & cec <br />422.10(a). <br />·The garbage disposal cord is limited to a range of 18” to 36” long.cec 422.16(b)(1). <br />·Dishwasher cord 36” to 48” long. romex installed with a plug is not an approved flexible <br />cord. cec 422.16(b)(2). <br />·Minimum 15 amp circuit for the dishwasher and a 15 amp circuit for the disposal. cec <br />210.23(a). <br />·If using a split outlet (2 circuits on the same yolk) for dishwasher/disposal, provide a <br />listed handle tie at the 2 circuit breakers at the panel. cec210.7(b). <br />·IC (direct contact) and at (air tight) rated cans are required for recessed lighting if <br />installed in an insulated ceiling. for occupancies with a horizontal (floor/ceiling <br />assembly) rated separation, the recessed fixtures shall be protected to the rating of the <br />separation (1 hour) or be listed for the required protection. this generally applies to <br />residential condominium construction where units are above or below other units <br />MECHANICAL <br />·A ducted residential exhaust hood is required. a metal, smooth interior surface duct <br />required on vent hood or down draft exhaust vent. aluminum flex duct not approved. <br />provide a back draft damper. cmc504.3. <br />·Minimum 30” vertical clearance to combustibles from cook top surface is required [cmc <br />921.3.1]. <br />·Kitchen local exhaust ventilation requires a minimum rate of 100cfm meeting the <br />requirements of ashra 62.2. this includes a maximum sound rating of 3 sone @ 100cfm. <br />PLUMBING <br />·A gas test is required on piping modifications (10 psi for 15 minutes). a maximum 15 psi <br />gauge is required for the gas test. a lower gas pressure test may be performed when <br />using a recording test gauge per section 1214.3 of the cpc. [cpc 1213.3]. <br />KITCHEN NOTES <br />·Gas lines that run under a slab shall run through an approved, vented, gas tight conduit. <br />[cpc1210.3.4]. <br />·An accessible shutoff valve shall be installed outside each appliance and ahead of the <br />union connected thereto and in addition to any valve on the appliance. [cpc 1210.11]. <br />·Provide maximum 6-ft- long listed gas flexible connector and shut off to freestanding <br />range. [cpc 1212.3.1]. <br />·A listed air gap is required for the dishwasher drain. [cpc 807.3]. <br />·The maximum flow rate of kitchen faucets shall not exceed 1.8 gallons per minute at 60 <br />psi. [cpc402.4]. <br />·Bathtub and shower floors and walls above bathtubs with installed shower head and in <br />shower compartments shall be finished with a nonabsorbent surface. such wall surface <br />shall extend to a height of not less than 6' above the floor [ crc r307.2]. <br />·An approved backwater valve is required for drainage piping serving fixtures located <br />below the elevation of the next upstream manhole cover. fixtures above such elevation <br />shall not discharge through the backwater valve. clean outs for drains that pass through a <br />back water valve shall be clearly identified with a permanent label stating "backwater <br />valve downstream" [cpc 710.1]. <br />·The smoke alarms shall be interconnected in such a manner that the activation of one <br />alarm will activate all of the alarms in the individual unit cfc 907.2.10.5 <br />·Smoke alarms shall receive their primary power from the building wiring and shall be <br />equipped with a battery backup cfc 907.2.10.6 <br />ELECTRICAL NOTES <br />1.- All penetrations into sound rated partitions or floor-ceiling assemblies shall <br />be sealed, lined, or insulated with an approved permanent resilient sealant. <br />2.- All rigid conduits, ducts, plumbing pipes, and appliance vents located in <br />sound rated assemblies shall be isolated from the building construction by <br />means of resilient sleeves, mounts, or a minimum 1/4" thick approved <br />resilient material. <br />3.- An approved permanent and resilient acoustical sealant shall be provided <br />along the joint between the floor and the separation walls. <br />4.- Metal ventilating and conditioned air ducts located in sound rated <br />assemblies shall be lined (exception: ducts serving only exit ways, kitchen <br />cooking facilities, and bathrooms need not be lined). <br />5.- Mineral fiber insulation shall be installed in joist spaces whenever a <br />plumbing, piping, or duct penetrates a floor-ceiling assembly or where such <br />unit passes through the plane of the floor-ceiling assembly from within a <br />wall. the insulation shall be installed to a point 12" beyond the pipe or duct. <br />this requirement is not applicable to fire sprinkler pipe, gas line or electrical <br />conduit. <br />6.- Electrical outlet boxes in opposite faces of separation walls shall be <br />separated horizontally by 24" and note that back and sides of boxes shall be <br />sealed with 1/8" resilient sealant and backed by a minimum of 2" thick <br />mineral fiber insulation. <br />7.- No wall furnace shall be installed in sound rated partitions. <br />8.- No electrical panel shall be installed in sound rated partitions. <br />9.- An approved permanent, and resilient acoustical sealant shall be provided <br />along the joint between the floor and the separation walls. <br />·Per california civil code article 1101.4 and CALGREEN section 301.1, <br />for all building alterations or improvements to a single family <br />residential property, existing plumbing fixtures in the entire house that <br />do not meet compliant flow rates will need to be upgraded. water <br />closets with a flow rate in excess of 1.6 gpf will need to be replaced <br />with water closets with a maximum flow rate of 1.28 gpf. shower <br />heads with a flow rate greater than 2.5 gpm will need to be replaced <br />with a maximum 1.8 gpm shower head. lavatory and kitchen faucets <br />with a flow rate greater than 2.2 gpm will need to be replaced with a <br />faucet with maximum flow rate of 1.2 gpm (or 1.8 gpm for kitchen <br />faucets). <br />·Bathroom fan shall be energy star compliant, ducted to terminate <br />outside the building, and controlled by a humidistat capable of being <br />adjusted between the relative humidity range of 50 to 80 percent. cgbc <br />4.506 <br />GREEN BUILDING NOTES <br />SOUND RATED PARTITION WALL NOTES <br />MECHANICAL <br />ELECTRICAL <br />1.- Receptacle outlets shall be installed in accordance with: <br />a.- At least one outlet accessible at grade level and not more than 6-1/2-ft. above grade <br /> shall be installed at the front and back of the dwelling <br />2.- All new 125-volt, single-phase, 15- and 20-ampere receptacles shall have a ground-fault <br /> circuit-interrupter (gfci or gfi ) protection when installed in the following locations: <br /> dishwashers & outdoor (weather-resistive, too) <br />3.- All 120-volt, single-phase 15- and 20-ampere branch circuits supplying new outlets <br />shall <br /> be protected by a listed arc-fault circuit interrupter (afci), combination-type, installed to <br /> provide protection of the branch circuit when installed in the single-family residence <br /> (bathrooms & garages are except)4.- Receptacles, cord connectors, and attachment plugs shall comply with the following : a. <br />all <br /> 125-volt, 15- and 20-ampere receptacles in dwellings shall be listed tamper-resistant7.- Exhaust fans with integral lighting system shall be switches separately from lighting <br />system <br /> or have a lighting system that can be manually turned on and off while allowing the fan to <br /> continue to operate for an extended period of time. <br />a.- Ducts shall not exceed a total combined horizontal length of 14 feet, including two 90 <br /> degree elbow unless permitted by the manufacture. <br />b.- Moisture exhaust ducts shall terminate outside the building and shall be equipped with <br /> back draft damper. <br />c.- The termination of the exhaust duct shall have a minimum clearance of 3'ft. from <br /> openings into the building. <br />Clothes dryers shall conform to the following: <br />SMOKE AND CARBON ALARM <br />a. On each additional story of the dwelling, including basements and habitable attics but <br />not including crawl spaces and uninhabitable attics.In dwelling or dwelling units with <br />split levels and without an intervening door between the adjacent levels, a smoke alarm <br />installed on the upper level shall suffice for the adjacent lower level provided that the <br />lower level is less than one full story below the upper level. <br />b. Alarms shall be interconnected such that the actuation of one alarm. Shall activate all <br />alarms. <br />c. Approved combined smoke alarms and carbon monoxide alarms shall be acceptable. <br />SMOKE ALARM <br />a. On every occupiable level of a dwelling unit, including basements. <br />b. Alarms shall be interconnected such that the actuation of one alarm shall activate all <br />alarms. <br />c. Approved combined smoke alarms and carbon monoxide alarms shall be acceptable. <br />CARBON MONOXIDE <br />ADDITIONAL NOTES