1. OSB OR WAFER BOARD (I.C.B.O. NER-108) MAY BE SUBSTITIUTED FOR STURCTURAL II <br />PLYWOOOD. <br />2. ALL NAILING SHALL UTILIZE COMMON NAILS FOR ALL HORIZONTAL DIAPHRAGMS. <br />3. ALL NAILING SHALL UTILIZE COMMON NAILS. <br />4. ALL SHEAR WALLS SHALL BE FULL LENGTH OF WALL IN NEW CONSTRUCTION, OR <br />LENGTH AS NOTED ON <br /> ADDITIONS. <br />5. ALL STRUCTURAL WOOD SHEAR WALLS SHALL BE COVERED, WITH A MIN. OF <br />2-LAYERS OF 15 # FELT <br /> UNDERLAYMENT PRIOR TO PLACING FINISH MATERIAL. <br />6. ALL SHEAR WALL PANELS TO BE ATTACHED TO ROOF FRAMING. <br />7. USE APPROVED PLATE WASHERS FOR ANCHOR BOLTS AND HOLD DOWN BOLTS. <br /> BOLT SIZE PLATE SIZE BOLT SIZE PLATE SIZE BOLT SIZE <br />PLATE SIZE <br /> 5/8" DIA. 3"X3"X0.229" 3/4" DIA. 2.75"x2.75"x5/16" 1" DIA. <br />3.5"x3.5"x3/8" <br /> 5/8" DIA. 3"X3"X0.229" 7/8" DIA. 3"x3"x3/8" <br />8. EXISTING 1/2" DIA. ANCHOR BOLTS AT EXISTING FOOTINGS ARE ACCEPTABLE. NEW <br />ANCHOR BOLTS AT <br /> EXISTING FOOTINGS SHALL BE THREADED AND EMBEDDED 5" INTO CONCRETE <br />FOOTING WITH EPOXY <br /> (I.C.B.O. 4945, L.A.R.R. 25185 OR EQ.) WITH 1.75 MINIMUM EDGE DISTANCE. (SPECIAL <br />INSPECTION REQ'D.) <br />9. PLATE WASHERS ARE REQUIRED FOR ALL HOLD DOWNS. <br />10. ALL HOLD DOWN ANCHOR NUTS SHALL BE TIGHTENED JUST PRIOR TO COVERING. <br />11. ALL BOLT HOLES SHALL BE DRILLED A MAXIMUM OF 1/16" OVERSIZED. <br />12. PROVIDE 1/2" EDGE DISTANCE FOR PLYWOOD EDGE NAILING. <br />13. PROVIDE 3x NOMINAL OR WIDER SILL PLATES THAT REST ON CONCRETE OR <br />MASONRY ARE REQUIRED <br /> FOR SHEAR WALL 11-12-13. <br />14. PROVIDE 3x STUDS BETWEEN ADJACENT PANELS ON SHEAR WALLS 11-12-13. <br />15. NAILS SHALL BE STAGGERED, WHERE NAILS ARE SPACED AT 2 3/4" O.C. OR LESS <br />FOR SHEAR WALLS <br /> 11-12-13. <br />16. STUCCO SHEAR WALLS SHALL UTILIZE SELF FURRING NAILS (MIN. 11-GA. 1 1/2" LONG, <br />7/16" DIA. HEAD, <br /> GALVANIZED FURRED A MIN. OF 1/4") TO ATTACH THE LATH TO THE STUDS. STAPLE <br />SHALL NOT BE USED. <br />GLUED LAMINATED LUMBER: <br />1. ALL GLUED LAMINATED MEMBERS SHALL BE COMBINATION <br />24 F - V4. CANTILEVERED OR CONTINUOUS MEMBERS SHALL BE <br />24 F - V8. <br />2. ALL GLUED LAMINATED MEMBERS SHALL BE <br />MANUFACTURED BY A FABRICATOR LICENSED BY THE CITY OF <br />SANTA ANA OR THE LOCAL <br />GOVERNING AGENCY. <br />3. ALL FABRICATION AND WORKMANSHIP SHALL BE IN <br />CONFORMANCE WITH THE CURRENT EDITION OF THE <br />STANDARD SPECIFICATIONS FOR STRUCTURAL GLUED <br />LAMINATED DOUGLAS FIR (COAST REGION) LUMBER BY THE <br />LUMBERMAN'S ASSOCIATION, AND THE CURRENT EDITION OF <br />TIMBER CONSTRUCTION. <br />4. FINISH OF THE MEMBERS SHALL BE INDUSTRIAL <br />APPEARANCE GRADE IN CONFORMACE WITH THE STANDARD <br />APPEARANCE GRADES OF THE A.I.T.C. <br />UNLESS NOTED OTHERWISE. <br />5. MEMBERS SHOWN ARE FOR DRY USE. <br />FOUNDATIONS: <br />1. THE FOLLOWING DESIGN IS BASED ON THE RECOMMENDATIONS GIVEN IN <br />THE FOLLOWING REPORT UNLESS OTHERWISE INDICATED. FOUNDATION <br />WORK SHALL BE PERFORMED IN ACCORDANCE WITH THIS REPORT. THE <br />REPORT IS PART OF THE PLANS AND SHOULD BE KEPT ON THE JOB SITE AT <br /> ALL TIMES. <br /> REPORT BY: <br /> REPORT NO: <br /> REPORT DATE: <br />2. FOUNDATION EXCAVATIONS SHALL BE EXAMINED AND IDENTIFY BY THE <br /> SOILS ENGINEER OR HIS REPRESENTATIVES PRIOR TO THE PLACEMENT <br />OF ANY REINFORCING STEEL OR CONCRETE. <br />3. THE FOUNDATION DESIGN IS BASED ON THE FOLLOWING CRITERIA: <br /> BREAKING ................................. PSF <br /> SKIN FRICTION ......................... PSF <br /> PASSIVE PRESSURE ................. PCF <br /> FRICTION COEFFICIENT............ 30 PCF (LEVEL) <br />4. VERTICAL EXCAVATIONS IN SOIL SHALL BE LIMITED TO 5 FEET VERTICAL <br />CUTS IN EXCESS OF 5 FEET SHALL BE CUT BACK AT 1:1, THE A-B-C SLOT CUT <br />PROCEDURES ARE TO BE USED. <br />5. ALL COMPACT SHALL CONFORM TO METHODS DESCRIBED IN THE SOILS <br /> REPORT. <br />6. MINIMUM SLAB ON GRADE CONSTRUCTION UNLESS NOTED OTHERWISE <br />ON THE PLANS BE 4-INCH CONCRETE REINFORCED WITH 6 x 6 - W2. 9 x W2.9 <br />WELDED WIRE MESH OVER 2-INCHES OVER 6-MIL VISQUEEN MOISTURE <br />BARRIER OVER 2-INCHES OF SAND. THE BUILDING FLOOR SLAB SHALL BE <br />SUPPORTED ON COMPACTED GRADE, BEDROCK OR APPROVED SOIL. <br />7. IF TRENCHES OR EXCAVATION OF 5 FEET OR MORE IN WHICH A PERSON <br /> MUST DESCEND, ARE REQUIRED. A PERMIT MUST BE OBTAINED FROM THE <br />CALIFORNIA DIVISION OF INDUSTRIAL SAFETY PRIOR TO THE ISSUANCE OF A <br />BUILDING PERMIT. <br />REINFORCING STEEL: <br />1. ALL REINFORCING STEEL, DOWELS AND TIES SHALL CONFROM TO ASTM <br />A 615, GRADE 60, UNLESS NOTED OTHERWISE. # 3 BARS SHALL BE ASTM <br />A 615, GRADE 40. <br />2. ALL REINFORCING STEEL SHALL BE LAPPED AS INDICATED ON THE <br />DRAWINGS. WHERE LAPS AND / OR SPLICE LOCATIONS ARE NOT <br />SPECIFICALLY INDICATED. VERIFY WITH THE ENGINEER IF A SPLICE CAN <br />BE PROVIDED. ALL REINFORCING STEEL SHALL BE LAPPED WITH A CLASS <br />"C" LAP UNLESS NOTED OTHERWISE. ALL SPLICE LOCATIONS SHALL BE <br />SHOWN ON SHOP DRAWINGS AND APPROVED PRIOR TO FABRICATON. <br />3. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A 82 AND A 185. <br />4. ALL REINFORCING STEEL IN MASONRY SHALL BE LAPPED 40 BAR DIAMETERS <br />OR TWO (2) FEET MINIMUM, UNLESS NOTED OTHERWISE. <br />FRAMING LUMBER: <br />1. ALL STRUCTURAL LUMBER SHALL BE DOUGLAS FIR OF THE FOLLOWING <br /> GRADES, CONFORMING TO STANDARD GRADING RULES FOR WEST COAST <br /> LUMBER, NO 16, UNLESS NOTED OTHEWISE: <br /> RAFTERS, JOISTS, PLATES.............................................. NO 2 <br /> 2x AND 4x BEAMS, STRINGERS, AND HEADERS............ NO 2 <br /> 6x AND 8x BEAMS, STRINGERS, AND HEADERS............ NO 1 <br /> POSTS AND TIMBERS...................................................... NO 1 <br /> STUDS............................................................. CONST. GRADE <br /> BLOCKING, AND STRIPPING.............................. STUD GRADE <br />2. PLYWOOD FOR ROOF SHEATHING SHALL BE CDX, UNLESS NOTED OTHEWISE. <br /> USE EXTERIOR TYPE, MINIMUM C-C GRADE WHERE PLYWOOD IS EXPOSED TO <br /> WEATHER. PLYWOOD FOR FLOOR SHEATHING SHALL BE CDX, UNLESS NOTED <br /> OTHEWISE. ALL PLYWOOD SHALL CONFORM TO U.S. PRODUCT STANDARD PS <br /> 1-86. EACH SHEET OF PLYWOOD SHALL BE IDENTIFIED BY A REGISTERED STAMP <br /> OR BRAND OF THE DOUGLAS FIR PLYWOOD ASSOCIATION. <br />3. ALL WOOD BEARING ON CONCRETE SHALL BE PRESSURE TREATED DOUGLAS <br />FIR. <br />4. STUDS OVER 10 FEET IN HEIGHT SUPPORTING TWO FLOORS AND A ROOF MUST <br /> BE 2x6 AT 16" O.C. UNLESS NOTED OTHERWISE. FOR STUDS GREATER THAN 16 <br /> FEET, SEE PLAN. STUDS IN CRIPPLE WALLS LESS THAN 4 FEET IN HEIGHT MAY <br /> MATCH THE STUDS ABOVE. <br />5. PROVIDE 2x SOLID BLOCKING BETWEEN JOISTS AND RAFTERS AT ALL SUPPORTS. <br /> BLOCKING SHALL BE ONE PIECE AND BE THE FULL DEPTH OF THE JOIST OR <br />RAFTER. <br />6. CROSS BRIDGING SHALL BE PROVIDED AT 8'-0" ON CENTER MAXIMUM FOR ALL <br />JOISTS AND RAFTERS MORE THAN 8" DEEP. <br />7. PROVIDE DOUBLE JOISTS UNDER PARTITIONS WHICH ARE PARALLEL TO THE <br />JOISTS. <br />8. PROVIDE SOLID, FULL BLOCKING UNDER PARTITIONS WHICH ARE <br />PERPENDICULAR TO THE JOISTS. <br />9. TOP PLATE OF ALL STUD WALLS SHALL BE TWO PIECES THE SAME SIZE AS THE <br />STUDS. SPLICES ARE TO LAP 4'-0" MINIMUM AND BE NAILED WITH 12-16d NAILS <br />MINIMUM EACH SIDE OF JOINT. <br />10. ALL NAILS SHALL BE COMMON, BOX OR SINKER, NAILING SHALL BE PER <br />CHAPTER 23 OF THE UNIFORM BUILDING CODE. <br />11. BOLT HOLES IN WOOD SHALL BE 1/32" TO 1/16" LARGER THAN THE NOMINAL BOLT <br /> DIAMETER ALL BOLTS SHALL HAVE STANDARD CUT WASHER UNDER HEAD AND <br />NUT UNLESS NOTED OTHERWISE. <br />12. ALL BOLTS SHALL BE RE-TIGHTENED PRIOR TO THE APPLICATION OF <br />SHEATHING,PLASTER, ETC.... <br />13. STRUCTURAL MEMBERS SHALL NOT BE CUT FOR PIPES, ETC.. UNLESS <br />SPECIFICALLY DETAILS. <br />14. WOOD STUDS MAY BE NOTCHED TO A DEPTH OF 25 % OF THE WIDTH MAXIMUM, <br /> EXCEPT INTERIOR NO BEARING STUDS WHICH MAY BE NOTCHED TO 40 % OF THE <br /> WIDTH MAXIMUM. STUDS MAY BE BORED TO 40 % OF THE WIDTH MAXIMUM. <br />EXCEPT INTERIOR NONBEARING STUD AND DOUBLE BEARING STUDS <br />(PROVIDED NO MORE THAN TWO SUCCESSIVE DOUBLED STUDS ARE BORED) <br />WHICH MAY BE BORED TO 60 % OF THE WIDTH MAXIMUM. BORED HOLES <br />SHALL NOT BE LOCATED AT THE SAME SECTION OF A STUD AS A CUT OR <br />NOTCH.; IN NO CASE SHALL THE EDGE OF A BORED HOLE BE NEARER THAN 5/8" <br />TO THE EDGE OF THE STUD. <br />15. PROVIDE FIRE STOPS AT ALL INTERSECTIONS OF STUD WALL AT FLOOR, CEILING <br /> AND ROOF. FIRE STOPS SHALL BE 2x NOMINAL THICKNESS OF WOOD AND SHALL <br /> BE THE FULL WIDTH OF THE ENCLOSED SPACE. PLACE FIRE STOPS AT A <br />MAXIMUM SPACING OF 8'-0" IN EACH DIRECTION AND AT THE SAME LINES AS <br />THE FIRE STOPS IN ADJACENT WALLS. <br />CONCRETE <br />1. ALL CONCRETE, UNLESS OTHERWISE, SHALL BE REGULAR WEIGHT, HARD <br /> ROCK TYPE (150 PSF). AGGREGATES SHALL CONFORM TO ASTM C33 WITH <br /> PROVEN SHRINKAGE CHARACTERISTICS OF LESS THAN 0.05 <br />2. ULTIMATE COMPRESSIVE STRENGTHS AT 28 DAYS SHALL BE: <br /> SLAB ON GRADE...... 3000 PSI CONTINUOUS FOOTINGS...... 3000 PSI <br /> PAD FOOTING.......... 3000 PSI RETAINING WALLS.................. 3000 PSI <br /> GRADE BEAMS......... 3000 PSI CASSIONS / PILES.................. 3000 PSI <br />3. CEMENT SHALL CONFORM TO ASTM C150, TYPE V. <br />4. PLACEMENT OF CONCRETE SHALL CONFORM WITH THE REQUIREMENTS OF <br />5. CONCRETE SHALL BE MAINTAINED IN A MOIST CONDITION FOR A MINIMUM <br /> OF FIVE (5) DAYS AFTER PLACEMENT. ALTERNATE METHODS WILL BE <br /> APPROVED IF SATISFACTORY PERFORMANCE CAN BE ASSURED. <br />6. KEYED CONSTRUCTION JOINTS SHALL BE USED IN ALL CASES. ALL LATINATE <br /> SHALL BE REMOVED. ALL VERTICAL JOINTS SHALL BE THROUGHTLY WETTED <br /> AND SLUSHED WITH A COAT OF NEAT CEMENT IMMEDIATELY BEFORE <br /> PLACING NEW CONCRETE. <br />7. ALL CONCRETE WITH A DESIGNATED STRENGTH GREATER THAN 2500 PSI <br /> SHALL REQUIRE CONTINUOUS INSPECTION BY AN INSPECTOR APPROVED BY <br /> THE BUILDING DEPARTMENT . <br />8. MINIMUM CONCRETE COVERAGE OF REINFORCING STEEL SHALL BE AS <br /> FOLLOWS: <br /> -CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO SOIL...........3" <br /> CONCRETE EXPOSED TO SOIL OR WEATHER: <br /> # 5 BARS, W 31 OR D 31 WIRES, AND SMALLER .......................................1 1/2" <br /> # 6 BARS, AND LARGER.....................................................................................2" <br /> CONCRETE NOT EXPOSED TO SOIL OR WEATHER OR IN CONTACT WITH SOIL: <br /> # 11 BARS, AND SMALLER.............................................................................3/4" <br /> # 14 BARS AND LARGER..............................................................................1 1/2" <br /> BEAMS AND COLUMNS................................................................................1 1/2" <br />9. PIPES OTHER THAN ELECTRICAL CONDUITS SHALL NOT BE EMBEDDED IN <br /> STRUCTURAL CONCRETE EXCEPT WHERE SPECIFICALLY APPROVED. <br />10. BEFORE NEW CONCRETE IS DEPOSITED ON OR AGAINST CONCRETE WHICH <br /> IS SET, THE SURFACE OF THE SET CONCRETE SHALL BE ROUGHENED <br /> SUFFICIENTLY TO EXPOSE THE AGGREGATE APPROXIMATELY 1/4" AND CLEANED. <br /> USE EPOXY WHERE REQUIRED. <br />11. EXPANSION BOLTS SHALL BE HILTI "KWIK" BOLTS: <br />( W / L = 0.45 MAX. TYP.) <br />GENERAL: <br />1. ALL MATERIAL AND WORKMANSHIP SHALL CONFORM TO THE <br />DRAWING <br /> AND SPECIFICATIONS. <br />2. DURING THE CONSTRUCTION PERIOD, THE CONTRACTOR SHALL BE <br /> RESPONSIBLE FOR THE SAFETY OF THE BUILDING. <br />3. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF <br />CONSTRUCTION. WHERE CONDITIONS ARE NOT SPECIFICALLY <br />INDICATED BUT ARE OF SIMILAR CHARACTER TO DETAILS SHOWN, <br />SIMILAR DETAILS OF CONSTRUCTION SHALL BE USED SUBJECT TO <br />REVIEW. <br />4. ALL DETAILS DESIGNATED AS STANDARD OR TYPICAL SHALL OCCUR <br />IN ADDITION TO ANY OTHER SPECIFIC DETAIL CALLED OUT. <br />5. ALL INFORMATION SHOWN ON THE DRAWINGS RELATIVE TO EXISTING <br />CONDITIONS IS GIVEN AS THE BEST PRESENT KNOWLEDGE. BUT <br />WITHOUT GUARANTEE OF ACURANCY. WHERE ACTUAL CONDITIONS <br />CONFLICT WITH THE DRAWINGS, THEY SHALL BE REPORTED THE <br />PROPER REVISIONS MAY BE MADE. MODIFICATION OF DETAILS OF <br />CONSTRUCTION SHALL NOT BE MADE WITHOUT WRITTEN APPROVAL. <br />CONCRETE MASONRY: <br />1. CONCRETE BLOCK UNITS SHALL CONFORM TO ASTM <br />C90-75, GRADE N-1 <br /> WITH A MINIMUM COMPRESSIVE STRENGHT OF 1500 PSI. <br />2. MORTAR SHALL CONFORM TO ASTM C270-80, TYPE S, WITH <br />A MINIMUM <br /> COMPRESSIVE STRENGTH OF 1800 PSI AT 28 DAYS. MIX: 1 <br />PART PORTLAND CEMENT, 1/2 PART LIME PUTTY, 4 1/2 PARTS <br />SAND (BY VOLUME). IF PLASTIC TYPE CEMENT IS USED, OMIT <br />LIME PUTTY. <br />3. GROUT SHALL CONFORM TO ASTM C476-80, WITH A <br />MINIMUM COMPRESSIVE STRENGTH OF 2000 PSI AT 28 DAYS. <br />MIX: 1 PART CEMENT, 3 PARTS SAND, 2 PARTS PEA GRAVEL. <br />SUFFICIENT WATER TO BRING THE MIXTURE TO A FLUID <br />CONSISTENCY. <br />4. SOLID GROUT ALL CELLS UNLESS NOTED OTHERWISE. <br />5. PROVIDE TESTS AS MAY BE REQUIRED BY THE BUILDING <br />OFFICIAL. <br />6. THE THICKNESS OF THE GROUT BETWEEN BLOCK UNITS <br />AND REINFORCING STEEL SHALL NOT BE LESS THAN 1/2", <br />BETWEEN PARALLEL REINFORCING BARS, NO LESS THAN 3/4". <br />7. IF WORK IS STOPPED ONE (1) HOUR OR LONGER, PROVIDE <br />HORIZONTAL <br /> CONSTRUCTION JOINTS BY STOPPING THE GROUT 1 1/2" <br />BELOW THE TOP OF THE BLOCK. <br />8. SEE REINFORCING STEEL NOTES AND STANDARD DETAILS <br />FOR REINFORCING REQUIREMENTS. REINFORCING STEEL IN <br />MASONRY SHALL BE LAPPED 40 BAR DIAMETERS MINIMUM. <br />9. SPECIAL INSPECTION BY AN INSPECTOR APPROVED BY <br />THE BUILDING <br /> DEPARTMENT IS NOT REQUIRED UNLESS NOTED <br />OTHERWISE. <br /> ICC ES ESR-1385 <br />EPOXY ANCHORS: <br />1. ALL EPOXY ANCHORS SPECIFIED ON THE PLANS SHALL BE BY ONE OF THE FOLLOWING <br />MANUFACTURES AND SHOULD BE INSTALLED PER THE MANUFACTURES <br />RECOMMENDATIONS: <br />HILTI RE-500 SD ICC REPORT No. ESR-2322 <br />2. CONTINUOUS SPECIAL INSPECTION BY A CITY OF SANTA ANA REGISTERED DEPUTY <br />INSPECTOR IS REQUIRED FOR ALL EPOXY ANCHOR INSTALLATIONS. <br />or SI:1 inch = 25.4 mm. <br />a.Common or box nails are permitted to be used except where otherwise stated. <br />b.Nails spaced at 6 inches on center at edges, 12 inches at intermediate supports <br /> except 6 inches at supports where spans are 48 inches or more. For nailing of <br /> wood structural panel and particleboard diaphragms and shear walls, refer to Section <br /> 2305. Nails for wall sheathing are permitted to be common, box or casing. <br />c.Common or deformed shank (6d - 2" ´ 0.113"; 8d - 21/2" ´ 0.131"; 10d - 3" ´ 0.148"). <br />d.Common (6d - 2" ´ 0.113"; 8d - 21/2" ´ 0.131"; 10d - 3" ´ 0.148"). <br />e.Deformed shank (6d - 2" ´ 0.113"; 8d - 21/2" ´ 0.131"; 10d - 3" ´ 0.148"). <br />f.Corrosion-resistant siding (6d - 17/8" ´ 0.106"; 8d - 23/8" ´ 0.128") or casing (6d - 2" ´ <br /> 0.099"; 8d - 21/2" ´ 0.113") nail. <br />g.Fasteners spaced 3 inches on center at exterior edges and 6 inches on center at intermediate <br /> supports, when used as structural sheathing. Spacing shall be 6 inches on center on the edges <br /> and 12 inches on center at intermediate supports for nonstructural applications. <br />h.Corrosion-resistant roofing nails with 7/16-inch-diameter head and 11/2-inch length for 1/2-inch <br /> sheathing and 1 3/4-inch length for 25/32-inch sheathing. <br />i.Corrosion-resistant staples with nominal 7/16-inch crown and 1 1/8-inch length for 1/2-inch <br /> sheathing and 1 1/2-inch length for 25/32-inch sheathing. Panel supports at 16 inches <br /> (20 inches if strength axis in the long direction of the panel, unless otherwise marked). <br />j.Casing (11/2" ´ 0.080") or finish (11/2" ´ 0.072") nails spaced 6 inches on panel edges, <br /> 12 inches at intermediate supports. <br />k.Panel supports at 24 inches. Casing or finish nails spaced 6 inches on panel edges, <br /> 12 inches at intermediate supports. <br />l.For roof sheathing applications, 8d nails (21/2" ´ 0.113") are the minimum <br /> required for wood structural panels. <br />m.Staples shall have a minimum crown width of 7/16 inch. <br />n.For roof sheathing applications, fasteners spaced 4 inches on center at edges, <br /> 8 inches at intermediate supports. <br />o.Fasteners spaced 4 inches on center at edges, 8 inches at intermediate supports for subfloor <br />and wall <br /> sheathing and 3 inches on center at edges, 6 inches at intermediate supports for roof sheathing. <br />p.Fasteners spaced 4 inches on center at edges, 8 inches at intermediate supports. <br />1. Joist to sill or girder 3 - 8d common (21/2" ´ 0.131") toenail <br /> 3 - 3" ´ 0.131" nails <br /> 3 - 3" 14 gage staples <br />2. Bridging to joist 2 - 8d common (21/2" ´ 0.131") toenail each end <br /> 2 - 3" ´ 0.131" nails <br /> 2 - 3" 14 gage staples <br />3. 1" ´ 6" subfloor or less to each joist 2 - 8d common (21/2" ´ 0.131") face nail <br />4. Wider than 1" ´ 6" subfloor to each joist 3 - 8d common (21/2" ´ 0.131") face nail <br />5. 2" subfloor to joist or girder 2 - 16d common (31/2" ´ 0.162") blind and face nail <br />6. Sole plate to joist or blocking 16d (31/2" ´ 0.135") at 16" o.c. typical face nail <br /> 3" ´ 0.131" nails at 8" o.c. <br />3" 14 gage staples at 12" o.c. <br />Sole plate to joist or blocking at braced 3" - 16d (31/2" ´ 0.135") at 16" braced wall panels <br />wall panel 4 - 3" ´ 0.131" nails at 16" end nail <br />4 - 3" 14 gage staples per 16" <br />7. Top plate to stud 2 - 16d common (31/2" ´ 0.162") <br />3 - 3" ´ 0.131" nails <br />3 - 3" 14 gage staples <br />8. Stud to sole plate 4 - 8d common (21/2" ´ 0.131") end nail <br />4 - 3" ´ 0.131" nails <br />3 - 3" 14 gage staples <br />2 - 16d common (31/2" ´ 0.162") <br />3 - 3" ´ 0.131" nails <br />3 - 3" 14 gage staples toenail <br />9. Double studs 16d (31/2" ´ 0.135") at 24" o.c. face nail <br />3" ´ 0.131" nail at 8" o.c. <br />3" 14 gage staple at 8" o.c. <br />10. Double top plates 16d (31/2" ´ 0.135") at 16" o.c. typical face nail <br /> 3" ´ 0.131" nail at 12" o.c. <br />3" 14 gage staple at 12" o.c. <br />Double top plates 8-16d common (31/2" ´ 0.162") lap splice <br />12-3" ´ 0.131" nails <br />12-3" 14 gage staples <br />11. Blocking between joists or rafters 3 - 8d common (21/2" ´ 0.131") toenail <br />to top plate 3 - 3" ´ 0.131" nails <br />3 - 3" 14 gage staples <br />12. Rim joist to top plate 8d (21/2" ´ 0.131") at 6" o.c. toenail <br />3" ´ 0.131" nail at 6" o.c. <br />3" 14 gage staple at 6" o.c. <br />13. Top plates, laps and intersections 2 - 16d common (31/2" ´ .162") face nail <br />3 - 3" ´ 0.131" nails <br />3 -3" 14 gage staples <br />14. Continuous header, two pieces (31/2" ´ 0.162")16" o.c. along edge <br /> 16d common <br /> 15. Ceiling joists to plate 3 - 8d common (21/2" ´ 0.131") toenail <br />5 - 3" ´ 0.131" nails <br />5 - 3" 14 gage staples <br />16. Continuous header to stud 4 - 8d common (21/2" ´ 0.131") toenail <br />17. Ceiling joists, laps over partitions (see 3 - 16d common (31/2" ´ 0.162") face nail <br /> minimum, Table 2308.10.4.1 <br /> Section 2308.10.4.1, Table 2308.10.4.1) 4 - 3" ´ 0.131" nails <br />4 - 3" 14 gage staples <br />18. Ceiling joists to parallel rafters (see <br />Section 2308.10.4.1, Table 2308.10.4.1)3 - 16d common (31/2" ´ 0.162") face nail <br />minimum, Table 2308.10.4.1 <br />4 - 3" ´ 0.131" nails <br />4 - 3" 14 gage staples <br />19. Rafter to plate 3 - 8d common (21/2" ´ 0.131") toenail <br />(see Section 2308.10.1, Table 2308.10.4.1) 3 - 3" ´ 0.131" nails <br />3 - 3" 14 gage staples <br />20. 1" diagonal brace to each stud and plate 2 - 8d common (21/2" ´ 0.131")face nail <br />2 - 3" ´ 0.131" nails <br />3 - 3" 14 gage staples <br />21. 1" ´ 8" sheathing to each bearing 3 - 8d common (21/2" ´ 0.131")face nail <br />22. Wider than 1" ´ 8" sheathing 3 - 8d common (21/2" ´ 0.131")face nail <br />to each bearing <br />23. Built-up corner studs 16d common (31/2" ´ 0.162")24" o.c. <br />3" ´ 0.131" nails 16" o.c. <br />3" 14 gage staples 16" o.c. <br />24. Built-up girder and beams 20d common (4" ´ 0.192") 32" o.c.face nail at top and <br />3" ´ 0.131" nail at 24" o.c.bottom staggered <br />3" 14 gage staple at 24" o.c 2 - 20d on opposite sides <br />2-20d common (4" ´ 0.192")face nail at ends <br />3 - 3" ´ 0.131" nails and at each splice <br />3 - 3" 14 gage staples <br />25. 2" planks 16d common (31/2" ´ 0.162")at each bearing <br />26. Collar tie to rafter 3 - 10d common (3" ´ 0.148")face nail <br />4 - 3" x 0.131" nails <br />4 - 3" 14 gage staples <br />27. Jack rafter to hip 3 - 10d common (3" x 0.148")toenail <br />4 - 3" ´ 0.131" nails <br />4 - 3" 14 gage staples <br />2 - 16d common (31/2" ´ 0.162")face nail <br />3 -3" ´ 0.131" nails <br />3 - 3" 14 gage staples <br />28. Roof rafter to 2-by ridge beam 2 - 16d common (31/2" ´ 0.162")toenail <br />3 - 3" ´ 0.131" nails <br />3 - 3" 14 gage staples <br />2-16d common (31/2" ´ 0.162")face nail <br />3 - 3" ´ 0.131" nails <br />3 - 3" 14 gage staples <br />29. Joist to band joist 3 - 16d common (31/2" ´ 0.162")face nail <br />4 - 3" ´ 0.131" nails <br />4 - 3" 14 gage staples <br />30. Ledger strip 3 - 16d common (31/2" ´ 0.162")face nail <br />4 - 3" x 0.131" nails <br />4 - 3" 14 gage staples <br />31. Wood structural panels and 1/2" and less 6dc,1 <br />particleboardb 2 3/8" ´ 0.113" nailn <br />Subfloor, roof and wall sheathing 1 3/4" 16 gageo <br />(to framing)19/32" to 3/4"8dd or 6de <br />2 3/8" ´ 0.113" nailp <br />2" 16 gagep <br />7/8" to 1"8dc <br />1 1/8" to 1 1/4"10dd or 8dd <br />Single Floor (combination subfloor-3/4"and less 6de <br />underlayment to framing)7/8" to 1"8de <br />1 1/8" to 1 1/4"10dd or 8de <br />32. Panel siding (to framing)1/2" or less6df <br />5/8"8df <br />33. Fiberboard sheathingg 1/2"No. 11 gage roofing nailh <br />6d common nail (2" ´ 0.113") <br />No. 16 gage staplei <br />25/32"No. 11 gage roofing nailh <br />8d common nail (21/2" ´ 0.131") <br />No. 16 gage staplei <br />34. Interior paneling 3/8"1/4"4dj <br />6dk <br />TABLE 2304.9.1 <br />FASTENING SCHEDULE <br />CONNECTION FASTENING LOCATION CONNECTION FASTENING LOCATION <br />N1.0 <br />NO <br />T <br />E <br />S <br />DE <br />S <br />I <br />G <br />N <br />E <br />R <br />: <br />TH <br />E <br />S <br />E <br /> <br />D <br />R <br />A <br />W <br />I <br />N <br />G <br />S <br />, <br /> <br />D <br />E <br />S <br />I <br />G <br />N <br /> <br />A <br />N <br />D <br /> <br />S <br />P <br />E <br />C <br />I <br />F <br />I <br />C <br />A <br />T <br />I <br />O <br />N <br />S <br /> <br />A <br />R <br />E <br /> <br />T <br />H <br />E <br /> <br />P <br />R <br />O <br />P <br />E <br />R <br />T <br />Y <br /> <br />A <br />N <br />D <br /> <br />C <br />O <br />P <br />Y <br /> <br />R <br />I <br />G <br />H <br />T <br /> <br />O <br />F <br /> <br />Z <br />A <br />H <br />A <br /> <br />A <br />R <br />C <br />H <br /> <br />D <br />E <br />S <br />I <br />G <br />N <br /> <br />A <br />N <br />D <br /> <br />S <br />H <br />A <br />L <br />L <br /> <br />N <br />O <br />T <br /> <br />B <br />E <br /> <br />U <br />S <br />E <br />D <br /> <br />O <br />N <br /> <br />A <br />N <br />Y <br /> <br />O <br />T <br />H <br />E <br />R <br /> <br />W <br />O <br />R <br />K <br /> <br />E <br />X <br />C <br />E <br />P <br />T <br /> <br />B <br />Y <br /> <br />A <br />G <br />R <br />E <br />E <br />M <br />E <br />N <br />T <br /> <br />W <br />I <br />T <br />H <br /> <br /> <br />Z <br />A <br />H <br />A <br /> <br />A <br />R <br />C <br />H <br /> <br />D <br />E <br />S <br />I <br />G <br />N <br />. <br /> <br />W <br />R <br />I <br />T <br />T <br />E <br />N <br /> <br /> <br /> <br /> <br />D <br />I <br />M <br />E <br />N <br />S <br />I <br />O <br />N <br />S <br /> <br />S <br />H <br />A <br />L <br />L <br />TA <br />K <br />E <br /> <br />R <br />E <br />F <br />E <br />R <br />E <br />N <br />C <br />E <br /> <br />O <br />V <br />E <br />R <br /> <br />S <br />C <br />A <br />L <br />E <br />D <br /> <br />D <br />I <br />M <br />E <br />N <br />S <br />I <br />O <br />N <br />S <br /> <br />A <br />N <br />D <br /> <br />S <br />H <br />A <br />L <br />L <br /> <br />B <br />E <br /> <br />V <br />E <br />R <br />I <br />F <br />I <br />E <br />D <br /> <br />O <br />N <br /> <br />T <br />H <br />E <br /> <br />J <br />O <br />B <br /> <br />S <br />I <br />T <br />E <br />, <br /> <br />A <br />N <br />Y <br /> <br />D <br />I <br />S <br />C <br />R <br />E <br />P <br />A <br />N <br />C <br />Y <br /> <br />S <br />H <br />A <br />L <br />L <br /> <br />B <br />E <br /> <br />B <br />R <br />O <br />U <br />G <br />H <br />T <br /> <br />T <br />O <br /> <br />T <br />H <br />E <br /> <br />N <br />O <br />T <br />I <br />C <br />E <br /> <br />O <br />F <br /> <br />Z <br />A <br />H <br />A <br /> <br />A <br />R <br />C <br />H <br /> <br />D <br />E <br />S <br />I <br />G <br />N <br /> <br />P <br />R <br />I <br />O <br />R <br /> <br />T <br />O <br /> <br />T <br />H <br />E <br /> <br />C <br />O <br />M <br />M <br />E <br />N <br />C <br />E <br />M <br />E <br />N <br />T <br /> <br />O <br />F <br /> <br />A <br />N <br />Y <br /> <br />W <br />O <br />R <br />K <br />DRAWN <br />CHECKED <br />R.H <br />DATE <br />11-18-2024 <br />SCALE <br />JOB NO. <br />24-031 <br />SHEET <br />OF SHEETS <br />90 <br />9 <br />- <br />2 <br />4 <br />6 <br />- <br />1 <br />2 <br />0 <br />4 <br />25 <br />5 <br /> <br />N <br /> <br />D <br /> <br />S <br />T <br />. <br /> <br />S <br />U <br />I <br />T <br />E <br /> <br />4 <br />0 <br />1 <br /> <br />L <br />, <br />SA <br />N <br /> <br />B <br />E <br />R <br />N <br />A <br />R <br />D <br />I <br />N <br />O <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />4 <br />0 <br />1 <br />AR <br />C <br />H <br /> <br />D <br />E <br />S <br />I <br />G <br />N <br />ZA <br />H <br />A <br />A <br />R <br />C <br />H <br />D <br />E <br />S <br />I <br />G <br />N <br />1 <br />@ <br />G <br />M <br />A <br />I <br />L <br />. <br />C <br />O <br />M <br />OW <br />N <br />E <br />R <br />PR <br />O <br />J <br />E <br />C <br />T <br />C.M <br />GA <br />R <br />A <br />G <br />E <br /> <br />C <br />O <br />N <br />V <br />E <br />R <br />S <br />I <br />O <br />N <br /> <br />T <br />O <br /> <br />A <br />D <br />U <br />MA <br />R <br />C <br />O <br /> <br />G <br />U <br />T <br />I <br />E <br />R <br />R <br />E <br />Z <br />25 <br />2 <br />2 <br /> <br />W <br />e <br />s <br />t <br /> <br />C <br />a <br />m <br />d <br />e <br />n <br /> <br />P <br />l <br />a <br />c <br />e <br />, <br /> <br />U <br />n <br />i <br />t <br /> <br /># <br /> <br />2 <br />Sa <br />n <br />t <br />a <br /> <br />A <br />n <br />a <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />4 <br />AD <br />D <br />R <br />E <br />S <br />S <br />NTS