Laserfiche WebLink
GENERAL NOTES CONTINUED <br />GENERAL <br />1.PROVIDE EACH BEDROOM, BASEMENT, AND HABITABLE ATTICS WITH <br />A MINIMUM OF ONE EXTERIOR WINDOW WITH A 44 MAXIMUM CLEAR <br />OPENING HEIGHT, 5.7 SQ. FT. MINIMUM CLEAR OPENABLE AREA <br />(MINIMUM 5.0 SQ. FT. AT GRADE FLOOR OPENINGS), 24 MINIMUM <br />CLEAR OPENABLE HEIGHT AND 20 MINIMUM CLEAR WIDTH, OR AN <br />OPENABLE EXTERIOR EXIT DOOR. (CRC R310.2.1 AND CRC R310.2.2) <br />WINDOW WELLS, LADDERS, AND STEPS SHALL COMPLY WITH CRC <br />R310.2.3. BARS, GRILLES, COVERS, ANDS SCREENS SHALL BE <br />RELEASABLE OR REMOVABLE FROM THE INSIDE WITHOUT THE USE <br />OF A KEY, TOOL, SPECIAL KNOWLEDGE, OR FORCE GREATER THAN <br />15LBS TO OPERATE THE EMERGENCY ESCAPE AND RESCUE <br />OPENINGS. (CRC R310.4) <br />2.EACH BATHROOM CONTAINING A BATHTUB, SHOWER OR <br />TUB/SHOWER COMBINATION SHALL BE MECHANICALLY VENTILATED <br />WITH ENERGY STAR APPROVED EQUIPMENT (MINIMUM 50CFM) WITH <br />AN INTEGRAL HUMIDISTAT INSTALLED. (CRC R303.3.1) <br />3.PROVIDE ATTIC CROSS VENTILATION: 1/150 OF ATTIC AREA OR 1/300 <br />WITH AT LEAST 40% BUT MORE THAN 50% OF VENTS ARE 3 FT. <br />ABOVE EAVE AND BALANCE IS AT EAVE. AS AN ALTERNATIVE IN <br />CLIMATE ZONE 16 (TRUCKEE REGION), THE NET AREA MAY BE <br />REDUCED TO 1/300 WHEN A CLASS I OR II VAPOR BARRIER IS <br />INSTALLED ON THE WARM-IN-WINTER SIDE OF THE CEILING. BAFFLES <br />ARE REQUIRED AT VENTS FOR INSULATION. PROVIDE MINIMUM OF 1 <br />INCH OF AIR SPACE BETWEEN INSULATION AND ROOF SHEATHING. <br />(CRC R806) <br />4.ENCLOSED RAFTER SPACES SHALL HAVE 1 INCH CLEAR CROSS <br />VENTILATION. (PROPERLY SIZED RAFTERS FOR INSULATION) (CRC <br />R806.3) <br />5.UNDER FLOOR CROSS VENTILATION: MINIMUM 1.0 SQ. FT. FOR EACH <br />150 SQ. FT. OF UNDER FLOOR WHEN A CLASS 1 VAPOR RETARDER IS <br />INSTALLED ON THE GROUND SURFACE THE MINIMUM AREA OF <br />VENTILATION MAY BE LIMITED TO 1SQ.FT FOR EACH 1,500 SQUARE <br />FEET OF UNDER-FLOOR ONE VENTILATION OPENING SHALL BE <br />WITHIN THREE (3) FEET OF EACH CORNER OF THE BUILDING (CRC <br />R408.1). UNVENTED CRAWL SPACES SHALL COMPLY WITH CRC <br />R408.3. <br />6.THE FOLLOWING AREAS SHALL HAVE SAFETY GLAZING: (CRC R308.4) <br />·SLIDING/SWINGING GLASS DOORS <br />·GLAZING IN WALLS AND ENCLOSURES FACING HOT TUBS, SPAS, <br />WHIRLPOOLS, SAUNAS, STEAM ROOMS, BATHTUBS, SHOWERS AND <br />SWIMMING POOLS WHERE THE GLAZING IS LESS THAN 60 INCHES <br />ABOVE THE STANDING SURFACE WITHIN THE COMPARTMENT AND <br />WITHIN 60 INCHES HORIZONTALLY OF THE WATERS EDGE (CRC <br />R308.4.5) <br />·GLAZING WITHIN A 24 ARC OF A DOOR THAT IS LESS THAN 60 INCHES <br />ABOVE THE FLOOR. GLAZING INSTALLED PERPENDICULAR TO A <br />DOOR IN A CLOSED POSITION AND WITHIN 24 INCHES OF THE DOOR <br />ONLY REQUIRES SAFETY GLAZING IF IT IS ON THE HINGE SIDE OF AN <br />INSWING DOOR. (CRC R308.4.2). <br />·GLAZING WHERE THE EXPOSED AREA IS GREATER THAN 9SQ.FT, <br />BOTTOM IS LESS THAN 18 IN. AND AT LEAST 36 IN. ABOVE THE FLOOR, <br />AND ADJACENT TO A WALKING SURFACE <br />·WITHIN 60IN. OF THE BOTTOM TREAD OF A STAIRWAY AND LESS <br />THAN 36IN. ABOVE THE LANDING <br />·GLAZING IN GUARDS AND RAILINGS <br />·GLAZING ADJACENT TO STAIRWAYS, LANDINGS, AND RAMPS WITHIN <br />36IN. HORIZONTALLY OF THE WALKING SURFACE LESS THAN 36IN. <br />ABOVE THE WALKING SURFACE <br />·PROVIDE LANDINGS AND A PORCH LIGHT AT ALL EXTERIOR DOORS. <br />LANDINGS ARE TO BE MINIMUM 3 FT DEEP X WIDTH OF DOOR. <br />LANDINGS AT REQUIRED EGRESS DOORS MAY STEP DOWN A <br />MAXIMUM OF 7.75 INCHES WHEN THE DOOR DOES NOT SWING OVER <br />THE LANDING AND 1.5 INCHES WHEN DOOR SWINGS ONTO THE <br />LANDING. OTHER THAN REQUIRED EXTERIOR EXIT DOORS MAY HAVE <br />A THRESHOLD OF 7.75 INCHES MAXIMUM; A LANDING IS NOT <br />REQUIRED IF A STAIR WITH TWO OR FEWER RISERS IS LOCATED ON <br />THE EXTERIOR SIDE AND THE DOOR DOES NOT SWING OVER THE <br />STAIRWAY. (CRC R311.3-R311.3.2) <br />FOUNDATIONS & CONCRETE SLABS <br />CONCRETE STRENGTH(S): <br />_______________________________________________________ <br />REBAR GRADES: <br />_____________________________________________________________ <br />1.SLOPE DRAINAGE 6 WITHIN THE FIRST 10FT. FROM THE FOUNDATION <br />WALL. IF PHYSICAL OBSTRUCTIONS OR LOT LINES PROHIBIT THE <br />10FT DISTANCE, A 2-5 PERCENT SLOPE SHALL BE PROVIDED TO AN <br />APPROVED ALTERNATIVE METHOD OF DIVERTING THE WATER AWAY <br />FROM THE FOUNDATION. IMPERVIOUS SURFACES SHALL ALSO BE <br />SLOPED A MINIMUM OF 2 PERCENT FOR 10FT AWAY FROM <br />STRUCTURES TO AN APPROVED DRAINAGE WAY. (CRC R401.3) <br />2.FOOTINGS SHALL EXTEND AT LEAST 12 INCHES INTO THE <br />UNDISTURBED GROUND SURFACE. (CRC R403.1.4) UNLESS ERECTED <br />ON SOLID ROCK, TO PROTECT AGAINST FROST AND FREEZING, THE <br />MINIMUM FOUNDATION DEPTH IS 18 INCHES BELOW GRADE IF <br />BETWEEN 4,000-7,000 FOOT ELEVATION AND 24 INCHES BELOW <br />GRADE FOR 7,000 FOOT ELEVATION AND ABOVE. EXCEPTION: <br />INTERIOR FOOTINGS SHALL BE A MINIMUM OF 12 INCHES BELOW <br />GRADE. (L-V 3.14) <br />3.STEPPED FOOTINGS SHALL BE USED WHEN SLOPE OF FOOTING <br />BOTTOM IS GREATER THAN 1 IN 10 (V: H). <br />4.CONCRETE SLABS: 3 ½ MINIMUM (CRC R506.1). SLABS UNDER LIVING <br />AREAS AND GARAGES SHALL BE REINFORCED WITH WIRE 6 X 6, 10 <br />GAUGE X 10 GAUGE WELDED MESH OR EQUIVALENT STEEL <br />REINFORCEMENT AND 4 THICKNESS OF 3/8 MINIMUM GRAVEL UNDER <br />THE CONCRETE SLAB. SEPARATE FROM SOIL WITH A 6 MIL <br />POLYETHYLENE VAPOR RETARDER WITH JOINTS LAPPED NOT LESS <br />THAN 6 INCHES IN LIVING AREAS. A CAPILLARY BREAK SHALL BE <br />INSTALLED WHEN A VAPOR RETARDER IS REQUIRED. <br />5.PROVIDE 18 X 24 FOUNDATION ACCESS THROUGH THE FLOOR OR <br />16X24 ACCESS THROUGH A PERIMETER WALL. (CRC R408.4) <br />6.MINIMUM SILL BOLTING: ½ ANCHOR BOLTS OR APPROVED ANCHORS <br />AT 6 FT. O.C. MAXIMUM FOR ONE-STORY (CRC R403.1.6). USE <br />ANCHOR BOLTS AT 4 FT. O.C. MAXIMUM FOR THREE STORY <br />CONSTRUCTION. EMBED BOLTS 7 MINIMUM. THE ANCHOR BOLTS <br />SHALL BE PLACED IN THE MIDDLE THIRD OF THE WIDTH OF THE <br />PLATE. LOCATE END BOLTS NOT LESS THAN 7 BOLT DIAMETERS, NOR <br />MORE THAN 12 FROM ENDS OF SILL MEMBERS. IN SDC D0 AND <br />ABOVE: PROVIDE 3X3X0.229 PLATE WASHERS ON EACH BOLT AT <br />BRACED OR SHEAR WALL LOCATIONS, STANDARD CUT WASHERS <br />SHALL BE PERMITTED FOR ANCHOR BOLTS NOT LOCATED IN <br />BRACED/SHEAR WALL LINES. <br />CLEARANCES AND TREATMENT FOR WOOD FRAMING <br />1.WEATHER EXPOSED GLU-LAM, BEAMS AND POSTS SHALL BE <br />PRESSURE TREATED OR SHALL BE WOOD OF NATURAL RESISTANCE <br />TO DECAY (CRC R317.1.3 & 5) <br />2.COLUMNS EXPOSED TO THE WEATHER OR IN BASEMENTS WHEN <br />SUPPORTED ON CONCRETE PIER OR METAL PEDESTALS SHALL BE <br />PRESSURE TREATED OR NATURAL RESISTANCE TO DECAY UNLESS <br />THE PIER/PEDESTALS PROJECT 1 ABOVE CONCRETE OR 6 ABOVE <br />EARTH AND THE EARTH IS COVERED BY AN APPROVED IMPERVIOUS <br />MOISTURE BARRIER. (CRC R317.1.4 EXC. 1) <br />3.COLUMNS IN ENCLOSED CRAWL SPACES OR UNEXCAVATED AREAS <br />LOCATED WITHIN THE PERIPHERY OF THE BUILDING SHALL BE <br />PRESSURE TREATED OR NATURAL RESISTANCE TO DECAY UNLESS <br />THE COLUMN IS SUPPORTED BY A CONCRETE PIER OR METAL <br />PEDESTAL OF A HEIGHT 8 OR MORE AND THE EARTH IS COVERED BY <br />AN IMPERVIOUS MOISTURE BARRIER. (CRC R317.1.4 EXC. 2) <br />4.DECK POSTS SUPPORTED BY CONCRETE PIERS OR METAL <br />PEDESTALS PROJECTING NOT LESS THAN 1 ABOVE A CONCRETE <br />FLOOR OR 6 ABOVE EXPOSED EARTH. (CRC R317.1.4 EXC. 3) <br />WALLS <br />1.POSITIVE POST TO BEAM CONNECTION SHALL BE PROVIDED TO <br />ENSURE AGAINST UPLIFT AND LATERAL DISPLACEMENT. (CRC R502.9 <br />& CBC 2304.9.7) <br />2.ALL FASTENERS USED FOR ATTACHMENT OF SIDING & INTO <br />PRESSURE TREATED LUMBER SHALL BE OF A CORROSION <br />RESISTANT TYPE (CRC R317.3). <br />3.FIRE-BLOCK IN CONCEALED SPACES OF STUD WALLS/PARTITIONS, <br />VERTICALLY AT CEILING/FLOOR LEVELS, HORIZONTALLY AT 10FT. <br />INTERVALS. FIRE-BLOCK AT SOFFITS, DROP CEILINGS/SIMILAR <br />LOCATIONS & IN CONCEALED SPACES AT THE TOP/BOTTOM OF STAIR <br />STRINGERS. (CRC R302.11) <br />4.PROVIDE APPROVED BUILDING PAPER UNDER THE BUILDING SIDING <br />AND APPROVED FLASHING AT EXTERIOR OPENINGS (CRC R703.2). <br />SPECIFY A MINIMUM OF 2 LAYERS OF GRADE D PAPER UNDER <br />STUCCO AND 2 LAYERS OF 15LB FELT (OR EQUIVALENT) UNDER <br />STONE VENEER. <br />5.STUCCO SHALL HAVE A MINIMUM CLEARANCE TO EARTH OF 4 <br />INCHES AND 2 INCHES TO PAVED SURFACES WITH AN APPROVED <br />WEEP SCREED. (CRC R703.7.2.1) MASONRY STONE VENEER SHALL BE <br />FLASHED BENEATH THE FIRST COURSE OF MASONRY AND PROVIDED <br />WITH WEEP HOLES IMMEDIATELY ABOVE THE FLASHING. (CRC <br />R703.8.5 AND R703.8.6) <br />ROOF <br />1.PROVIDE A MINIMUM 22 X 30 ACCESS OPENING TO ATTIC (CRC <br />R807); MAY BE REQUIRED TO BE 30X30 TO REMOVE THE LARGEST <br />PIECE OF MECHANICAL EQUIPMENT PER THE CALIFORNIA <br />MECHANICAL CODE. <br />2.ROOF DRAINS/GUTTERS REQUIRED TO BE INSTALLED PER THE <br />CALIFORNIA PLUMBING CODE WITH LEAF/ DEBRIS PROTECTION ALSO <br />INSTALLED. <br />4.ASPHALT SHINGLES WITH SLOPED ROOFS 2/12 TO 4/12 SHALL HAVE <br />TWO LAYERS OF UNDERLAYMENT APPLIED PER CRC R905.2.2. <br />GARAGE AND CARPORT <br />1.GARAGE SHALL BE SEPARATED FROM THE DWELLING UNIT & ATTIC <br />AREA BY ½ INCH GYPSUM BOARD APPLIED TO THE GARAGE SIDE. <br />GARAGE BENEATH HABITABLE ROOMS SHALL BE SEPARATED BY NOT <br />LESS THAN 5/8 TYPE X GYPSUM BOARD. STRUCTURE SUPPORTING <br />FLOOR/CEILING ASSEMBLIES USED FOR REQUIRED SEPARATIONS <br />SHALL HAVE ½ GYPSUM BOARD INSTALLED MINIMUM. DOOR <br />OPENINGS FROM THE GARAGE TO THE DWELLING SHALL BE SOLID <br />WOOD/STEEL DOORS OR HONEYCOMB STEEL DOORS NOT LESS <br />THAN 1 3/8 THICK OR A 20 MINUTE RATED FIRE DOOR. DOORS SHALL <br />BE SELF-CLOSING & SELF-LATCHING. NO OPENINGS DIRECTLY INTO A <br />SLEEPING ROOM FROM THE GARAGE. WHEN THE DWELLING AND <br />GARAGE HAS FIRE SPRINKLERS INSTALLED PER R309.6 AND R313, <br />DOORS INTO THE DWELLING UNIT FROM THE GARAGE ONLY NEED TO <br />BE SELF-CLOSING AND SELF-LATCHING. (CRC R302.5.1 & T-R302.6) <br />(CARPORTS OPEN ON TWO OR MORE SIDES AND NO ENCLOSED <br />AREAS ABOVE DO NOT REQUIRE A SEPARATION) <br />2.DUCTS PENETRATING THE GARAGE TO DWELLING SEPARATION <br />SHALL BE A MINIMUM OF 26 GAUGE WITH NO OPENINGS INTO THE <br />GARAGE. (CRC R302.5.2) <br />3.PENETRATIONS THROUGH THE GARAGE TO DWELLING SEPARATION <br />WALL (OTHER THAN DUCTS AS LISTED ABOVE) SHALL BE <br />FIRE-BLOCKED PER CRC SECTION R302.11, ITEM #4. <br />4.GARAGE AND CARPORT FLOOR SURFACES SHALL BE <br />NON-COMBUSTIBLE MATERIAL AND SLOPE TO DRAIN TOWARDS THE <br />GARAGE DOOR OPENING. (CRC R309.1) <br />5.APPLIANCES AND RECEPTACLES INSTALLED IN GARAGE <br />GENERATING A GLOW, SPARK OR FLAME SHALL BE LOCATED 18 <br />ABOVE FLOOR UNLESS IT IS LISTED AS FLAMMABLE VAPOR IGNITION <br />RESISTANT. PROVIDE PROTECTIVE POST OR OTHER IMPACT <br />BARRIER FROM VEHICLES (CMC 308.0). <br />STAIRWAYS & RAMPS <br />1.EXTERIOR STAIR STRINGERS MUST BE NATURALLY RESISTANT TO <br />DECAY OR PRESSURE TREATED. (CRC R317.1) <br />2.RISE SHALL BE MAXIMUM 7.75; RUN SHALL BE 10 MINIMUM; <br />HEADROOM 6-8 MINIMUM; WIDTH 36 MINIMUM, 31.5 BETWEEN A <br />HANDRAIL ON ONE SIDE AND 27 WITH HANDRAILS ON TWO SIDES. <br />VARIATION BETWEEN RISER HEIGHTS 3/8 MAXIMUM. A NOSING NOT <br />LESS THAN .75 INCHES BUT NOT MORE THAN 1.25 INCHES SHALL BE <br />PROVIDED ON STAIRWAYS WITH SOLID RISERS WHERE THE TREAD <br />DEPTH IS LESS THAN 11 INCHES. THE LEADING EDGE OF TREADS <br />SHALL PROJECT NOT MORE THAN 1.25 INCHES BEYOND THE TREAD <br />BELOW. OPEN RISERS ARE PERMITTED, PROVIDED THE OPENING <br />BETWEEN THE TREADS DOES NOT PERMIT THE PASSAGE OF A 4 <br />SPHERE. (OPENINGS ARE NOT LIMITED WHEN THE STAIR HAS A RISE <br />OF 30 OR LESS). (CRC R311.7) <br />3.STAIRWAYS WITH 4 OR MORE RISERS SHALL HAVE A HANDRAIL ON <br />ONE SIDE 34 TO 38 ABOVE THE TREAD NOSING. CIRCULAR <br />HANDRAILS SHALL HAVE AN OUTSIDE DIAMETER OF 1.25-2; IF NOT <br />CIRCULAR, IT SHALL HAVE A PERIMETER DIMENSION OF 4-6.25 WITH <br />A MAXIMUM CROSS SECTIONAL DIMENSION OF 2.25. SEE R311.7.8.3 <br />ITEM# 2 FOR TYPE II HANDRAILS WITH A PARAMETER OVER 6.25. A <br />MINIMUM CLEARANCE OF 1.5 SHALL BE MAINTAINED FROM THE WALL <br />OR OTHER SURFACE. HANDRAILS SHALL BE RETURNED, TERMINATE <br />IN NEWEL POSTS, OR SAFETY TERMINALS. (CRC R311.7.8.2) <br />4.GUARDS SHALL BE 42 MINIMUM HEIGHT (UNLESS ACTING AS A <br />HANDRAIL/GUARD FOR A STAIRWAY; THE GUARD HEIGHT MAY BE <br />34-38 IN HEIGHT), WITH OPENINGS LESS THAN 4 INCHES CLEAR <br />(GUARDS ON THE OPEN SIDES OF STAIRS MAY HAVE 4 3/8 <br />OPENINGS). (CRC R312) <br />5.PROVIDE LANDINGS AT THE TOP/BOTTOM OF THE STAIRWAY THE <br />WIDTH OF THE STAIRWAY. THE DEPTH OF THE LANDING SHALL BE 36 <br />MINIMUM. (SEE CRC R311.7.6 FOR EXCEPTIONS). <br />6.USABLE SPACES UNDERNEATH ENCLOSED/UNENCLOSED <br />STAIRWAYS SHALL BE PROTECTED BY A MINIMUM OF ½ GYPSUM <br />BOARD. (CRC R302.7) <br />7.RAMPS SERVING THE EGRESS DOOR SHALL HAVE A SLOPE OF NOT <br />MORE THAN 1 UNIT VERTICAL IN 12 UNITS HORIZONTAL (8.3-PERCENT <br />SLOPE). ALL OTHER RAMPS SHALL HAVE A MAXIMUM SLOPE OF 1 <br />UNIT VERTICAL IN 8 UNITS HORIZONTAL (12.5-PERCENT SLOPE). <br />EXCEPTION: WHERE IT IS TECHNICALLY INFEASIBLE TO COMPLY <br />BECAUSE OF SITE CONSTRAINTS, RAMPS SHALL HAVE A SLOPE OF <br />NOT MORE THAN 1 UNIT VERTICAL IN 8 UNITS HORIZONTAL <br />(12.5-PERCENT SLOPE) (CRC R311.8.1). PROVIDE 3X3 LANDINGS AT <br />THE TOP AND BOTTOM OF RAMPS, WHERE DOORS OPEN ONTO <br />RAMPS, AND WHERE RAMPS CHANGE DIRECTIONS. (CRC R311.8) <br />DECKS <br />1.GUARDS ARE REQUIRED IF DECK OR FLOOR IS OVER 30 ABOVE <br />GRADE, MINIMUM 42 HIGH, WITH OPENINGS LESS THAN 4 (CRC <br />R312). GUARDRAILS SHALL BE DESIGNED AND DETAILED FOR <br />LATERAL FORCES ACCORDING TO CRC TABLE 301.5. <br />2.PROVIDE DECK LATERAL LOAD CONNECTIONS AT EACH END OF THE <br />DECK AND AT DECK INTERSECTIONS PER CRC R507.2.4. <br />CONNECTORS SHALL HAVE A MINIMUM ALLOWABLE STRESS DESIGN <br />CAPACITY OF 1,500LBS AND INSTALL WITH 24 OF THE END OF THE <br />DECK. 750LB RATED DEVICES ARE ALLOWED (DTT1Z AS EXAMPLE) IF <br />LOCATED EVENLY AT 4 POINTS ALONG THE DECK. <br />3.POSTS/COLUMNS SHALL BE RETRAINED AT THE BOTTOM END TO <br />PREVENT LATERAL DISPLACEMENT; CLEARLY SHOW APPROVED <br />POST BASES, STRAPS, ETC TO ACHIEVE THIS PER CRC R407.3 <br />4.HARDWARE AND FASTENERS TO BE HOT-DIPPED GALVANIZED, <br />STAINLESS STEEL, SILICON BRONZED OR COPPER. (CRC R317.3) <br />ELECTRICAL <br />1.NO ELECTRICAL PANELS SHALL BE IN CLOSETS OF BATHROOMS. <br />MAINTAIN A CLEARANCE OF 36 INCHES IN FRONT OF PANELS, 30 <br />WIDE OR WIDTH OF EQUIPMENT AND 6-6 HIGH FOR HEADROOM (CEC <br />110.26). <br />2.A CONCRETE-ENCASED ELECTRODE (UFER) CONSISTING OF 20 OF <br />REBAR OR #4 COPPER WIRE PLACED IN THE BOTTOM OF A FOOTING <br />IS REQUIRED FOR ALL NEW CONSTRUCTION. (CEC 250.52(A) BOND <br />ALL METAL GAS AND WATER PIPES TO GROUND. ALL GROUND <br />CLAMPS SHALL BE ACCESSIBLE AND OF AN APPROVED TYPE. (CEC <br />250.104) <br />3.ALL 15/20 AMPERE RECEPTACLES INSTALLED PER CEC 210.52 SHALL <br />BE LISTED TAMPER-RESISTANT RECEPTACLES. (CEC 406.12) <br />4.ALL BRANCH CIRCUITS SUPPLYING 15/20 AMPERE OUTLETS IN <br />FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, <br />LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, <br />CLOSETS, HALLWAYS, KITCHENS, LAUNDRY ROOM OR SIMILAR <br />ROOMS/AREAS SHALL BE PROTECTED BY A LISTED COMBINATION <br />TYPE ARC-FAULT CIRCUIT INTERRUPTER. (CEC 210.12) <br />5.PROVIDE A MINIMUM OF ONE 20A CIRCUIT TO BE USED FOR THE <br />LAUNDRY RECEPTACLE. (CEC 210.11(C)(2)) PROVIDE A MINIMUM OF <br />ONE 20A CIRCUIT FOR BATHROOM RECEPTACLE OUTLETS. (CEC <br />210.11(C)(3) <br />6.PROVIDE AT LEAST 1 OUTLET IN BASEMENTS, GARAGES, LAUNDRY <br />ROOMS, DECKS, BALCONIES, PORCHES AND WITHIN 3 OF THE <br />OUTSIDE OF EACH BATHROOM BASIN. (CEC 210.52 (D), (F) & (G)) <br />7.FURNACES INSTALLED IN ATTICS AND CRAWL SPACES SHALL HAVE <br />AN ACCESS PLATFORM (CATWALK IN ATTICS LIGHT SWITCH AND <br />RECEPTACLE IN THE SPACE. PROVIDE A SERVICE RECEPTACLE FOR <br />THE FURNACE. (CEC 210.63) <br />8.ALL DWELLINGS MUST HAVE ONE EXTERIOR OUTLET AT THE FRONT <br />AND THE BACK OF THE DWELLING. (CEC 210.52(E)) <br />9.GARAGE RECEPTACLES SHALL NOT SERVE OUTLETS OUTSIDE THE <br />GARAGE. A MINIMUM OF 1 RECEPTACLE SHALL BE PROVIDED FOR <br />EACH CAR SPACE. (210.52(G)(1)) <br />10.A 15/20 AMP RECEPTACLE SHALL BE INSTALLED WITHIN 50FT OF <br />ELECTRICAL SERVICE EQUIPMENT. (CEC 210.64) <br />11.KITCHENS, DINING ROOMS, PANTRIES, BREAKFAST NOOKS, AND <br />SIMILAR AREAS MUST HAVE A MINIMUM OF TWO 20A CIRCUITS. <br />KITCHEN, PANTRY, BREAKFAST NOOKS, DINING ROOMS, AND SIMILAR <br />AREAS COUNTER OUTLETS MUST BE INSTALLED IN EVERY COUNTER <br />SPACE 12 INCHES OR WIDER, NOT GREATER THAN 4 O.C., WITHIN <br />24 INCHES OF THE END OF ANY COUNTER SPACE AND NOT HIGHER <br />THAN 20 ABOVE COUNTER. (CEC 210.52 (C)) ISLAND COUNTER <br />SPACES SHALL HAVE AT LEAST 1 RECEPTACLE OUTLET UNLESS A <br />RANGE TOP OR SINK IS INSTALLED THAN 2 RECEPTACLES MAY BE <br />REQUIRED. 1 RECEPTACLE IS REQUIRED FOR PENINSULAR COUNTER <br />SPACES. RECEPTACLES SHALL BE LOCATED BEHIND KITCHEN SINKS <br />IF THE COUNTER AREA DEPTH BEHIND THE SINK IS MORE THAN 12 <br />FOR STRAIGHT COUNTERS AND 18 FOR CORNER INSTALLATIONS. <br />(CEC FIGURE 210.52(C)(1)) <br />12.RECEPTACLES SHALL BE INSTALLED AT 12 O.C. MAXIMUM IN WALLS <br />STARTING AT 6 MAXIMUM FROM THE WALL END. WALLS LONGER <br />THAN TWO FEET SHALL HAVE A RECEPTACLE. HALLWAY WALLS <br />LONGER THAN 10 FT SHALL HAVE A RECEPTACLE IN HALLWAYS. (CEC <br />210.52(A)) <br />13.RECEPTACLES SHALL NOT BE INSTALLED WITHIN OR DIRECTLY OVER <br />A BATHTUB OR SHOWER STALL. (CEC 406.9(C) LIGHT PENDANTS, <br />CEILING FANS, LIGHTING TRACKS, ETC SHALL NOT BE LOCATED <br />WITHIN 3FT HORIZONTALLY AND 8FT VERTICALLY ABOVE A SHOWER <br />AND/OR BATHTUB THRESHOLD. (CEC 410.10(D)) <br />14.ALL LIGHTING/FAN FIXTURES LOCATED IN WET OR DAMP LOCATIONS <br />SHALL BE RATED FOR THE APPLICATION. (CEC 410.10) <br />15.GFCI OUTLETS ARE REQUIRED: FOR ALL KITCHEN RECEPTACLES <br />THAT ARE DESIGNED TO SERVE COUNTERTOP SURFACES, <br />DISHWASHERS, BATHROOMS, IN UNDER-FLOOR SPACES OR BELOW <br />GRADE LEVEL, IN EXTERIOR OUTLETS, WITHIN 6 OF A <br />LAUNDRY/UTILITY/WET BAR INKS, LAUNDRY AREAS, AND IN ALL <br />DEVICE OR GARAGE DOOR OPENER (CEC 210.8). <br />16.CARBON-MONOXIDE ALARMS SHALL BE INSTALLED IN DWELLING <br />UNITS WITH FUEL-BURNING APPLIANCES OR WITH ATTACHED <br />GARAGES (CRC R315): <br />·OUTSIDE OF EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE <br />VICINITY OF BEDROOMS <br />·ON EVERY LEVEL OF A DWELLING UNIT INCLUDING BASEMENTS <br />·ALTERATIONS, REPAIRS, OR ADDITIONS EXCEEDING 1,000 DOLLARS <br />(MAY BE BATTERY OPERATED) <br />17.SMOKE ALARMS SHALL BE INSTALLED (CRC (R314): <br />·IN EACH ROOM USED FOR SLEEPING PURPOSES. <br />·OUTSIDE OF EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE <br />VICINITY OF BEDROOMS. <br />·IN EACH STORY, INCLUDING BASEMENTS. <br />·SHALL NOT BE INSTALLED WITHIN 20FT HORIZONTALLY OF COOKING <br />APPLIANCES AND NO CLOSER THAN 3FT TO MECHANICAL <br />REGISTERS, CEILING FANS AND BATHROOM DOORS WITH A BATHTUB <br />OR SHOWER UNLESS THIS WOULD PREVENT PLACEMENT OF A <br />SMOKE DETECTOR (314.3(4)). <br />·ALTERATIONS, REPAIRS, OR ADDITIONS EXCEEDING 1,000 DOLLARS. <br />(MAY BE BATTERY OPERATED) <br />18.ALL SMOKE AND CARBON-MONOXIDE ALARMS SHALL BE HARDWIRED <br />WITH A BATTERY BACKUP (SMOKE ALARMS SHALL HAVE A 10-YEAR <br />SEALED BATTERY). (CRC R314.4 & R315.1.2) <br />19.ALL 15/20 AMPERE RECEPTACLES IN WET LOCATIONS SHALL HAVE <br />IN-USE (BUBBLE) COVERS INSTALLED. ALL RECEPTACLES IN WET <br />LOCATIONS SHALL ALSO BE LISTED WEATHER-RESISTANT TYPE. <br />(CEC 406.9(B)(1) <br />PLUMBING <br />1.UNDERFLOOR CLEANOUTS SHALL NOT BE MORE THAN 5 FEET FROM <br />AN UNDERFLOOR ACCESS, ACCESS DOOR OR TRAP DOOR. (CPC <br />707.9) <br />2.ABS PIPING SHALL NOT BE EXPOSED TO DIRECT SUNLIGHT UNLESS <br />PROTECTED BY WATER BASED SYNTHETIC LATEX PAINTS. (CPC <br />312.13) <br />3.PVC PIPING SHALL NOT BE EXPOSED TO DIRECT SUNLIGHT UNLESS <br />PROTECTED BY WATER BASED SYNTHETIC LATEX PAINT, .04 THICK <br />WRAP OR OTHERWISE PROTECTED FROM UV DEGRADATION. (CPC <br />312.14) <br />4.THE ADJACENT SPACE NEXT TO SHOWERS WITHOUT THRESHOLDS <br />SHALL BE CONSIDERED A WET LOCATION WHEN USING THE CRC, <br />CBC, AND THE CEC. (CPC 408.5) <br />5.SHOWER COMPARTMENTS, REGARDLESS OF SHAPE, SHALL HAVE A <br />MINIMUM FINISHED INTERIOR OF 1024 SQUARE INCHES (32 BY 32) <br />AND SHALL ALSO BE CAPABLE OF ENCOMPASSING A 30 CIRCLE. THE <br />REQUIRED AREA AND DIMENSIONS SHALL BE MEASURED AT A <br />HEIGHT EQUAL TO THE TOP OF THE THRESHOLD AND SHALL BE <br />MAINTAINED TO A POINT OF NOT LESS THAN 70 ABOVE THE SHOWER <br />DRAIN OUTLET. (CPC 408.6) PROVIDE CURTAIN ROD OR DOOR A <br />MINIMUM OF 22 IN WIDTH (CPC 408.5). SHOWERS AND TUBS WITH <br />SHOWERS REQUIRE A NON-ABSORBENT SURFACE UP TO 6 ABOVE <br />THE FLOOR. (CRC R307.2) <br />6.WATER HEATERS: PROVIDE PRESSURE RELIEF VALVE WITH DRAIN <br />TO OUTSIDE FOR WATER HEATER. (CPC 504.6) PROVIDE SEISMIC <br />STRAPPING IN THE UPPER & LOWER THIRD OF THE WATER HEATER A <br />MINIMUM OF 4 ABOVE CONTROLS. (CPC 507.2) THE WATER HEATER <br />SHALL BE OF AN INSTANTANEOUS TYPE OR THE FOLLOWING SHALL <br />BE PROVIDED (NEW CONSTRUCTION ONLY ) (CEC 150(N)): <br />·A 120V RECEPTACLES PROVIDED WITHIN 3FT <br />·A CATEGORY III OR IV VENT, OR A STRAIGHT (WITHOUT BENDS) TYPE <br />B VENT <br />·CONDENSATE DRAIN THAT IS NO MORE THAN 2 INCHES HIGHER THAN <br />THE BASE OF THE WATER HEATER <br />·GAS SUPPLY LINE WITH A MINIMUM 200,000 BTU/HR DEDICATED <br />CAPACITY FOR THE WATER HEATER <br />·DOMESTIC HOT WATER LINES SHALL BE INSULATED. INSULATION <br />SHALL BE THE THICKNESS OF THE PIPE DIAMETER UP TO 2 IN SIZE <br />AND MINIMUM 2 THICKNESS FOR PIPES LARGER THAN 2 IN <br />DIAMETER. (CPC 609.11) <br />·A 3-INCH GRAVITY DRAIN SHALL BE PROVIDED AT THE LOW POINT OF <br />UNDERFLOOR SPACES, INSTALLED SO AS TO PROVIDE 1/4-INCH PER <br />FOOT GRADE AND TERMINATE AT AN EXTERIOR POINT OF THE <br />BUILDING PROTECTED FROM BLOCKAGE. THE OPENING SHALL BE <br />SCREENED WITH A CORROSION-RESISTANT WIRE MESH WITH MESH <br />OPENINGS OF 1/4-INCH IN DIMENSION. LENGTHS OF THE GRAVITY <br />DRAINS OVER 10 FEET IN LENGTH SHALL BE FIRST APPROVED BY <br />THE BUILDING OFFICIAL. (L-V 8.9) <br />·WATER HEATERS LOCATED IN ATTICS, CEILING ASSEMBLIES AND <br />RAISED FLOOR ASSEMBLIES SHALL SHOW A WATER-TIGHT <br />CORROSION RESISTANT MINIMUM 1 ½ DEEP PAN UNDER THE WATER <br />HEATER WITH A MINIMUM ¾ INCH DRAIN TO THE EXTERIOR OF THE <br />BUILDING. (CPC 507.5) <br />·WATER CLOSET SHALL BE LOCATED IN A SPACE NOT LESS THAN 30 <br />IN WIDTH (15 ON EACH SIDE) AND 24 MINIMUM CLEARANCE IN <br />FRONT. (CPC 402.5) <br />11.THE MAXIMUM HOT WATER TEMPERATURE DISCHARGING FROM A <br />BATHTUB OR WHIRLPOOL BATHTUB FILLER SHALL NOT EXCEED 120 <br />DEGREES F. (CPC 418) <br />12.PROVIDE ANTI-SIPHON VALVES ON ALL HOSE BIBS. (CPC 603.5.7) <br />13.FLOOR DRAINS SHALL BE PROVIDED WITH A TRAP PRIMER. (CPC <br />1007) <br />14.MAXIMUM WATER FLOW RATES. (CGBSC 4.303.1): <br />·WATER CLOSETS: 1.28GPF <br />·URINALS: .125GPF <br />·KITCHEN FAUCETS: 1.8GPM @ 60PSI <br />·LAVATORY FAUCETS: 1.2PGM @ 60PSI <br />·SHOWERHEADS: 2GPM <br />MECHANICAL <br />1.WOOD BURNING APPLIANCES SHALL BE ONE OF THE FOLLOWING: <br />·A PELLET-FUELED WOOD BURNING HEATER. <br />·A U.S. EPA PHASE II CERTIFIED WOOD BURNING HEATER. <br />·AN APPLIANCE OR FIREPLACE DETERMINED TO MEET THE U.S. EPA <br />PARTICULATE MATTER EMISSION STANDARD OF LESS THAN 7.5 <br />GRAMS PER HOUR FOR A NON-CATALYTIC WOOD FIRED APPLIANCE <br />OR 4.1 GRAMS PER HOUR FOR A CATALYTIC WOOD FIRED APPLIANCE <br />AND IS APPROVED IN WRITING BY THE APCO. <br />1.ALL NEWLY INSTALLED GAS FIREPLACES SHALL BE DIRECT VENT <br />AND SEALED-COMBUSTION TYPE. (CMC 912.2) <br />2.ANY INSTALLED WOOD STOVE OR PELLET STOVE SHALL HAVE A <br />PERMANENT NSPS LABEL CERTIFYING EMISSION LIMITS. <br />3.TOP CHIMNEY MUST EXTEND A MINIMUM OF 2 FT. ABOVE ANY PART <br />OF THE BUILDING WITHIN 10 FT. (CMC 802.5.4) <br />4.FIREPLACES SHALL HAVE CLOSABLE METAL OR GLASS DOORS, HAVE <br />COMBUSTION AIR INTAKE DRAWN FROM THE OUTSIDE AND HAVE A <br />READILY ACCESSIBLE FLUE DAMPENER CONTROL. CONTINUOUS <br />BURNING PILOT LIGHTS ARE PROHIBITED. (CEC 150.0(E)) <br />5.PROVIDE COMBUSTION AIR FOR ALL GAS FIRED APPLIANCES PER <br />CMC CHAPTER 7. <br />6.GAS VENTS PASSING THROUGH AN INSULATED ASSEMBLY SHALL <br />HAVE A METAL INSULATION SHIELD A MINIMUM 2 ABOVE INSULATION. <br />(509.6.2.7) <br />7.GAS WATER HEATER AND FURNACE ARE NOT ALLOWED IN AREAS <br />OPENING INTO BATHROOMS, CLOSETS OR BEDROOMS UNLESS <br />INSTALLED IN A CLOSET EQUIPPED WITH A LISTED GASKETED DOOR <br />ASSEMBLY AND A LISTED SELF-CLOSING DEVICE WITH ALL <br />COMBUSTION AIR OBTAINED FROM THE OUTDOORS. (CPC 504) <br />8.ROOF TOP EQUIPMENT ON ROOFS WITH OVER 4/12 SLOPE SHALL <br />HAVE A LEVEL 30X30 WORKING PLATFORM. (CMC 304.2) <br />9.EXHAUST OPENINGS TERMINATING TO THE OUTDOORS SHALL BE <br />COVERED WITH A CORROSION RESISTANT SCREEN ¼-1/2 IN <br />OPENING SIZE (NOT REQUIRED FOR CLOTHES DRYERS). (CMC 502.1) <br />10. VENT DRYER TO OUTSIDE OF BUILDING (NOT TO UNDER-FLOOR <br />AREA). VENT LENGTH SHALL BE 14 MAXIMUM. SHALL TERMINATE A <br />MINIMUM OF 3 FROM THE PROPERTY LINE AND ANY OPENING INTO <br />THE BUILDING. (CMC 504.4.2) <br />11. ENVIRONMENTAL AIR DUCTS SHALL NOT TERMINATE LESS THAN 3 <br />TO A PROPERTY LINE, 10 TO A FORCED AIR INLET, 3 TO OPENINGS <br />INTO THE BUILDING AND SHALL NOT DISCHARGE ON TO A PUBLIC <br />(CMC 502.2.1) <br />12. PROVIDE MINIMUM 100 SQUARE INCHES MAKE-UP AIR FOR CLOTHES <br />DRYERS INSTALLED IN CLOSETS. (CMC 504.4.1(1)) <br />13. HEATING SYSTEM IS REQUIRED TO MAINTAIN 68 DEGREES AT 3 FT. <br />ABOVE FLOOR LEVEL AND 2FT FROM EXTERIOR WALLS IN ALL <br />HABITABLE ROOMS. (CRC R303.9) <br />ENERGY CODE <br />1.ALL DUCTS IN CONDITIONED SPACES MUST INCLUDE R-4.2 <br />INSULATION. (CALIFORNIA ENERGY CODE 150.1(C)9) <br />2.INSULATE THE FIRST 5 OF HOT/COLD WATER LINES, ALL LINES ¾ <br />INCH IN DIAMETER OR LARGER, ALL RECIRCULATION PIPING, PIPING <br />TO STORAGE TANKS AND ALL HOT WATER PIPES TO KITCHEN <br />FIXTURES FROM THE WATER HEATER. (CALIFORNIA ENERGY CODE <br />150(J)(2)) <br />3.ISOLATION WATER VALVES REQUIRED FOR INSTANTANEOUS WATER <br />HEATERS 6.8KBTU/HR AND ABOVE VALVES SHALL BE INSTALLED ON <br />BOTH COLD AND HOT WATER LINES. EACH VALVE WILL NEED A HOSE <br />BIB OR OTHER FITTING ALLOWING FOR FLUSHING THE WATER <br />HEATER WHEN THE VALVES ARE CLOSED. (CEC 110.3(C)7) <br />4.ALL LUMINAIRES MUST BE HIGH EFFICACY (CALIFORNIA ENERGY <br />CODE 150.0(K)1A) <br />5.THE MAXIMUM NUMBER OF BLANK ELECTRICAL BOXES INSTALLED <br />MORE THAN 5 FEET ABOVE THE FLOOR IS LIMITED TO THE NUMBER <br />OF BEDROOMS. THE BLANK BOXES SHALL BE SERVED BY A DIMMER, <br />VACANCY SENSOR OR FAN SPEED CONTROL. (CALIFORNIA ENERGY <br />CODE 150.0(K)1B) <br />6.LUMINARIES RECESSED IN INSULATED CEILINGS MUST MEET THESE <br />REQUIREMENTS (CALIFORNIA ENERGY CODE 150.0(K)1C): <br />·THEY MUST BE RATED FOR DIRECT INSULATION CONTACT (IC). <br />·THEY MUST BE CERTIFIED AS AIRTIGHT (AT) CONSTRUCTION. <br />·THEY MUST HAVE A SEALED GASKET OR CAULKING BETWEEN THE <br />HOUSING AND CEILING TO PREVENT FLOW OF HEATED OR COOLED <br />AIR OUT OF LIVING AREAS AND INTO THE CEILING CAVITY. <br />·THEY MAY NOT CONTAIN A SCREW BASE SOCKETS <br />·THEY SHALL CONTAIN A JA8 COMPLIANT LIGHT SOURCE <br />·IN BATHROOMS, GARAGES, LAUNDRY ROOMS, AND UTILITY ROOMS, <br />AT LEAST ONE LUMINAIRE IN EACH OF THESE SPACES SHALL BE <br />CONTROLLED BY A VACANCY SENSOR. (CALIFORNIA ENERGY CODE <br />150.0(K)2J) <br />·JOINT APPENDIX A (JA8) CERTIFIED LAMPS SHALL BE CONSIDERED <br />HIGH EFFICACY. JA8 COMPLIANT LIGHT SOURCES SHALL BE <br />CONTROLLED BY A VACANCY SENSOR OR DIMMER. (EXCEPTION: <br /><70SF CLOSETS AND HALLWAY) (CALIFORNIA ENERGY CODE <br />150.0(K)2K) <br />·UNDER-CABINET LIGHTING SHALL BE SWITCHED SEPARATELY FROM <br />OTHER LIGHTING SYSTEMS. (CALIFORNIA ENERGY CODE 150.0(K)2L) <br />·ALL EXTERIOR LIGHTING SHALL BE HIGH EFFICACY, BE CONTROLLED <br />BY A MANUAL ON/OFF SWITCH AND HAVE ONE OF THE FOLLOWING <br />CONTROLS (THE MANUAL SWITCH SHALL NOT OVERRIDE THE <br />AUTOMATIC CONTROL DEVICE): (CALIFORNIA ENERGY CODE <br />150.0(K)3A) <br />·PHOTO-CONTROL AND MOTION SENSOR <br />·PHOTO-CONTROL AND AUTOMATIC TIME SWITCH CONTROL <br />·ASTRONOMICAL TIME CLOCK CONTROL TURNING LIGHTS OFF <br />DURING THE DAY <br />·ALL HIGH EFFICACY LIGHT FIXTURES SHALL BE CERTIFIED AS <br />HIGH-EFFICACY LIGHT FIXTURES BY THE CALIFORNIA ENERGY <br />COMMISSION. <br />·CONTRACTOR SHALL PROVIDE THE HOMEOWNER WITH A LUMINAIRE <br />SCHEDULE GIVING THE LAMPS USED IN THE LUMINAIRES INSTALLED. <br />(CALIFORNIA ENERGY CODE 10-103(B)) <br />·PROJECT SHALL MEET THE MINIMUM VENTILATION AND ACCEPTABLE <br />INDOOR AIR QUALITY REQUIREMENTS PER ASHRAE STANDARD 62.2. <br />WINDOW OPERATION IS NOT A PERMISSIBLE METHOD OF PROVIDING <br />THE WHOLE BUILDING VENTILATION AIRFLOW REQUIRED. THIS IS <br />SUBJECT TO HERS TESTING. THE FOLLOWING LABEL MUST BE <br />ATTACHED TO THE FAN SWITCH: TO MAINTAIN MINIMUM LEVELS OF <br />OUTSIDE AIR VENTILATION REQUIRED FOR GOOD HEALTH, THE FAN <br />CONTROL SHOULD BE ON AT ALL TIMES WHEN THE BUILDING IS <br />OCCUPIED, UNLESS THERE IS SEVERE OUTDOOR AIR <br />CONTAMINATION. (CALIFORNIA ENERGY CODE 150.0(O)) <br />WILDLAND URBAN INTERFACE (WUI) <br />BUILDINGS CONSTRUCTED AFTER JANUARY 1, 2008 <br />1.EXTERIOR WALL COVERINGS SHALL BE NONCOMBUSTIBLE, IGNITION <br />RESISTANT, HEAVY TIMBER, LOG WALL OR FIRE RESISTIVE <br />CONSTRUCTION. (CRC R337.7) <br />2.EXTERIOR WALL COVERINGS SHALL EXTEND FROM THE FOUNDATION <br />TO THE ROOF AND TERMINATE AT 2 INCH NOMINAL SOLID BLOCKING <br />BETWEEN RAFTERS AND OVERHANGS. (CRC R337.7.3.1) <br />3.OPEN/ENCLOSED ROOF EAVES AND SOFFITS, EXTERIOR PORCH <br />CEILINGS, FLOOR PROJECTIONS, UNDER-FLOOR AREAS AND <br />UNDERSIDES OF APPENDAGES TO COMPLY WITH IGNITION <br />RESISTANT CONSTRUCTION REQUIREMENTS. (CRC R337.5-9) (SHOW <br />COMPLIANCE ON THE PLANS). <br />4.SPACES CREATED BETWEEN ROOF COVERINGS AND ROOF DECKING <br />SHALL BE FIRE STOPPED BY APPROVED MATERIALS OR HAVE ONE <br />LAYER OF MINIMUM 72LB MINERAL SURFACED NONPERFORATED CAP <br />SHEET COMPLYING WITH ASTM D 3909. (CRC R337.5.2) <br />5.VALLEY FLASHING SHALL BE NOT LESS THAN 26AWG AND INSTALLED <br />OVER NOT LESS THAN ONE LAYER OF MINIMUM 72LB MINERAL <br />SURFACED NON-PERFORATED CAP SHEET COMPLYING WITH ASTM D <br />3909 AND AT LEAST 36 INCHES WIDE RUNNING THE FULL LENGTH. <br />(CRC R337.5.3) <br />6.ATTIC GABLE AND EAVES ABOVE 12FT AND UNDER-FLOOR <br />VENTILATION SHALL BE PROVIDED WITH FULLY COVERED METAL <br />WIRE MESH, VENTS, OR OTHER MATERIALS THAT HAVE A MINIMUM <br />1/16 INCH AND MAXIMUM 1/8 INCH OPENINGS, NON-COMBUSTIBLE <br />AND CORROSION RESISTANT. ALL OTHER EAVE VENTS SHALL BE <br />LISTED/APPROVED TO RESIST THE INTRUSION OF FLAME AND <br />BURNING (CRC R337.6) <br />7.EXTERIOR GLAZING SHALL HAVE A MINIMUM OF ONE-TEMPERED <br />PANE, GLASS BLOCK, HAVE A FIRE RESISTIVE RATING OF 20 MINUTES <br />OR BE TESTED TO MEET PERFORMANCE REQUIREMENTS OF SFM <br />STANDARD 12-7A-2. (CRC R337.8.2) <br />8.EXTERIOR DOORS INCLUDING GARAGE DOORS SHALL BE <br />NONCOMBUSTIBLE, IGNITION RESISTANT MATERIAL, MINIMUM 1 3/8 <br />INCH SOLID CORE, MINIMUM 20 MINUTE FIRE RESISTIVE RATING OR <br />SHALL BE TESTED TO MEET THE PERFORMANCE REQUIREMENTS OF <br />SFM STANDARD 12-7A-1. (CRC R337.8.3) <br />9.THE WALKING SURFACE MATERIAL OF DECKS, PORCHES, BALCONIES <br />AND STAIRS WITHIN 10FT OF GRADE LEVEL SHALL BE IGNITION <br />RESISTANT MATERIAL, EXTERIOR FIRE RETARDANT TREATED WOOD <br />OR NONCOMBUSTIBLE MATERIAL. (CRC R337.9) <br />GREEN BUILDING <br />1.PROJECTS WHICH DISTURB LESS THAN ONE ACRE OF SOIL AND ARE <br />NOT PART OF A LARGER COMMON PLAN OF DEVELOPMENT WHICH IN <br />TOTAL DISTURBS ONE ACRE OR MORE, SHALL MANAGE STORM <br />WATER DRAINAGE DURING CONSTRUCTION, ONE OR MORE OF THE <br />FOLLOWING MEASURES SHALL BE IMPLEMENTED TO PREVENT <br />FLOODING OF ADJACENT PROPERTY, PREVENT EROSION AND <br />RETAIN SOIL RUNOFF ON THE SITE (CGBSC 4.106.2): <br />·RETENTION BASINS OF SUFFICIENT SIZE SHALL BE UTILIZED TO <br />RETAIN STORM WATER ON SITE <br />·WHERE STORM WATER IS CONVEYED TO A PUBLIC DRAINAGE <br />SYSTEM, COLLECTION POINT, GUTTER, OR SIMILAR DISPOSAL <br />METHOD, WATER SHALL BE FILTERED BY USE OF A BARRIER SYSTEM, <br />WATTLE OR OTHER METHOD APPROVED BY THE ENFORCING <br />AGENCY. <br />2.ALL NEW RESIDENTIAL CONSTRUCTION WITH ATTACHED PRIVATE <br />GARAGES SHALL HAVE THE FOLLOWING FOR ELECTRIC VEHICLE (EV) <br />CHARGING STATIONS (CGBSC 4.106.4): <br />·INSTALL A MINIMUM 1-INCH CONDUIT CAPABLE OF SUPPLYING A <br />208/240V BRANCH CIRCUIT TO A SUITABLE BOX LOCATION FOR EV <br />CHARGING. THE OTHER END SHALL TERMINATE TO THE MAIN <br />SERVICE AND/OR SUBPANEL. <br />·THE MAIN PANEL AND/OR SUBPANEL SHALL BE OF SUFFICIENT SIZE <br />TO INSTALL A 40-AMPERE DEDICATED BRANCH CIRCUIT. THE <br />DEDICATED OVERCURRENT PROTECTION SPACE SHALL BE LABELED <br />EV CAPABLE. <br />3.MULTIPLE SHOWER HEADS SERVING A SINGLE SHOWER SHALL HAVE <br />A COMBINED FLOW RATE OF 2GPM OR THE SHOWER SHALL BE <br />DESIGNED TO ALLOW ONLY ONE SHOWER OUTLET TO BE IN <br />OPERATION AT A TIME. (CGBSC 4.303.1.3.2) <br />4.RESIDENTIAL PROJECTS WITH AN AGGREGATE LANDSCAPE AREA <br />EQUAL TO OR GREATER THAN 500 SQUARE FEET SHALL COMPLY <br />WITH EITHER A LOCAL WATER EFFICIENT LANDSCAPE ORDINANCE <br />OR THE CURRENT CALIFORNIA DEPARTMENT OF WATER <br />RESOURCES MODEL WATER EFFICIENT LANDSCAPE ORDINANCE <br />(MWELO), WHICHEVER IS MORE STRINGENT. AUTOMATIC IRRIGATION <br />SYSTEM CONTROLLERS INSTALLED AT TIME OF FINAL INSPECTION <br />SHALL HAVE WEATHER OR SOIL BASED CONTROLLERS AND/OR <br />WEATHER BASED CONTROLLERS WITH RAIN SENSORS. SOIL <br />MOISTURE BASED CONTROLLERS ARE NOT REQUIRED TO HAVE RAIN <br />SENSOR INPUT. (CGBSC 4.304) <br />5.RECYCLE AND/OR REUSE A MINIMUM OF 65 PERCENT OF <br />NONHAZARDOUS CONSTRUCTION AND DEMOLITION WASTE. (CGBSC <br />4.408.2) <br />6.AT TIME OF FINAL INSPECTION, A BUILDING OPERATION AND <br />MAINTENANCE MANUAL, COMPACT DISC, ETC SHALL BE PROVIDED <br />CONTAINING THE FOLLOWING: (CGBSC 4.410) <br />·DIRECTIONS THAT MANUAL SHALL REMAIN ONSITE FOR THE LIFE OF <br />THE BUILDING <br />·OPERATION AND MAINTENANCE INSTRUCTIONS FOR EQUIPMENT, <br />APPLIANCES, ROOF/YARD DRAIN-AGE, IRRIGATION SYSTEMS, ETC <br />·INFORMATION FROM LOCAL UTILITY, WATER AND WASTE RECOVERY <br />PROVIDERS <br />·PUBLIC TRANSPORTATION AND CARPOOL OPTIONS <br />·MATERIAL REGARDING IMPORTANCE OF KEEPING HUMIDITY LEVELS <br />BETWEEN 30-60 PERCENT <br />·INFORMATION REGARDING ROUTINE MAINTENANCE PROCEDURES <br />·STATE SOLAR ENERGY INCENTIVE PROGRAM INFORMATION <br />·A COPY OF ANY REQUIRED SPECIAL INSPECTION VERIFICATIONS <br />THAT WERE REQUIRED (IF ANY) <br />7.THE PROJECT SHALL MEET MINIMUM POLLUTANT CONTROL <br />REQUIREMENTS FOR ADHESIVES, SEALANTS, CAULKS, PAINTS, <br />CARPET, RESILIENT FLOORING SYSTEMS, ETC. (CGBSC 4.504) <br />8.DUCT OPENINGS RELATED TO HVAC SYSTEMS SHALL BE COVERED <br />WITH TAPE, PLASTIC, SHEET METAL OR OTHER METHODS TO <br />REDUCE THE AMOUNT OF WATER, DUST AND DEBRIS WHICH MAY <br />ENTER THE SYSTEM. (CGBSC 4.504.1) <br />GENERAL NOTES BASED ON THE 2019 CALIFORNIA BUILDING STANDARD <br />CODES. THIS IS NOT AN ALL INCLUSIVE LIST OF CODE REQUIREMENTS <br />SPECIFIC TO THE PROJECT. REFERENCE APPLICABLE SHEETS AND <br />SPECIFIC AREAS OF THE PLANS FOR LOCATIONS OF FIXTURES/ <br />EQUIPMENT, STRUCTURAL COMPONENTS, STRUCTURAL DESIGN <br />CRITERIA, BUILDING FINISHES AND OTHER COMPONENTS SPECIFIC TO <br />THE PROJECT CONSTRUCTION. <br />Construction Waste Management Worksheet (Weight Method) - CW 3 <br />Project Name; <br />Project Location; <br />Project Manager; <br />Waste Hauler; <br />Date: <br />Completed By: <br />Signature: <br />Notes: <br />Page of <br />A B C D <br />Insert Weight totals into proper category below <br />Waste Material Type Recycled Reused Diverted <br />Non-Recycled <br />(Disposed) <br />Asphalt <br />Asphalt Shingles <br />Brick (broken) <br />Cardboard <br />Carpet/Carpet Pad <br />Concrete <br />Gypsum Board (Drywall) <br />Masonry <br />Metals <br />Pallets <br />Plastic <br />Wood (engineered) <br />Wood (solid sawn) <br />Office Waste <br />Other <br />Other <br />Other <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />Step 1 - Insert weight totals into Columns A, B and D where apropiate. <br />Step 2 - And Column A to column B and insert total into Column C for total diverted weight. <br />Step 3 - And each Column down and enter total in the boxes provided. <br />If Column C is larger than column D (on the summary sheet). compliance with 65 percent waste reduction requirement is achieved. <br />If multuiple worksheets are used, transfer column totals from each worksheet to the summary sheet. <br />Totals <br />Construction Waste Management Worksheet (Weight Method) - CW 2 <br />Project Name; <br />Project Location; <br />Project Manager; <br />Waste Hauler; <br />Date: <br />Completed By: <br />Signature: <br />Notes: <br />Page of <br />A B C D <br />Insert Weight totals into proper category below <br />Waste Material Type Recycled Reused Diverted <br />Non-Recycled <br />(Disposed) <br />Asphalt <br />Asphalt Shingles <br />Brick (broken) <br />Cardboard <br />Carpet/Carpet Pad <br />Concrete <br />Gypsum Board (Drywall) <br />Masonry <br />Metals <br />Pallets <br />Plastic <br />Wood (engineered) <br />Wood (solid sawn) <br />Office Waste <br />Other <br />Other <br />Other <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />+= <br />Step 1 - Insert weight totals into Columns A, B and D where apropiate. <br />Step 2 - And Column A to column B and insert total into Column C for total diverted weight. <br />Step 3 - And each Column down and enter total in the boxes provided. <br />If Column C is larger than column D (on the summary sheet). compliance with 65 percent waste reduction requirement is achieved. <br />If multuiple worksheets are used, transfer column totals from each worksheet to the summary sheet. <br />Totals <br />Instruction for Weight or volume Method: <br />Chose which method of construction waste trackind to be used throughout the project. Choose either the weight method or <br />the volume method, but do not use different methods on the same worksheet. <br />To minimize confusion, use the same unit of measure and do not mix pounds and tons, or Cu. Yds. and Cu. Ft. on the same <br />worksheet it is easiest to slay with the same unit of measure for the entire project to avoid the need for conversions. <br />Enter construction waste materials that are to be recycled under Recycled (Column A). <br />Add amounts from column A to amounts from Column B and enter the total under Diverted (Column C). <br />Add amounts in each column (A, B, C, and D) and enter these sums into Total boxes. <br />If the divertes amount )Column C) is greater than the Non-Recycled /Disposed amount (Column D), compliance with the <br />Whwn more than one worksheet is used, transfer the data onto the Weight or Volume Summary Worksheet the completion <br />Enter construction waste materials that are to be reused under Reused (Column B). <br />Enter construction waste materials that will not get recycled or reused under Non-Recycled/Disposed (Column D). <br />construction waste reduction requirement of at least 65 percent per Section 4.408.1 has been achieved. <br />on the project. <br />Examples of weights and volumes of some typical construction waste materials. <br />Material Range of pounds per cubic <br />yard <br />Typical pounds per cubic <br />yard <br />Typical cubic yards per ton <br />Asphalt roofing material <br />Asphalt - paving <br />Cardboard <br />Concrete <br />Gypsum Drywall <br />Metals <br />Wood <br />250 - 460 <br />1300 - 2200 <br />70 - 135 <br />315 - 470 <br />220 - 1940 <br />200 - 540 <br />1300 - 2200 <br />360 <br />1750 <br />85 <br />1750 <br />400 <br />540 <br />499 <br />5.5 <br />1.1 <br />23.5 <br />1.1 <br />5 <br />3.7 <br />5 <br />* Source: Sacramento Regional Solid Waste Authority <br />Standard conversions: 1 cubic yard equals 27 cubic feet <br />1 ton equals 2000 pounds <br />G2.1 <br />GE <br />N <br />E <br />R <br />A <br />L <br /> <br />N <br />O <br />T <br />E <br />S <br />PA <br />R <br />T <br /> <br />2 <br />DE <br />S <br />I <br />G <br />N <br />E <br />R <br />: <br />TH <br />E <br />S <br />E <br /> <br />D <br />R <br />A <br />W <br />I <br />N <br />G <br />S <br />, <br /> <br />D <br />E <br />S <br />I <br />G <br />N <br /> <br />A <br />N <br />D <br /> <br />S <br />P <br />E <br />C <br />I <br />F <br />I <br />C <br />A <br />T <br />I <br />O <br />N <br />S <br /> <br />A <br />R <br />E <br /> <br />T <br />H <br />E <br /> <br />P <br />R <br />O <br />P <br />E <br />R <br />T <br />Y <br /> <br />A <br />N <br />D <br /> <br />C <br />O <br />P <br />Y <br /> <br />R <br />I <br />G <br />H <br />T <br /> <br />O <br />F <br /> <br />Z <br />A <br />H <br />A <br /> <br />A <br />R <br />C <br />H <br /> <br />D <br />E <br />S <br />I <br />G <br />N <br /> <br />A <br />N <br />D <br /> <br />S <br />H <br />A <br />L <br />L <br /> <br />N <br />O <br />T <br /> <br />B <br />E <br /> <br />U <br />S <br />E <br />D <br /> <br />O <br />N <br /> <br />A <br />N <br />Y <br /> <br />O <br />T <br />H <br />E <br />R <br /> <br />W <br />O <br />R <br />K <br /> <br />E <br />X <br />C <br />E <br />P <br />T <br /> <br />B <br />Y <br /> <br />A <br />G <br />R <br />E <br />E <br />M <br />E <br />N <br />T <br /> <br />W <br />I <br />T <br />H <br /> <br /> <br />Z <br />A <br />H <br />A <br /> <br />A <br />R <br />C <br />H <br /> <br />D <br />E <br />S <br />I <br />G <br />N <br />. <br /> <br />W <br />R <br />I <br />T <br />T <br />E <br />N <br /> <br /> <br /> <br /> <br />D <br />I <br />M <br />E <br />N <br />S <br />I <br />O <br />N <br />S <br /> <br />S <br />H <br />A <br />L <br />L <br />TA <br />K <br />E <br /> <br />R <br />E <br />F <br />E <br />R <br />E <br />N <br />C <br />E <br /> <br />O <br />V <br />E <br />R <br /> <br />S <br />C <br />A <br />L <br />E <br />D <br /> <br />D <br />I <br />M <br />E <br />N <br />S <br />I <br />O <br />N <br />S <br /> <br />A <br />N <br />D <br /> <br />S <br />H <br />A <br />L <br />L <br /> <br />B <br />E <br /> <br />V <br />E <br />R <br />I <br />F <br />I <br />E <br />D <br /> <br />O <br />N <br /> <br />T <br />H <br />E <br /> <br />J <br />O <br />B <br /> <br />S <br />I <br />T <br />E <br />, <br /> <br />A <br />N <br />Y <br /> <br />D <br />I <br />S <br />C <br />R <br />E <br />P <br />A <br />N <br />C <br />Y <br /> <br />S <br />H <br />A <br />L <br />L <br /> <br />B <br />E <br /> <br />B <br />R <br />O <br />U <br />G <br />H <br />T <br /> <br />T <br />O <br /> <br />T <br />H <br />E <br /> <br />N <br />O <br />T <br />I <br />C <br />E <br /> <br />O <br />F <br /> <br />Z <br />A <br />H <br />A <br /> <br />A <br />R <br />C <br />H <br /> <br />D <br />E <br />S <br />I <br />G <br />N <br /> <br />P <br />R <br />I <br />O <br />R <br /> <br />T <br />O <br /> <br />T <br />H <br />E <br /> <br />C <br />O <br />M <br />M <br />E <br />N <br />C <br />E <br />M <br />E <br />N <br />T <br /> <br />O <br />F <br /> <br />A <br />N <br />Y <br /> <br />W <br />O <br />R <br />K <br />DRAWN <br />CHECKED <br />R.H <br />DATE <br />06-07-2024 <br />SCALE <br />JOB NO. <br />24-031 <br />SHEET <br />OF SHEETS <br />90 <br />9 <br />- <br />2 <br />4 <br />6 <br />- <br />1 <br />2 <br />0 <br />4 <br />25 <br />5 <br /> <br />N <br /> <br />D <br /> <br />S <br />T <br />. <br /> <br />S <br />U <br />I <br />T <br />E <br /> <br />4 <br />0 <br />1 <br /> <br />L <br />, <br />SA <br />N <br /> <br />B <br />E <br />R <br />N <br />A <br />R <br />D <br />I <br />N <br />O <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />4 <br />0 <br />1 <br />AR <br />C <br />H <br /> <br />D <br />E <br />S <br />I <br />G <br />N <br />ZA <br />H <br />A <br />A <br />R <br />C <br />H <br />D <br />E <br />S <br />I <br />G <br />N <br />1 <br />@ <br />G <br />M <br />A <br />I <br />L <br />. <br />C <br />O <br />M <br />25 <br />2 <br />2 <br /> <br />W <br />e <br />s <br />t <br /> <br />C <br />a <br />m <br />d <br />e <br />n <br /> <br />P <br />l <br />a <br />c <br />e <br />, <br /> <br />U <br />n <br />i <br />t <br /> <br /># <br /> <br />2 <br />Sa <br />n <br />t <br />a <br /> <br />A <br />n <br />a <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />4 <br />GA <br />R <br />A <br />G <br />E <br /> <br />C <br />O <br />N <br />V <br />E <br />R <br />S <br />I <br />O <br />N <br /> <br />T <br />O <br /> <br />A <br />D <br />U <br />AD <br />D <br />R <br />E <br />S <br />S <br />OW <br />N <br />E <br />R <br />PR <br />O <br />J <br />E <br />C <br />T <br />MA <br />R <br />C <br />O <br /> <br />G <br />U <br />T <br />I <br />E <br />R <br />R <br />E <br />Z <br />C.M