Nnrrlvc.
<br />1. ALL RECEPTACLE OUTLETS SHALL BE LISTED
<br />TAMPER -RESISTANT RECEPTACLE PER GEC
<br />406.11
<br />2. OUTDOOR RECEPTACLES SHALL BE LISTED AS
<br />WEATHER RESISTANT, PER SEC. 406.9(B) (1 )
<br />3. A MINIMUM OF (1) 20-AMP CIRCUIT FOR
<br />BATHROOM(5) OUTLET. SUCH CIRCUIT SHALL
<br />HAVE NO OTHER OUTLETS. THI5 CIRCUIT MAY
<br />SERVE MORE THAN ONE BATHROOM. GEC,
<br />2 10-2 3(A)
<br />4. PROVIDE A MINIMUM OF 2 - 20 AMP SMALL
<br />APPLIANCE CIRCUITS FOR THE KITCHEN
<br />COUNTER TOP5. SUCH CIRCUIT SHALL NO
<br />OTHERS OUTLETS. LOADS SHALL BE BALANCED.
<br />GEG 2 1 0-52(B) (2)
<br />5. PROVIDE A MINIMUM OF 1 - 20 AMP LAUNDRY
<br />BRANCH CIRCUIT. SUCH CIRCUIT SHALL HALL NO
<br />OTHER OUTLETS. GEC, 2 1 0-25(A)
<br />6. ALL 1 20-VOLT, SINGLE PHASE, 15 AND 20
<br />AMPERE BRANCH CIRCUITS IN KITCHEN, FAMILY
<br />ROOM5, DINING ROOMS, LIVING ROOMS,
<br />PARLORS, LIBRARIES, DENS, BEDROOMS,
<br />5UNROOM5, RECREATION ROOMS, CLOSETS,
<br />HALLWAYS, LAUNDRY AREAS, OR 51MILAR
<br />ROOMS OR AREAS SHALL BE PROTECTED BY A
<br />L15TED ARC -FAULT CIRCUIT INTERRUPTER,
<br />COMBINATION -TYPE. (GEG 2 10.1 2.) LIGHTS,
<br />OUTLETS, SD, GM, ETC.
<br />XTnrripc.
<br />1. ALL INSTALLED LUMINAIRE MUST BE
<br />HIGH EFFICACY IN ACCORDANCE WITH
<br />TABLE 150.0-A.
<br />2. EXHAUST FANS MUST BE SWITCHED
<br />SEPARATELY FROM LIGHTING
<br />SYSTEMS.
<br />3. IN BATHROOMS, GARAGES, LAUNDRY
<br />ROOMS, AND UTILITY ROOMS, AT
<br />LEAST ONE LUMINAIRE IN EACH OF
<br />THESE SPACES MUST BE
<br />CONTROLLED BY A VACANCY
<br />SENSOR.
<br />4. OUTDOOR LIGHTING PERMANENTLY
<br />MOUNTED TO A RESIDENTIAL
<br />BUILDING, OR TO OTHER BUILDING ON
<br />THE SAME LOT, MUST MEET THE
<br />REQUIREMENT IN ITEM § 1 50.0(K)3Ai
<br />(ON AND OFF SWITCH) AND THE
<br />REQUIREMENTS IN EITHER ITEM §
<br />1 50.0(K)3AH (PHOTOCELL AND
<br />MOTION SENSOR) OR ITEM §
<br />1 50.O(K)3Aiii (PHOTO CONTROL AND
<br />AUTOMATIC, TIME 5WITGH CONTROL,
<br />ASTRONOMICAL TIME CLOCK, OR
<br />EMG5).
<br />ELECTRICAL NOTES:
<br />T
<br />AFGI
<br />/*AFGI AFGI
<br />FL FL
<br />AFGI
<br />CFI I (N) BEDROOM # 1
<br />(E) 8'-0" GL. HT. (N) SD
<br />�p-EA
<br />GI / AFGI
<br />FLFL
<br />AFGI
<br />GFGI
<br />42+ .
<br />\ SOS
<br />0
<br />FGI
<br />OAFCI
<br />D + AFL
<br />(N)
<br />GO GFGI
<br />1 8+t
<br />I GFGI
<br />2 X L I
<br />GFGI AFGI I A�T-CC w 2 \
<br />(FOR AIR
<br />HANDLER)
<br />(N) LIVING ROOM
<br />I
<br />AA AFGI (E) 6-0" CL. H j} W kD
<br />{ }0
<br />AFGI i ,�
<br />5-2 ` FLU - - CI - - AFGI In
<br />FLZ
<br />\ FL w
<br />EXHAUST \ O O
<br />FAN AF1� \ AFGI m "*
<br />50 GFM
<br />1 ) ALL BRANCH CIRCUITS THAT SUPPLY ALL 1 20-VOLT, SINGLE PHASE, 15
<br />AND 20 AMPERE BRANCH CIRCUITS OUTLETS INSTALLED IN DWELLING
<br />UNIT SHALL BE PROTECTED BY AN ARC, -FAULT CIRCUIT
<br />INTERRUPTER(5). (GEG 2 10.12). FOR ENTIRE CIRCUIT, NOT JUST THE
<br />OUTLETS.
<br />2) PROVIDE A 20 AMP GFGI PROTECTED ELECTRICAL OUTLET WITHIN 56"
<br />OF THE OUTSIDE EDGE OF EACH BATHROOM SINK BASIN. OUTLET
<br />SHALL BE LOCATED ON A WALL OR PARTITION THAT 15 ADJACENT TO
<br />THE BASIN OR INSTALLED ON THE SIDE OR FACE OF THE BASIN
<br />CABINET NOT MORE THAN 1 2" BELOW THE COUNTERTOP.
<br />5) RECEPTACLES SHALL BE LISTED AND LABELED AS
<br />TAMPER -RESISTANT.
<br />4) A MINIMUM OF (1) 20 AMP CIRCUIT 15 REQUIRED FOR BATHROOMS. SUCH
<br />CIRCUITS SHALL HAVE NO OTHER OUTLETS. THIS CIRCUIT MAY SERVE
<br />MORE THAN ONE BATHROOM. GEG 2 1 0.52(D)
<br />5) NO PENDANT LIGHT FIXTURES IN ZONE 5' AWAY AND V ABOVE THE
<br />BATHTUB OR SHOWER.
<br />6) LUMINARIES LOCATED WITHIN THE ACTUAL OUTSIDE DIMENSIONS OF THE
<br />TUB OR SHOWER, UP TO 5 FEET VERTICALLY FROM THE TOP OF THE
<br />BATHTUB RIM OR SHOWER THRESHOLD, SHALL BE MARKED AS
<br />SUITABLE FOR DAMP LOCATIONS, PROVIDED WITH A SOLID LENS AND
<br />BE GFGI PROTECTED.
<br />7) BATHROOM LIGHTING SHALL BE HIGH EFFICACY LUMINARIES (40
<br />LUMENS PER WATT) OR CONTROLLED BY A VACANCY (OCCUPANCY)
<br />SENSOR CERTIFIED TO COMPLY WITH SEC 1 1 9(D) GEES. THIS 15 A
<br />MANUAL ON, AUTO OFF DEVICE.
<br />5) AUTOMATIC ON OR DEVICES WITH AN OVERRIDE 5WITGH P051TION ARE
<br />NOT APPROVED. HIGH EFFICACY, INCANDESCENT LIGHTING OR FANS
<br />ARE REQUIRED TO BE SWITCHED SEPARATELY.
<br />9) RECESSED LUMINARIES INSTALLED IN AN INSULATED CEILING SHALL BE
<br />IC, RATED (ZERO CLEARANCE) AND AT RATED (AIRTIGHT) AND SHALL
<br />BE SEALED AND/OR GASKET BETWEEN CEILING AND HOUSING.
<br />1 0) FOR OCCUPANCIES WITH A HORIZONTAL (FLOOR/CEILING ASSEMBLY)
<br />RATED SEPARATION, THE RECESSED FIXTURES SHALL BE PROTECTED
<br />TO THE RATING OF THE SEPARATION (1 HOUR) OR BE LISTED FOR THE
<br />REQUIRED PROTECTION. THIS GENERALLY APPLIES TO RESIDENTIAL
<br />CONDOMINIUM CONSTRUCTION WHERE UNITS ARE ABOVE OR BELOW
<br />OTHER UNITS.
<br />1 1) ALL RECEPTACLES LISTED IN SECTION 2 1 0-52 SHALL BE L15TED AS
<br />TAMPER -RESISTANT FOR ALL 15 AND 20 AMPERE RECEPTACLES IN
<br />DWELLING UNIT FAMILY, DINING, LIVING, PARLORS, LIBRARIES, DENS,
<br />BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS,
<br />OR 51MILAR ROOMS AND AREAS PER GEG SEC 406.12
<br />FL
<br />WEATHERPROOF PHOTO
<br />IN/ PLUG GAP CONTROL
<br />GFGI/
<br />wP NOTE - HARD WIRED SMOKE
<br />DETECTORS [CRC R314] :
<br />A MINIMUM OF 20 FT. FROM PERMANENT COOKING
<br />EQUIPMENT (OR 10 FT. WITH PHOTO -ELECTRIC
<br />TYPE.
<br />LEGEND
<br />TITLE 24 - 2ND UNIT NOTES: WHOLE -BUILDING VENTILATION RATE j EXISTING WALL TO REMAIN
<br />HVAG EQUIPMENT: MINI SPLIT HP SUMMARY: NEW WALL
<br />HEATING ENTER THE REQUIRED FAN FLOW RATE (GFM):
<br />EFF. TYPE: HSPF
<br />HSPF / GOP: 5.7 ■ CONTINUOUS FAN FLOW (GFM) = 407 / 100 + -7.5 (1 + 1) = 20 GFM
<br />GAP 47: 12000 (USE 50 GFM) ELECTRICAL LEGEND
<br />GAP 1 7: 7 500
<br />COOLING ■ USE THE FAN FLOW RATE FROM THIS SUMMARY FOR SELECTION OF
<br />EFF. TYPE: EER5EER THE WHOLE -BUILDING VENTILATION FAN AND FOR THE DUCT DESIGN AMP PANEL (PER PLANS)
<br />SEER / 5EER2: 20 FOR THE WHOLE -BUILDING VENTILATION SYSTEM FROM TABLE 7.1.
<br />THERMOSTAT - SETBACK I G- IRRIGATION CONTROLLER
<br />HEATING $ COOLING I5 DUCTED ■ DUGT 51ZE (IN) = 5" (V DUCT 51ZE ® (WEATHER OR 501L M015TURE BASED)
<br />DUCT LOCATION - ATTIC DUPLEX ELEC. OUTLET (1 1 OV)
<br />CEILING INSULATION VENTED MAXIMUM ALLOWABLE DUCT LENGTH (FT.) = 1 00'MAX
<br />WATER HEATER: DOMESTIC HOT WATER (DHW) THE SWITCH OPERATING THE EXHAUST FAN SHALL HAVE A LABEL =AFGI GROUND FAULT INTERUPTED CIRCUIT
<br />NATURAL GA5 STATING: DUPLEX OUTLET (1 20V IN/
<br />ENERGY FACTOR: 0.95 EFF. "OPERATE WHEN HOUSE 15 IN USE" OR/ GFGI
<br />200,000 BTU/HR "FAN 15 TO BE LEFT ON TO ENSURE INDOOR AIR QUALITY" OR/ GROUND FAULT INTERRUPTER)
<br />KITCHEN PIPE INSULATION "KEEP ON EXCEPT WHEN GONE OVER 7 DAYS" GFGI/DUPLEX OUTLET (1 20V WEATHER
<br />pNp RESISTANT OUTLET, (5FI)
<br />DUCT INSULATION VALUES: R-6 EXHAUST FAN SHALL HAVE A SOUND RATING OF 1 50NE OR LE55 WP WATER PROOF
<br />FAN SPECIFICATIONS: H t
<br />MANUFACTURE PANASONIC - WHISPER GREEN 50 GFM H05E BIBS W/ ANTI-51PHONE
<br />WALL MOUNTED LIGHT (FL)
<br />MODEL: FV-OS- 1 1 VKL 1
<br />CEILING MOUNTED LIGHT (AFGI - FL)
<br />6" RECESS LIGHT (AFGI - FL) -- HIGH EFFICACY
<br />CEILING FAN W/ LIGHT (AFGI - FL)
<br />SINGLE POLE SWITCH
<br />2 EXHAUST FAN (1 00 GFM) TO OUTSIDE
<br />ENERGY STAR RATED $ HUMID15TAT CONTROLLED
<br />LIGHT & EXHAUST FAN COMBO
<br />FL FLUORESCENT LIGHT BULB FIXTURE _ (PIN BASE +
<br />CERTIFIED TO
<br />D DIMMER SWITCH THE ENERGY
<br />I GOMMI5510N)
<br />+05 OCCUPANT SENSORS
<br />+3 3-WAY SWITCH
<br />W SMOKE DETECTOR BATTERY
<br />Q I ®5D (INTER -CONNECTED)
<br />vo
<br />z CARBON MONOXIDE DETECTORS
<br />®GO (GRG R3 1 5) SECTIONS R315.1 & R3 15.2
<br />WEATHERPROOF DATA COMMUNICATIONS OUTLET
<br />W/ PLUG GAP
<br />GFGI/ (INDICATE NONSTANDARD MOUNTING HT.)
<br />WP
<br />TELEPHONE OUTLET
<br />1 (INDICATE NONSTANDARD MOUNTING HT.)
<br />(N) TANKLE55 NOTES:
<br />D 1
<br />WH TELEVISION OUTLET
<br />�.; A ® (N) TANKLE55 WH 1 9 9,900 BTU (4'-0" MIN. TV (INDICATE NONSTANDARD MOUNTING HT.)
<br />it SEPARATE FROM WH VENT TO WINDOWS.)
<br />a NOT PROVIDE SHALL VENT THRU ROOF. 2X4 LIGHTS - FLUORESCENT TUBE
<br />(CMG 802.8)
<br />MO5 MANUAL -ON OCCUPANCY SENSOR (1) IONIZATION
<br />MANUFACTURE: RHEEM
<br />MODEL: ECOH2O0XLN- 1 (OUTDOOR) H H = HUMID15TAT CONTROLLED VS VACANCY
<br />ENERGY FACTOR: OA 3 SENSOR
<br />�I GAS: NATURAL ELECTRICAL NOTES:
<br />- - AA
<br />5-2
<br />NOTE:
<br />PROVIDE AN EXHAUST
<br />RATE OF 250 GFM
<br />FAN IN THE KITCHEN
<br />GFGI HOOD OVER ELECTRIC
<br />RANGE: _
<br />IRAN67F:
<br />% GE OR 1 60 GFM
<br />OD OVER NATURAL GA5
<br />% GE OR 250 GFM
<br />(E) MAIN FRONT HOUSE -
<br />TO REMAIN - NO CHANGE)
<br />(E) AG
<br />(E) 24X36 FLR CONDENSER
<br />ACCESS A (N) TANKLE55 RELOCATE (N)
<br />(GRG R405.4) WH
<br />(E) AMP
<br />PANEL X
<br />I� lil i I
<br />�Ll
<br />(E) BATH #2 (E) BEDROOM #3
<br />_ (E) 6-0" CL. HT. (I-) V-O" CL. HT.
<br />1[�DI I
<br />rz U
<br />W w o0 w
<br />.c
<br />[GARAGE CONVERT INTO ADU UNIT]
<br />ELECTRICAL PLAN
<br />SCALE: 1 /4" = 1'-0"
<br />CITY OF SANTA ANA
<br />PI nni ilding A ency
<br />z N UEN
<br />v C7i ::GN + ASSOCIATES
<br />FO 'i-GI�❑VE,•CAV
<br />E CE
<br />TEL: (714) 4613-71 63
<br />WEBSITE: WWW,WIX.COM/
<br />NGUYENADESIGN/ANTHONY
<br />THE DRAWINGS, IDEAS,
<br />Ma
<br />St
<br />ARGEMENTS
<br />AND
<br />I I[ ATI❑NS CONTAINED IN
<br />H
<br />E.D❑CUMENTS ARE THE
<br />Dale,
<br />PROPERTY AND COPYRIGHT OF
<br />NGUYEN DESIGN + ASSOCIATES
<br />AND SHALL NOT BE USED ON
<br />ANY OTHER WORK EXCEPT BY
<br />AGREEMENT WITH NGUYEN
<br />DESIGN + ASSOCIATES.
<br />WRITTEN DIMENSIONS SHALL
<br />TAKE PREFERENCE OVER SCALED
<br />DIMENSIONS AND SHALL BE
<br />VERIFIED ON THE JOB SITE.
<br />ANY DISCREPANCY SHALL BE
<br />BROUGHT TO THE NOTICE OF
<br />NGUYEN DESIGN + ASSOCIATES.
<br />PRIOR TO THE COMMENCEMENT
<br />OF ANY WORK.
<br />1. PROVIDE APPROVED SMOKE ALARMS, SMOKE ALARMS SHALL BE
<br />INTERCONNECTED SUCH THAT THE ACTIVATION OF ONE ALARM WILL
<br />ACTIVATE ALL ALARMS.
<br />2. SMOKE DETECTORS SHALL BE "HARD WIRED" AND SHALL BE EQUIPPED
<br />WITH BATTERY BACK-UP @ ALL NEW BEDROOMS.
<br />3. BATTERY OPERATED SMOKE DETECTOR PERMITTED IN EXISTING
<br />CONSTRUCTION.
<br />4. FOR SINGLE-FAMILY DWELLINGS AND DUPLEXES ARE NOT CHECKED
<br />FOR PLUMBING, MECHANICAL AND ELECTRICAL CODE COMPLIANCE.
<br />THESE DISCIPLINES ARE SUBJECT TO FIELD INSPECTION.
<br />5. THE RESIDENCE SHALL CONFORM TO THE STATE ENERGY STANDARDS.
<br />6. WALLS 2 FT. OR GREATER SHALL HAVE AN OUTLET. OUTLETS SHALL BE
<br />SPACED MAX. 1.2 FT. APART, AND A MAXIMUM OF 6 FT. FROM END OF
<br />WALL5 OR OPENING (GEC 2 1 0-52A)
<br />7. ALL RECEPTACLE OUTLETS SHALL BE LISTED TAMPER-RESISTAND
<br />RECEPTACLE PER GEG 406.1 1.
<br />5. BATHROOM RECEPTACLES SHALL BE SERVED BY A DEDICATED 20
<br />AMP CIRCUIT PER GEG 2 1 0-52(D).
<br />ENERGY LIGHTING
<br />A. KITCHENS. AT LEAST HALF THE INSTALLED WATTAGE OF LUMINARIES IN
<br />KITCHENS SHALL BE HIGH EFFICACY AND THE ONES THAT ARE NOT MUST
<br />BE SWITCHED SEPARATELY.
<br />B. LIGHTING IN BATHROOMS, GARAGES, LAUNDRY ROOMS AND UTILITY
<br />ROOMS. ALL LUMINARIES SHALL EITHER BE HIGH EFFICACY OR SHALL BE
<br />CONTROLLED BY AN OCCUPANT SENSOR.
<br />C. OTHER ROOMS. ALL LUMINARIES SHALL EITHER BE HIGH EFFICACY OR
<br />SHALL BE CONTROLLED BY AN OCCUPANT 5EN50R OR DIMMER.
<br />CLOSETS THAT ARE LESS THAN 70 SQUARE FOOT ARE EXEMPT FROM
<br />THI5 REQUIREMENT.
<br />FOR ALTERATIONS, REPAIRS AND ADDITIONS OF EXISTING DWELLINGS
<br />EXCEEDING $ 1,000 CARBON MONOXIDE ALARMS ARE REQUIRED IN THE
<br />SPECIFIC PERMITTED DWELLINGS OR SLEEPING UNITS THAT HAVE
<br />ATTACHED GARAGES OR FUEL -BURNING APPLIANCES. THE CARBON
<br />MONOXIDE ALARMS MAY BE BATTERY OPERATED AND NOT
<br />INTERCONNECTED. (CRC R3 1 4.5.1 )
<br />- ALARMS WILL BE BATTERY OPERATED.
<br />- ALARMS SHALL BE LOCATED OUTSIDE OF EACH SEPARATE DWELLING
<br />UNIT SLEEPING AREA NEAR THE BEDROOMS) AND ON EVERY LEVEL
<br />INCLUDING BASEMENTS. (GRG R315.3)
<br />- LISTING $ APPROVAL BY THE OFFICE OF THE STATE FIRE MARSHAL
<br />FOR COMBINED CARBON MONOXIDE & SMOKE ALARMS ARE ALLOWED.
<br />ALL NEW CONSTRUCTION, INTERIOR OR EXTERIOR ALTERATIONS, REPAIRS,
<br />OR ADDITIONS REQUIRING A PERMIT AND HAVING A VALUATION IN EXCESS
<br />OF $ 1,000, AN APPROVED CARBON MONOXIDE ALARM SHALL BE
<br />INSTALLED IN DWELLING UNITS AND IN SLEEPING UNITS WITHIN WHICH
<br />FUEL -BURNING APPLIANCES ARE INSTALLED AND IN DWELLING UNITS THAT
<br />HAVE ATTACHED GARAGES SHALL BE PROVIDED WITH CARBON
<br />MONOXIDE ALARMS (CRC R3 1 5)
<br />- CARBON MONOXIDE ALARMS SHALL ONLY BE REQUIRED IN THE
<br />5PEGIFIG DWELLING UNIT OR SLEEPING UNIT FOR WHICH THE PERMIT WA5
<br />OBTAINED. CARBON MONOXIDE ALARMS REQUIRED BY SECTIONS
<br />(CRC, R3 15.1 AND R5 1 5.2) SHALL BE INSTALLED. UL 2034/2075
<br />-IN NEW BUILDING, CARBON MONOXIDE ALAM5 SHALL BE
<br />INTERCONNECTED AND HARDWIRED. (CRC R3 15.1 AND R3 15.2)
<br />- ALARMS SHALL BE LOCATED OUTSIDE OF EACH SEPARATE DWELLING
<br />UNIT SLEEPING AREA NEAR THE BEDROOM(5) AND ON EVERY LEVEL
<br />INCLUDING BASEMENTS. (CRC R3 15.3)
<br />- WHERE MORE THAN ONE CARBON MONOXIDE ALARM IS REQUIRED TO
<br />BE INSTALLED WITHIN THE DWELLING UNIT OR WITHIN A SLEEPING UNIT
<br />THE ALARM SHALL BE INTERCONNECTED IN A MANNER THAT
<br />ACTIVATION OF ONE ALARM SHALL ACTIVATE ALL OF THE ALARMS IN
<br />THE INDIVIDUAL UNIT.
<br />EXCEPTION:
<br />INTERCONNECTION 15 NOT REQUIRED IN EXISTING DWELLING UNITS WHERE
<br />REPAIRS DO NOT RESULT IN THE REMOVAL OF WALL AND CEILING FINISHED,
<br />THERE 15 NO ACCESS BY MEANS OF ATTIC, BASEMENT OR GRAWL SPACE,
<br />AND NO PREVIOUS METHOD FOR INTERCONNECTION EXISTED.
<br />QROF E^SS ,,
<br />IOAn
<br />G/ c
<br />j9/01 /2025
<br />CONSULTANT:
<br />F�
<br />W "
<br />UO��
<br />z W
<br />L7A�oT
<br />Z��z�
<br />dw�Lu
<br />� Z �Lu
<br />O `
<br />v
<br />ELECTRICAL
<br />PLAN
<br />DRAYNING TITLE:
<br />PLAN CHECK:
<br />PLAN GHEGK# 1 01 123252
<br />C56# 4504613
<br />REV151ON5:
<br />DATE
<br />Z1
<br />OS- 1 1 -2025
<br />0
<br />09-0 1 -2025
<br />DRAWN BY: ANTHONY NGUYEN
<br />5GALE:
<br />AS NOTED
<br />DATE:
<br />09-0 1 -2025
<br />PROJECT NO:
<br />N2403 1 03
<br />SHEET NO. 07 OF
<br />15 SHEETS
<br />
|