Laserfiche WebLink
RESIDENTIAL MEASURES SUMMARY <br />RMS-1 <br />Project Name <br />Building Type m Single Family m Addition Alone <br />Date <br />2349 N Spurgeon St ADU <br />❑ Multi Family ❑ Existing+ Addition/Alteration <br />11012912024 <br />Project Address <br />California Energy Climate Zone <br />Total Cond. Floor Area <br />Addition <br /># of Units <br />2349 N Spurgeon St ADU <br />Santa Ana <br />CA Climate Zone 08 <br />1 1,000 <br />I 1,000 <br />I 1 <br />INSULATION <br />Area <br />Construction Type <br />Cavity (ft) Special Features <br />Status <br />Wall Wood Framed <br />R 15 806 <br />New <br />Wall Wood Framed <br />R 15 176 <br />New <br />Wall Wood Framed <br />R 15 97 <br />New <br />Wall Wood Framed <br />R 15 53 <br />New <br />Wall Wood Framed <br />R 19 55 <br />New <br />Demising Wood Framed <br />- <br />no insulation 43 <br />Existing <br />Demising Wood Framed <br />R 13 43 <br />New <br />Slab Unheated Slab -on -Grade <br />- no insulation 1.000 Perim = 106' <br />New <br />FENESTRATION <br />I Total Area: <br />330 Glazing Percentage: 33.0% New/Altered Average U-Factor: <br />0.30 <br />Orientation Area (ft) <br />U-Fac SHGC Overhang Sidefins Exterior Shades <br />Status <br />Front (S) 70.0 <br />0.300 <br />0.23 none none N/A <br />New <br />Front (S) 24.0 <br />0.300 <br />0.23 none none N/A <br />New <br />Rear (N) 63.0 <br />0.300 <br />0.23 none none N/A <br />New <br />Right (E) 96.0 <br />0.300 <br />0.23 none none N/A <br />New <br />Right (E) 15.0 <br />0.300 <br />0.23 none none N/A <br />New <br />Leff (W) 48.0 <br />0.300 <br />0.23 none none N/A <br />New <br />Left (W) 13.5 <br />0.300 <br />0.23 none none N/A <br />New <br />HVAC SYSTEMS <br />Qty. Heating <br />Min. Eff <br />Cooling Min. Eff Thermostat <br />Status <br />1 Electric Heat Pump <br />8.50 HSPF <br />Split Heat Pump 15.0 SEER Setback <br />New <br />HVAC DISTRIBUTION <br />Duct <br />Location Heating <br />Cooling Duct Location R-Value <br />Status <br />(N) HVAC System Ductless / with Fan <br />Ductless n!a n1a <br />New <br />WATER HEATING <br />Qty. Type <br />Gallons <br />Min. Eff Distribution <br />Status <br />1 Small Instantaneous Gas <br />1 <br />097 Standard <br />New <br />EnergyPro 9.3 by EnergySoft User Number.' 3835 <br />1D: 17066 <br />Page 14 of 21 <br />RESIDENTIAL MEASURES SUMMARY <br />RMS-1 <br />Project Name <br />2349 N Spurgeon St ADU <br />Project Address <br />2349 N Spurgeon St ADU <br />I Building Type m Single Family CO Addition Alone <br />❑ Multi Family ❑ Existing+ Addition/Alteration <br />California Energy Climate Zone Total Cond. Floor Area Addition <br />Santa Ana CA Climate Zone 08 1,000 1,000 <br />Date <br />1012912024 <br /># of Units <br />1 <br />INSULATION <br />Construction Type <br />Area <br />Cavity (ft) Special Features <br />Status <br />Roof Wood Framed Attic <br />R 30 1.000 Add=R-13.0 <br />New <br />FENESTRATION <br />Orientation Area(ft) <br />Total Area: 330 Glazing Percentage: 33.0% 1 New/Altered Average U-Factor: <br />U-Fac SHGC Overhang Sidefins Exterior Shades <br />0.30 <br />Status <br />HVAC SYSTEMS <br />Qty. Heating <br />Min. Eff Cooling Min. Eff Thermostat <br />Status <br />HVAC DISTRIBUTION Duct <br />Location Heating Cooling Duct Location R-Value <br />Status <br />WATER HEATING <br />Qty. Type <br />Gallons Min. Eff Distribution <br />Status <br />EnergyPro 9.3 by EnergySoft User Number.' 3835 1D: I7066 <br />Page 15 of 21 <br />HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY <br />Project Name <br />2349 N Spurgeon St ADU <br />System Name <br />(N) HVAC System <br />Date <br />10/29/2024 <br />Floor Area <br />1,000 <br />ENGINEERING CHECKS <br />SYSTEM LOAD <br />Number of Systems <br />, 1 <br />Total Room Loads <br />Return Vented Lighting <br />Return Air Ducts <br />Return Fan <br />Ventilation <br />Supply Fan <br />Supply Air Ducts <br />TOTAL SYSTEM LOAD <br />COIL <br />CFM <br />533 <br />0 <br />COOLING <br />PEAK <br />COIL HTG. <br />PEAK <br />Heating System <br />Output per System 1 30.000 <br />Sensible <br />Latent <br />CFM <br />Sensible <br />11,469 <br />489 <br />336 <br />13.359 <br />0 <br />Total Output (Btuh) <br />1 30.000 <br />0 <br />Output (Btuh/sgft) <br />1 30.0 <br />0 <br />Cooling System <br />0 <br />0 <br />Output per System <br />30,000 <br />01 <br />0 <br />0 <br />0 <br />Total Output (Btuh) <br />30.000 <br />0 <br />489 <br />0 <br />Total Output (Tons) <br />2.5 <br />0 <br />0 <br />Total Output (Btuh/sgft) <br />30.0 <br />Total Output (sgft/Ton) <br />400.0 <br />1 11,469 <br />13,359 <br />Air System <br />CFM per System <br />0 <br />HVAC EQUIPMENT SELECTION <br />Airflow (cfm) <br />0 <br />Ductless Mini Split Heat Pump <br />0 <br />22.413 <br />Airflow (cfm/sgft) <br />0.00 <br />E28702 <br />Airflow (cfm/Ton) <br />Outside Air (%) <br />0.0 <br />0 0% <br />22.413 <br />Jan 1 Alvi <br />Total Adjusted System Output <br />(Adjusted for Peak Design conditions) <br />TIME OF SYSTEM PEAK <br />0F <br />Outside Air (cfm/sgft) 0.00 <br />1 <br />- <br />Note. values above given at ARI conditions <br />I Aug 3 PM <br />HEATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heating Peak) <br />33IF <br />Outside Air 4r- <br />0 cfm <br />68 IF <br />- <br />0I <br />Heating Coil <br />I <br />n_5 . . <br />FROOM� <br />68 °F <br />COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak) <br />Outside Air <br />0 cfm <br />75 61 ' - 55 S4 - <br />Cooling Coil <br />H <br />L7 <br />55 / 54 <br />46.7% ROOM <br />7T <br />CITY OF SANTA ANA <br />Plannirig and Building Age cy <br />M <br />. I1__ <br />2022 Single -Family Residential Mandatory Requirements Summary 'IF <br />rA <br />qzt <br />NOTE: Single-family residential buildings subject to the Energy Codes must comply with all applicable mandatory measures, regardless of the com lance approach used. Review the respective section for more information. pptoved <br />(04/2022 <br />Buildin Envelope: R E R `ITT I S N C <br />Air Leakage. Manufactured fenestration, exterior doors. and exterior pet doors must limit air leakage to 0.3 CFM per squ <br />re foo r <br />§ 110.6(a)l: <br />less when tested per NFRC-400, ASTM E283. or AAMA+WDMA/CSA 101/I.S.2/A440-2011. ' <br />§ 110.6(a)5: <br />Labeling. Fenestration products and exterior doors must have a label meeting the requirements of § 10-111(a). <br />Field fabricated exterior doors and fenestration products must use 1-1-factorsand solar heat gain coefficient (SHGC) <br />flues from <br />§ 110.6(b): <br />Tables 110.E-A, 110.E-B, or JA4.5 for exterior doors. The must be caulked and/or weather-stripped. ' <br />Air Leakage. All joints, penetrations, and other openings in the building envelope that are potential sources of air leakagemust <br />be <br />§ 110-7: <br />caulked, asketed. or weather stripped. <br />§ 110.8(a): <br />Insulation Certification by Manufacturers. Insulation must be certified by the Department of Consumer Affairs, Bureau <br />of I�yi�hlalIC <br />VV �� GG/1.J7 <br />Goods and Services (BHGS). <br />§ 110.8(g): <br />Insulation Requirements for Heated Slab Floors. Heated slab floors must be insulated per the requirements of § 110. <br />g). <br />Roofing Products Solar Reflectance and Thermal Emittance. The thermal emittance and aged solar reflectance valu <br />s <br />§ 110.8(i): <br />roofing material must meet the requirements of § 110.8(i) and be labeled per §10-113 when the installation of a cool roof <br />s specified <br />on the CF1R. <br />§ 110.8(j): <br />Radiant Barrier. When required, radiant barriers must have an emittance of 0.05 or less and be certified to the Departm t of Consumer <br />Affairs. <br />Roof Deck, Ceiling and Rafter Roof Insulation. Roof decks in newly constructed attics in climate zones 4 and 8-16 area -weighted <br />average U-factor not exceeding U-0.184. Ceiling and rafter roofs minimum R-22 insulation in wood -frame ceiling: or area -weighted average <br />§ 150.0(a): <br />U-factor must not exceed 0.043. Rafter roof alterations minimum R-19 or area -weighted average U-factor of 0.054 or less. Attic access <br />doors must have permanently attached insulation using adhesive or mechanical fasteners. The attic access must be gasketed to <br />prevent air leakage. Insulation must be installed in direct contact with a roof or ceiling which is sealed to limit infiltration and exfiltrationi <br />as specified in § 110.7.. including but not limited to placing insulation either above or below the roof deck or on to of a drywall ceiling <br />§ 150.0(b): <br />Loose -fill Insulation. Loose fill insulation must meet the manufacturer's required density for the labeled R-value. <br />Wall Insulation. Alinimum R-13 insulation in 2x4 inch wood framing wall or have a U-factor of 0.102 or less, or R-20 in 2x6 inch wood <br />§ 150.0(c): <br />framing or have a U-factor of 0.071 or less. Opaque non -framed assemblies must have an overall assembly U-factor not exceeding 0.102. <br />Masonry walls must meet Tables 150.1-A or B. ' <br />§ 150.0(d): <br />Raised -floor Insulation. Minimum R-19 insulation in raised wood framed floor or 0.037 maximum U-factor. ' <br />Slab Edge Insulation. Slab edge insulation must meet all of the following: have a water absorption rate, for the insulation material alone <br />§ 150.0(f): <br />without facings, no greater than 0.3 percent, have a water vapor permeance no greater than 2.0 perm per inch: be protected from <br />physical damage and UV light deterioration: and. when installed as part of a heated slab floor, meet the requirements of § 110.8(g). <br />Vapor Retarder. In climate zones 1 through 16. the earth floor of unvented crawl space must be covered with a Class I or Class II <br />§ 150.0(g)l: <br />vapor retarder. This requirement also applies to controlled ventilation crawl space for buildings complying with the exception to <br />150.0(d). <br />Vapor Retarder. In climate zones 14 and 16, a Class I or Class II vapor retarder must be installed on the conditioned space side of <br />§ 150.0(g)2: <br />all insulation in all exterior walls, vented attics, and unvented attics with air -permeable insulation. <br />Fenestration Products. Fenestration, including skylights. separating conditioned space from unconditioned space or outdoors must have <br />§ 150.0(q): <br />a maximum U-factor of 0.45 or area -weighted average U-factor of all fenestration must not exceed 0.45. ' <br />V <br />N Q .. <br />a) U C <br />�_ I- <br />1 t <br />Q) <br />• <br />+� <br />W L_ a) O <br />• <br />� O C;) 0 <br />1",_.M � CV <br />4i - 3:= r- <br />V Q <br />U <br />41 <br />I` <br />M <br />. > <br />- <br />Fireplaces, Decorative Gas Appliances, and Gas Log: <br />§ 110.5(e) Pilot Light. Continuously burning pilot lights are not allowed for indoor and outdoor fireplaces. <br />§ 150.0(e)l: Closable Doors. Masonry or factory -built fireplaces must have a closable metal or glass door covering the entire opening of the firebox. <br />Combustion Intake. Masonry or factory -built fireplaces must have a combustion outside air intake. which is at least six square inches in V J <br />§ 150.0(e)2: area and is equipped with a readily accessible, operable, and tight -fitting damper or combustion -air control device. ' W <br />§ 150.0(e)3: Flue Damper. Masonry or factory -built fireplaces must have a flue damper with a readily accessible control. ' <br />Space Conditioning, Water Heating, and Plumbing System: <br />Certification. Heating. ventilation. and air conditioning (HVAC) equipment, water heaters, showerheads, faucets, and all other <br />§ 110.0-§ 110.3: <br />regulated appliances must be certified by the manufacturer to the California Energy Commission. ' <br />§ 110.2(a): <br />HVAC Efficiency. Equipment must meet the applicable efficiency requirements in Table 110.2-A through Table 110.2-N. <br />Controls for Heat Pumps with Supplementary Electric Resistance Heaters. Heat pumps with supplementary electric resistance <br />§ 110.2(b): <br />heaters must have controls that prevent supplementary heater operation when the heating load can be met by the heat pump alone: <br />and in which the cut -on temperature for compression heating is higher than the cut -on temperature for supplementary heating, and <br />the cut-off temperature for compression heating is higher than the cut-off temperature for supplementary heating. ' <br />Thermostats. All heating or cooling systems not controlled by a central energy management control system (EMCS) must have a <br />§ 110.2(c): <br />setback thermostat. ' <br />Insulation. Unfired service water heater storage tanks and solar water -heating backup tanks must have adequate insulation, or tank <br />110.3 c 3: <br />surface heat loss rating. <br />Isolation Valves. Instantaneous water heaters with an input rating greater than 6.8 kBtu per hour (2 kW) must have isolation valves with <br />§ 110.3(c)6: <br />hose bibbs or other fittings on both cold and hot water lines to allow for flushing the water heater when the valves are closed. <br />D <br />r <br />�./ / <br />W <br />2i <br />LL <br />cj� O <br />^ <br />� J V_ <br />5l6122 <br />Q w <br />0 W <br />Z = <br />Q U) <br />2 <br />N <br />2022 Single -Family Residential Mandatory Requirements Summary S 2022 Single -Family Residential Mandatory Requirements Summary 4S 2022 Single -Family Residential Mandatory Requirements Summary e 2022 Single -Family Residential Mandatory Requirements Summary W <br />Pilot Lights. Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces:. household cooking appliances <br />§ 110.5, <br />(except appliances without an electrical connection with pilot lights <br />supply <br />P Y voltage that consume less than 150 Btu per hour ): and pool and e 9 <br />spa heaters. ' <br />Building Cooling and Heating Loads_ Heating and/or cooling loads are calculated in accordance with the ASHRAE Handbook, <br />§ 150.0(h)l: <br />Equipment Volume, Applications Volume. and Fundamentals Volume: the SMACNA Residential Comfort System Installation <br />Standards Manual: or the ACCA Manual J using design conditions specified in § 150.0(h)2. <br />§ 150.0(h)3A: <br />Clearances. Air conditioner and heat pump outdoor condensing units must have a clearance of at least five feet from the outlet of any <br />dryer. <br />Liquid Line Drier. Air conditioners and heat pump systems must be equipped with liquid line filter driers if required, as specified by the <br />§ 150.0(h)3B: <br />manufacturer's instructions. <br />Water Piping, Solar Water -heating System Piping, and Space Conditioning System Line Insulation. All domestic hot water <br />150.0 )1: <br />piping must be insulated as specified in § 609.11 of the California Plumbing Code.' <br />Insulation Protection. Piping insulation must be protected from damage, including that due to sunlight, moisture, equipment' <br />§ 150.00)2: <br />maintenance. and wind as required by §120.3(b). Insulation exposed to weather must be water retardant and protected from UV light (no <br />adhesive tapes). Insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space must <br />include, or be protected by, a Class I or Class II vapor retarder. Pipe insulation buried below grade must be installed in a waterproof and <br />non -crushable casing or sleeve. <br />Gas or Propane Water Heating Systems. Systems using gas or propane water heaters to serve individual dwelling units must <br />designate a space at least 2.5' x 2.5' x 7' suitable for the future installation of a heat pump water heater, and meet electrical and <br />§ 150.0(n)l: <br />plumbing requirements, based on the distance between this designated space and the water heater location: and a condensate drain nc <br />more than 2" higher than the base of the water heater <br />Solar Water -heating Systems. Solar water -heating systems and collectors must be certified and rated by the Solar Rating and <br />§ 150.0(n)3: <br />Certification Corporation (SRCC), the International Association of Plumbing and Mechanical Officials. Research and Testing (IAPMO <br />R&T). or by a listing agency that is approved by the executive director. <br />Ducts and Fans: I <br />Ducts. Insulation installed on an existing space -conditioning duct must comply with § 604.0 of the California Mechanical Code (CMC). If a <br />§ 110 8(d)3 <br />contractor installs the insulation, the contractor must certify to the customer, in writing, that the insulation meets this requirement. <br />CMC Compliance. All air -distribution system ducts and plenums must meet CMC §§ 601.0-605.0 and ANSIISMACNA-006-2006 HVAC <br />Duct Construction Standards Metal and Flexible 3rd Edition. Portions of supply -air and return -air ducts and plenums must be insulated to <br />R-6.0 or higher: ducts located entirely in conditioned space as confirmed through field verification and diagnostic testing (RA3.1.4.3.8) <br />do not require insulation. Connections of metal ducts and inner core of flexible ducts must be mechanical) fastened. Openings must be <br />q Y <br />sealed with mastic. tape, or other duct -closure system that meets the applicable UL requirements, or aerosol sealant that meets UL 723 <br />§ 150.0(m)l: <br />The combination of mastic and either mesh or tape must be used to seal openings greater than % . If mastic or tape is used. Building <br />cavities, air handler support platforms, and plenums designed or constructed with materials other than sealed sheet metal. duct board or <br />flexible duct must not be used to convey conditioned air. Building cavities and support platforms may contain ducts. ducts installed in <br />these spaces must not be compressed. ' <br />Factory -Fabricated Duct Systems. Factory -fabricated duct systems must comply with applicable requirements for duct construction. <br />§ 150.0(m)2: <br />connections, and closures: joints and seams of duct systems and their components must not be sealed with cloth back rubber adhesive <br />duct tapes unless such tape is used in combination with mastic and draw bands. <br />Field -Fabricated Duct Systems. Field -fabricated duct systems must comply with applicable requirements for: pressure -sensitive tapes, <br />§ 150.0(m)3: <br />mastics, sealants, and other requirements specified for duct construction. <br />§ 150.0(m)7: <br />Backdraft Damper. Fan systems that exchange air between the conditioned space and outdoors must have backdraft or automatic <br />dampers. <br />Gravity Ventilation Dampers. Gravity ventilating systems serving conditioned space must have either automatic or readily accessible, <br />§ 150.0(m)8: <br />manually operated dampers in all openings to the outside. except combustion inlet and outlet air openings and elevator shaft vents. <br />Protection of Insulation. Insulation must be protected from damage due tosunlight, moisture, equipment maintenance, and wind. <br />§ 150.0(m)9: <br />Insulation exposed to weather must be suitable for outdoor service (e.g.. protected by aluminum, sheet metal, painted canvas, or plastic <br />cover). Cellular foam insulation must be protected as above or painted with a water retardant and solar radiation -resistant coatin . <br />§ 150.0(m)10: <br />Porous Inner Core Flex Duct. Porous inner cores of flex ducts must have a non -porous layer or air barrier between the inner core and <br />outer vapor barrier. <br />Duct System Sealing and Leakage Test. When space conditioning systems use forced air duct systems to supply conditioned air to an <br />§ 150.0(m)l 1: <br />occupiable space, the ducts must be sealed and duct leakage tested. as confirmed through field verification and diagnostic testing, in <br />accordance with Reference Residential Appendix RA3.1. <br />Air Filtration. Space conditioning systems with ducts exceeding 10 feet and the supply side of ventilation systems must have MERV 13 <br />§ 150.0(m)12: <br />or equivalent filters. Filters for space conditioning systems must have a two inch depth or can be one inch if sized per Equation 150.0-A. <br />Clean -filter pressure drop and labeling must meet the requirements in §150.0(m)l2. Filters must be accessible for regular service. Filter <br />racks or grilles must use gaskets. sealing, or other means to close gaps around the inserted filters to and prevents air from bypassing the <br />filter. ' <br />Space Conditioning System Airflow Rate and Fan Efficacy. Space conditioning systems that use ducts to supply cooling must have <br />a hole for the placement of a static pressure probe. or a permanently installed static pressure probe in the supply plenum. Airflow must <br />§ 150.0(m)13: be >_ 350 CFlv1 per ton of nominal cooling capacity. and an air -handling unit fan efficacy 5 0.45 watts per CFM for gas furnace air <br />handlers and 5 0.58 watts per CFM for all others. Small duct high velocity systems must provide an airflow >_ 250 CFM per ton of nominal <br />cooling capacity. and an air -handling unit fan efficacy 5 0.62 watts per CFM. Field verification testing is required in accordance with <br />Reference Residential Appendix RA3.3. " <br />Ventilation and Indoor Air Quality: <br />Requirements for Ventilation and Indoor Air Quality. All dwelling units must meet the requirements of ASHRAE Standard 62.2, <br />§ 150.0(0)1: <br />Ventilation and Acceptable Indoor Air Quality in Residential Buildings subject to the amendments specified in § 150.0(o)l. " <br />Central Fan Integrated (CFI) Ventilation Systems. Continuous operation of CFI air handlers is not allowed to provide the whole- <br />§ 150.0(o)l B: <br />dwelling unit ventilation airflow required per §150.0(o)l C. A motorized damper(s) must be installed on the ventilation duct(s) that <br />prevents all airflow through the space conditioning duct system when the damper(s) is closed andcontrolled per §150.0(o)1Biii&iv. CFI <br />ventilation systems must have controls that track outdoor air ventilation run time. and either open or close the motorized damper(s) for <br />compliance with 150.0 0 1C. <br />Whole -Dwelling Unit Mechanical Ventilation for Single -Family Detached and townhouses . Single-family detached dwelling units. <br />§ 150.0(o)1 C. <br />and attached dwelling units not sharing ceilings or floors with other dwelling units, occupiable spaces, public garages, or commercial <br />spaces must have mechanical ventilation airflow specified in § 150.0(o)l Ci-iii. <br />§ 150.0(o)l G <br />Local Mechanical Exhaust. Kitchens and bathrooms must have local mechanical exhaust, nonenclosed kitchens must have demand - <br />controlled exhaust system meeting requirements of §150.0(o)lGiii.enclosed kitchens and bathrooms can use demand -controlled or <br />continuous exhaust meeting §150.0(o)l Giii-iv. Airflow must be measured by the installer per §150.0(o)l Gv. and rated for sound per <br />§150.0(o)1Gvi. ' <br />§ 150.0(o)l H&I: <br />Airflow Measurement and Sound Ratings of Whole -Dwelling Unit Ventilation Systems. The airflow required per § 150.0(o)1C must <br />be measured by using a flow hood, flow grid, or other airflow measuring device at the fan's inlet or outlet terminals/grilles per Reference <br />Residential Appendix RA3.7. Whole -Dwelling unit ventilation systems must be rated for sound per ASHRAE 62.2 §7.2 at no less than the <br />minimum airflow rate required by §150.0(o)1C. <br />Field Verification and Diagnostic Testing. Whole -Dwelling Unit ventilation airflow, vented range hood airflow and sound rating, <br />§ 150 0(o)2: <br />and HRV and ERV fan efficacy must be verified in accordance with Reference Residential Appendix RA3.7. Vented range hoods <br />must be verified per Reference Residential Appendix RA3.7.4.3 to confirm if it is rated b HVI or AHAM to comply with the airflow <br />P pP Y P Y <br />rates and sound requirements per §150.0(o)l G <br />Pool and Spa Systems and Equipment: I <br />Certification by Manufacturers. Any pool or spa heating system or equipment must be certified to have all of the following: compliance <br />§ 110.4(a): <br />with the Appliance Efficiency Regulations and listing in MAEDbS; an on -off switch mounted outside of the heater that allows shutting off <br />the heater without adjusting the thermostat setting, a permanent weatherproof plate or card with operating instructions, and must not <br />use electric resistance heating. " <br />Piping. Any pool or spa heating system or equipment must be installed with at least 36 inches of pipe between the filter and the heater, or <br />§ 110.4(b)l: <br />dedicated suction and return lines, or built-in or built-up connections to allow for future solar heating. <br />Covers. Outdoor pools ors as that have a heat pump or gas heater must have a cover. <br />Directional Inlets and Time Switches for Pools. Pools must have directional inlets that adequately mix the pool water, and a time <br />q Y P • <br />§ 110.4 b 3: <br />switch that will allow all pumps to be set or programmed to run only Burin off-peak electric demand periods. <br />§ 110.5: <br />Pilot Light. Natural gas pool and spa heaters must not have a continuously burning pilot light. <br />Pool Systems and Equipment Installation. Residential pool systems orequipment must meet the specified requirements for um <br />YP YP q pump <br />150.0 <br />§ (P): <br />sizing, flow rate. piping. filters. and valves. <br />Lighting: I <br />§ 150.0(k)1G: <br />Screw based luminaires. Screw based luminaires must contain lamps that comply with Reference Joint Appendix JA8.' <br />Light Sources in Enclosed or Recessed Luminaires. Lamps and other separable light sources that are not compliant with the JA8 <br />150.0 k 1H: <br />§ O <br />elevated temperature requirements. including marking requirements. must not be installed in enclosed or recessed luminaires. <br />P q 9 9 q <br />Light Sources in Drawers, Cabinets, and Linen Closets. Light sources internal to drawers, cabinetry or linen closets are not required <br />§ 150.0(k)l l: <br />to comply with Table 150.0-A or be controlled by vacancy sensors provided that they are rated to consume no more than 5 watts of <br />power, emit no more than 150 lumens, and are equipped with controls that automatically turn the lighting off when the drawer. cabinet or <br />linen closet is closed. <br />§ 150.0(k)2A: <br />Interior Switches and Controls. All forward phase cut dimmers used with LED light sources must comply with NEMA SSL 7A. <br />§ 150.0(k)2B: <br />Interior Switches and Controls. Exhaust fans must be controlled separately from lighting systems. ' <br />Accessible Controls. Lighting must have readily accessible wall -mounted controls that allow the lighting to be manually turned <br />§ 150.0(k)2A: <br />on and off.' <br />Multiple Controls. Controls must not bypass a dimmer, occupant sensor, or vacancy sensor function if the dimmer or sensor is installed <br />§ 150.0(k)2B: <br />to comply with <br />A 150.0(k). <br />§ 150.0(k)2C: <br />Mandatory Requirements. Lighting controls must comply with the applicable requirements of § 110.9. <br />Energy Management Control Systems. An energy management control system (EMCS) may be used to comply with dimming. <br />§ 150.0(k)2D: <br />occupancy. and control requirements if it provides the functionality of the specified control per § 110.9 and the physical controls specified <br />in § 150.0(k)2A. <br />Automatic Shutoff Controls. In bathrooms, garages, laundry rooms, utility rooms and walk-in closets, at least one installed lunimaire <br />§ 150.0(k)2E: <br />must be controlled by an occupancy or vacancy sensor providing automatic -off functionality. Lighting inside drawers and cabinets with <br />opaque fronts or doors must have controls that turn the light off when the drawer or door is closed. <br />Dimmers. Lighting in habitable spaces (e.g., living rooms. dining rooms. kitchens. and bedrooms) must have readily accessible wall- <br />§ 150.0(k)2F: <br />mounted dimming controls that allow the lighting to be manually adjusted up and down. Forward phase cut dimmers controlling LED ligi- <br />sources in theses aces must comply with NEMA SSL 7A. <br />§ 150.0(k)2K: <br />Independent controls. Integrated lighting of exhaust fans shall be controlled independently from the fans. Lighting under cabinets or <br />shelves, lightn in display cabinets, and switched outlets must be controlled separately from ceiling -installed lighting. _ <br />Residential Outdoor Lighting. For single-family residential buildings, outdoor lighting permanently mounted to a residential building, or to <br />150.0 k 3A: <br />§ () <br />other buildings on the same lot must have a manual on/off switch and either a photocell and motion sensor or automatic time switch <br />9 <br />control) or an astronomical time clock. An energy management control system that provides the specified control functionality and meets all <br />applicable requirements may be used to meet these requirements. <br />Internallyilluminated address signs. Internally illuminated address signs must either comply with 140.8 or consume no more than 5 <br />9 Y 9 PY § <br />§ 150.0(k)4: <br />watts of power. <br />Residential Garages for Eight or More Vehicles. Lighting for residential parking garages for eight or more vehicles must comply with the <br />§ 150.0(k)5 <br />applicable requirements for nonresidential garages in §§ 110.9. 130.0. 130.1, 130.4. 140.6. and 141.0. <br />Solar Readiness: <br />Single-family Residences. Single-family residences located in subdivisions with 10 or more single-family residences and where the <br />§ 110.10(a)1: <br />application for a tentative subdivision map for the residences has been deemed complete and approved by the enforcement agency, <br />which do not have a photovoltaic system installed. must comply with the requirements of § 110.10(b)-(e). <br />Minimum Solar Zone Area. The solar zone must have a minimum total area as described below. The solar zone must comply with <br />access, pathway. smoke ventilation. and spacing requirements as specified in Title 24, Part 9 or other parts of Title 24 or in any <br />requirements adopted by a local jurisdiction. The solar zone total area must be comprised of areas that have no dimension less than 5 <br />feet and are no less than 80 square feet each for buildings with roof areas less than or equal to 10,000 square feet or no less than 160 <br />§110.10(b)1A: <br />square feet each for buildings with roof areas greater than 10,000 square feet. For single-family residences, the solar zone must be <br />located on the roof or overhang of the building and have a total area no less than 250 square feet. ' <br />§ 110.10(b)2: <br />Azimuth_ All sections of the solar zone located on steep -sloped roofs must have an azimuth between 90-300° of true north. <br />Shading. The solar zone must not contain any obstructions, including but not limited to: vents. chimneys, architectural features. and roof <br />§ 110.10(b)3A: <br />mounted equipment. <br />Shading. Any obstruction located on the roof or any other part of the building that projects above a solar zone must be located at least twice the <br />§ 110.10(b)3B: <br />horizontal distance of the height difference between the highest point of the obstruction and the horizontal projection of the nearest point of the <br />solar zone, measured in the vertical plane.' <br />Structural Design Loads on Construction Documents. For areas of the roof designated as a solar zone, the structural design loads for <br />§ 110.10(b)4: <br />roof dead load and roof live load must be clearly indicated on the construction documents. <br />Interconnection Pathways. The construction documents must indicate: a location reserved for inverters and metering equipment and a <br />Y 9 <br />110.10 c : <br />§ O <br />pathway reserved for routing of conduit from the solar zone to the point of interconnection with the electrical service and for sin le-famil. <br />P Y 9 P 9 <br />residences and central water -heating systems, a pathway reserved for routing plumbing from the solar zone to the water -heating system,.___ <br />Documentation. A copy of the construction documents or a comparable document indicating the information from § 1 1 0. 10(b)-(c) must be <br />§ 110.10(d): <br />provided to the occupant. <br />§ 110.10(e)l: <br />Main Electrical Service Panel. The main electrical service panel must have a minimum busbar rating of 200 amps. <br />Main Electrical Service Panel. The main electrical service panel must have a reserved space to allow for the installation of a double pole <br />§ 110.10(e)2: <br />circuit breaker for a future solar electric installation. The reserved space must be permanently marked as "For Future Solar Electric." <br />Electric and Energy Storage Ready: <br />5l6/22 5/6/22 5/6/22 5/6/22 M M - 1 <br />Energy Storage System (ESS) Ready. All single-family residences must meet all of the following: Either ESS-ready interconnection <br />§ 150.0(s) <br />equipment with backed up capacity of 60 amps or more and four or more ESS supplied branch circuits. or a dedicated raceway from the <br />main service to a subpanel that supplies the branch circuits in § 150.0(s): at least four branch circuits must be identified and have their <br />source collocated at a single panelboard suitable to be supplied by the ESS, with one circuit supplying the refrigerator, one lighting circuit <br />near the primary exit, and one circuit supplying a sleeping room receptacle outlet', main panelboard must have a minimum busbar rating of <br />225 amps: sufficient space must be reserved to allow future installation of a system isolation equipmentJtransfer switch within 3' of the main <br />anelboard, with raceways installed between the panelboard and the switch location to allow the connection of backup power source. <br />Heat Pump Space Heater Ready. Systems using gas or propane furnaces to serve individual dwelling units must include: A dedicated <br />150.0 t <br />4 r Y installed i h r h i r r t l h blank er <br />unobstructed 2 OV b anch circuit wiring nsta ed within 3' of a furnace with circuit conductors rated a east 30 amps with the b an cov <br />identified as "240V ready:" and a reserved main electrical service panel space to allow for the installation of a double pole circuit breaker <br />permanently marked as "For Future 240V use.' <br />Electric Cooktop Ready. Systems using gas or propane cooktop to serve individual dwelling units must include: A dedicated unobstructed <br />§ 150.0(u) <br />240V branch circuit wiring installed within 3' of the cooktop with circuit conductors rated at least 50 amps with the blank cover identified as <br />240V ready:' and a reserved main electrical service panel space to allow for the installation of a double pole circuit breaker permanently <br />marked as "For Future 240V use.' <br />Electric Clothes Dryer Ready. Clothes dryer locations with gas or propane plumbing to serve individual dwelling units must include: A <br />§ 150.0(v) <br />dedicated unobstructed 240V branch circuit wiring installed within 3' of the dryer location with circuit conductors rated at least 30 amps with <br />the blank cover identified as "240V ready:" and a reserved main electrical service panel space to allow for the installation of a double pole <br />circuit breaker permanently marked as 'For Future 240V use." <br />J <br />I— <br />'Exceptions may apply. CD <br />(N <br />CD <br />O <br />L1J <br />D <br />0 0 <br />Q Q o <br />I�_ <br />- --+ .--, <br />C/) W CV <br />0) <br />O O Q <br />a) a) U <br />0) 0) <br />C: <br />� 73 <br />c- Q Q <br />W <br />Z Z <br />Ir- O-) M <br />LO <br />M <br />co <br />N <br />N <br />Lighting Controls and Components. All lighting control devices and systems, ballasts, and luminaires must meet the applicable <br />§ 110.9: <br />requirements of § 110.9. ' <br />§ 150.0(k)1A: <br />Luminaire Efficacy. All installed luminaires must meet the requirements in Table 150.0-A, except lighting integral to exhaust fans. kitchen <br />range hoods. bath vanity mirrors, and garage door openers; navigation lighting less than 5 watts: and lighting internal to drawers. cabinets, and linen <br />closets with an efficacy of at least 45 lumens per watt. <br />§ 150.0(k)lB: <br />Screw based luminaires. Screw based luminaires must contain lamps that comply with Reference Joint Appendix JA8.' <br />150.0 k 1C: <br />§ () <br />Recessed Downlight Luminaires in Ceilings. Luminaires recessed into ceilings must not contain screw based sockets, must be airtight, <br />and must be sealed with a gasket or caulk. California Electrical Code § 410.116 must also be met. <br />Light Sources in Enclosed or Recessed Luminaires. Lamps and other separable light sources that are not compliant with the JA8 <br />§ 150.0(k)1D: <br />elevated temperature requirements. includin marking requirements. must not be installed in enclosed or recessed luminaires. <br />§ 150.0(k)tE: <br />Blank Electrical Boxes. The number of electrical boxes that are more than five feet above the finished floor and do not contain a <br />luminaire or other device shall be no more than the number of bedrooms. These boxes must be served by a dimmer, vacancy sensor <br />control. low voltage wiring. or fan speed control. <br />Lighting Integral to Exhaust Fans. Lighting integral to exhaust fans (except when installed by the manufacturer in kitchen exhaust <br />§ 150.0(k)1F: <br />hoods) must meet the applicable requirements of § 150.0(k).' <br />