Laserfiche WebLink
Docusign Envelope ID: 244D77F2-FOA2-4894-B44B-1CO03F256B68 <br />ELECTRICAL <br />PART 1: GENERAL <br />2.2 MATERIALS AND EQUIPMENT: <br />1.1 GENERAL CONDITIONS: <br />A. THE CONTRACTOR SHALL INSPECT THE SITE WHERE THIS WORK IS TO BE <br />A. CONDUIT: <br />PERFORMED AND FULLY FAMILIARIZE HIMSELF WITH ALL CONDITIONS RELATED TO <br />THIS PROJECT. <br />1. RIGID GALVANIZED STEEL CONDUIT (RGS) SHALL BE HOT -DIP GALVANIZED <br />INSIDE AND OUTSIDE INCLUDING ENDS AND THREADS AND ENAMELED OR <br />B. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS AND LICENSES AND <br />LACQUERED INSIDE IN ADDITION TO GALVANIZING. <br />SHALL MAKE ALL DEPOSITS AND PAY ALL FEES REQUIRED FOR THE PERFORMANCE <br />OF WORK UNDER THIS SECTION. <br />2. FLEXIBLE METAL CONDUIT SHALL BE GALVANIZED, ZINC -COATED STEEL, PVC <br />COATED FOR OUTDOOR APPLICATIONS. <br />C. DRAWINGS SHOW THE GENERAL ARRANGEMENT OF ALL SYSTEMS AND COMPONENTS <br />COVERED UNDER THIS SECTION. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS. <br />3. CONDUIT CLAMPS, STRAPS AND SUPPORTS SHALL BE STEEL OR MALLEABLE <br />DRAWINGS SHALL NOT BE SCALED TO DETERMINE DIMENSIONS. <br />IRON. ALL FITTINGS SHALL BE COMPRESSION TYPE AND WATERTIGHT. <br />1.2 LAWS. REGULATIONS, ORDINANCES. STATUTES AND CODES: <br />4. NON-METALLIC CONDUIT AND FITTINGS SHALL BE SCHEDULE 40 PVC, <br />HEAVY -WALL RIGID WITH SOLVENT -CEMENT -TYPE JOINTS AS RECOMMENDED BY <br />A. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL <br />THE MANUFACTURER. <br />CODE, AND ALL APPLICABLE LOCAL LAWS, REGULATIONS, ORDINANCES, STATUTES <br />AND CODES. <br />B. WIRE AND CABLE: <br />1.3 REFERENCES: <br />1. WIRE AND CABLE SHALL BE FLAME-RETARDANT, MOISTURE AND HEAT <br />RESISTANT THERMOPLASTIC, SINGLE CONDUCTOR, COPPER, TYPE <br />A. THE PUBLICATIONS LISTED BELOW FORM PART OF THIS SPECIFICATION. EACH <br />THHN/THWN-2, 600 VOLT, SIZES AS INDICATED, #12 AWG MINIMUM. <br />PUBLICATION SHALL BE THE LATEST REVISION AND ADDENDUM IN EFFECT ON THE <br />DATE THIS SPECIFICATION IS ISSUED FOR CONSTRUCTION UNLESS NOTED <br />2. #10 AWG AND SMALLER CONDUCTORS SHALL BE SOLID AND #8 AWG AND <br />OTHERWISE. EXCEPT AS MODIFIED BY THE REQUIREMENTS SPECIFIED HEREIN OR <br />LARGER CONDUCTORS SHALL BE STRANDED. <br />THE DETAILS OF THE DRAWINGS, WORK INCLUDED IN THIS SPECIFICATION SHALL <br />CONFORM TO THE APPLICABLE PROVISIONS OF THESE PUBLICATIONS. <br />3. SOLDERLESS, PRESSURE -TYPE CONNECTORS CONSTRUCTED OF <br />HIGH -STRENGTH, NON -CORRODIBLE, TIN-PLATED COPPER DESIGNED TO <br />1. NEC (NATIONAL ELECTRICAL CODE) <br />FURNISH HIGH -PULLOUT STRENGTH AND HIGH CONDUCTIVITY JOINTS SHALL BE <br />USED. <br />2. ANSI/IEEE (AMERICAN NATIONAL STANDARDS INSTITUTE) <br />4. SUPPORT GRIPS SHALL BE SINGLE WEAVE, CLOSED MESH, HIGH-GRADE, NON- <br />3. IEEE (INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS) <br />MAGNETIC, TIN -COATED BRONZE CAPABLE OF SUPPORTING TEN TIMES THE <br />CABLE DEAD WEIGHT, HUBBELL KELLEMS OR APPROVED EQUAL. <br />4. ASTM (AMERICAN SOCIETY FOR TESTING AND MATERIALS) <br />C. DISCONNECT SWITCHES: <br />5. ICEA (INSULATED CABLE ENGINEERS ASSOCIATION) <br />1. DISCONNECT SWITCHES SHALL BE HEAVY DUTY, DEAD -FRONT, QUICK -MAKE, <br />6. NEMA (NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION) <br />QUICK -BREAK, EXTERNALLY OPERABLE, HANDLE LOCKABLE AND INTERLOCKED <br />WITH COVER IN CLOSED POSITION, RATING AS INDICATED, UL LABELED <br />7. NFPA NATIONAL FIRE PROTECTION ASSOCIATION) <br />( ) <br />FURNISHED IN NEMA 3R ENCLOSURE, SQUARE D CLASS 3110 OR APPROVED <br />EQUAL. <br />8. OSHA (OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION) <br />D. SYSTEM GROUNDING: <br />9. UL (UNDERWRITERS LABORATORIES, INC.) <br />1. GROUNDING CONDUCTOR SHALL BE SOLID TINNED BARE COPPER, SIZE AS <br />INDICATED, EXCEPT ABOVE GROUND GROUNDING CONDUCTORS SHALL BE <br />1.4 SCOPE OF WORK: <br />STRANDED INSULATED. <br />A. WORK UNDER THIS SECTION SHALL CONSIST OF FURNISHING ALL LABOR, MATERIAL <br />2. GROUND BUSSES SHALL BE GALVANIZED STEEL BARS OF RECTANGULAR CROSS <br />AND ASSOCIATED SERVICES REQUIRED TO COMPLETELY CONSTRUCT AND LEAVE <br />SECTION. <br />READY FOR OPERATION SYSTEMS AS SHOWN ON THE DRAWINGS AND HEREIN <br />DESCRIBED. <br />3. CONNECTORS SHALL BE HIGH -CONDUCTIVITY, HEAVY DUTY, LISTED AND <br />LABELED AS GROUNDING CONNECTORS FOR THE MATERIALS USED. USE <br />B. ALL ELECTRICAL EQUIPMENT UNDER THIS CONTRACT SHALL BE PROPERLY TESTED, <br />TWO -HOLE COMPRESSION LUGS WITH HEAT SHRINK FOR MECHANICAL <br />ADJUSTED, AND ALIGNED BY THE CONTRACTOR. <br />CONNECTIONS, <br />C. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL EXCAVATING, DRAINING, <br />4. EXOTHERMIC WELDED CONNECTIONS SHALL BE PROVIDED IN KIT FORM AND <br />TRENCHES, BACKFILLING, AND REMOVAL OF EXCESS DIRT. <br />SELECTED FOR THE SPECIFIC TYPES, SIZES, AND COMBINATIONS OF <br />CONDUCTORS AND OTHER ITEMS TO BE CONNECTED. <br />D. THE CONTRACTOR SHALL FURNISH TO THE OWNER, CERTIFICATES OF FINAL <br />INSPECTION AND APPROVAL FROM THE INSPECTION AUTHORITIES HAVING <br />5. GROUND RODS SHALL BE COPPER -CLAD STEEL WITH HIGH -STRENGTH STEEL <br />JURISDICTION. <br />CORE AND ELECTROLYTIC -GRADE COPPER OUTER SHEATH, MOLTEN WELDED TO <br />CORE, 3/4" x 10'-0". <br />PART 2: PRODUCTS <br />2.1 GENERAL <br />E. OTHER MATERIALS: <br />1. THE CONTRACTOR SHALL PROVIDE OTHER MATERIALS, THOUGH NOT <br />A. ALL ITEMS OF MATERIALS AND EQUIPMENT SHALL BE NEW, FREE FROM DEFECTS <br />SPECIFICALLY DESCRIBED, WHICH ARE REQUIRED FOR A COMPLETELY <br />AND OF THE BEST QUALITY NORMALLY USED FOR THE PURPOSE IN GOOD <br />OPERATIONAL SYSTEM AND PROPER INSTALLATION OF THE WORK. <br />COMMERCIAL PRACTICE. <br />B. ALL MATERIALS AND EQUIPMENT SHALL BE ACCEPTABLE TO THE AUTHORITY HAVING <br />JURISDICTION AS SUITABLE FOR THE USE INTENDED. <br />C. ALL EQUIPMENT SHALL BEAR THE UNDERWRITERS LABORATORIES LABEL OF <br />APPROVAL, AND SHALL CONFORM TO REQUIREMENTS OF THE NATIONAL ELECTRICAL <br />CODE. <br />D. ALL OVERCURRENT DEVICES SHALL HAVE AN INTERRUPTING RATING EQUAL TO OR <br />GREATER THAN THE SHORT CIRCUIT CURRENT TO WHICH THEY ARE SUBJECTED, <br />10,000 AIC MINIMUM. VERIFY AVAILABLE SHORT CIRCUIT CURRENT DOES NOT <br />EXCEED THE RATING OF ELECTRICAL EQUIPMENT. <br />a i riv <br />r: <br />Planning and Building Age <br />11 /10/2025 <br />Q FS d <br />Sff PAN TVsI AN <br />KEISLING <br />_ m <br />J 24647 <br />as erID: <br />D TEL/�ECT I AL <br />2 �Q <br />Docu Signry/bytJF <br />S0bla,t LS�In� <br />EF94D8A5B80B407 <br />ENGINEERING LICENSE: <br />STATE OF CALIFORNIA <br />ENGINEER: PE#: DISCIPLINE: <br />SDK SHELTON D. KEISLING 24647 ELECTRICAL E <br />DJW DAVID J WALDRON 25608 ELECTR CAL E <br />TMS TERRANCE M. SUPER 17150 ELECTRICAL E <br />rjeanHarbo!5 <br />PLANS PREPARED FOR: <br />AGI 1 <br />PLANS PREPARED BY: <br />��. <br />SSC <br />DRAWING NOTICE: <br />THIS DRAWING HAS NOT BEEN PUBLISHED AND IS THE SOLE <br />PROPERTY OF SSC, INC_ AND IS LENT TO THE BORROWER FOR <br />THEIR CONFIDENTIAL USE ONLY, AND IN CONSIDERATION OF <br />THE LOAN OF THIS DRAWING, THE BORROWER PROMISES AND <br />AGREES TO RETURN IT UPON REQUEST AND AGREES THAT IT <br />WILL NOT BE REPRODUCED, COPIED, LENT OR OTHERWISE <br />DISPOSED OF DIRECTLY OR INDIRECTLY, NCR USED FOR ANY <br />PURPOSE OTHER THAN FOR WHICH IT IS FURNISHED. <br />SUBMITTALS: <br />DESCRIPTION <br />DATE <br />BY <br />REV <br />ISSUED FOR REVIEW <br />11/22/24 <br />ART <br />0 <br />REVISED PER CLIENT COMMENTS <br />12/13/24 <br />ART <br />1 <br />REVISED PER CLIENT COMMENTS <br />01/28/25 <br />DWO <br />2 <br />REVISED PER CLIENT COMMENTS <br />09/05/25 <br />TJM <br />3 <br />REVISED PER AHJ COMMENTS <br />11/07/25 <br />EDA <br />4 <br />APPLICANT SITE NAME: <br />CLEAN HARBORS (SANTA ANA) <br />APPLICANT SITE NUMBER: <br />AGI-EV-0006 <br />SITE ADDRESS. <br />2120 S YALE STREET <br />SANTA ANA, CA 92704 <br />SHEET DESCRIPTION: <br />SHEET#: <br />SPECIFICATIONS <br />SP-2 0 <br />(4 OF 5) <br />