<br />ELECTRICAL
<br />PART 1: GENERAL
<br />2.2 MATERIALS AND EQUIPMENT:
<br />1.1 GENERAL CONDITIONS:
<br />A. THE CONTRACTOR SHALL INSPECT THE SITE WHERE THIS WORK IS TO BE
<br />A. CONDUIT:
<br />PERFORMED AND FULLY FAMILIARIZE HIMSELF WITH ALL CONDITIONS RELATED TO
<br />THIS PROJECT.
<br />1. RIGID GALVANIZED STEEL CONDUIT (RGS) SHALL BE HOT -DIP GALVANIZED
<br />INSIDE AND OUTSIDE INCLUDING ENDS AND THREADS AND ENAMELED OR
<br />B. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS AND LICENSES AND
<br />LACQUERED INSIDE IN ADDITION TO GALVANIZING.
<br />SHALL MAKE ALL DEPOSITS AND PAY ALL FEES REQUIRED FOR THE PERFORMANCE
<br />OF WORK UNDER THIS SECTION.
<br />2. FLEXIBLE METAL CONDUIT SHALL BE GALVANIZED, ZINC -COATED STEEL, PVC
<br />COATED FOR OUTDOOR APPLICATIONS.
<br />C. DRAWINGS SHOW THE GENERAL ARRANGEMENT OF ALL SYSTEMS AND COMPONENTS
<br />COVERED UNDER THIS SECTION. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS.
<br />3. CONDUIT CLAMPS, STRAPS AND SUPPORTS SHALL BE STEEL OR MALLEABLE
<br />DRAWINGS SHALL NOT BE SCALED TO DETERMINE DIMENSIONS.
<br />IRON. ALL FITTINGS SHALL BE COMPRESSION TYPE AND WATERTIGHT.
<br />1.2 LAWS. REGULATIONS, ORDINANCES. STATUTES AND CODES:
<br />4. NON-METALLIC CONDUIT AND FITTINGS SHALL BE SCHEDULE 40 PVC,
<br />HEAVY -WALL RIGID WITH SOLVENT -CEMENT -TYPE JOINTS AS RECOMMENDED BY
<br />A. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL
<br />THE MANUFACTURER.
<br />CODE, AND ALL APPLICABLE LOCAL LAWS, REGULATIONS, ORDINANCES, STATUTES
<br />AND CODES.
<br />B. WIRE AND CABLE:
<br />1.3 REFERENCES:
<br />1. WIRE AND CABLE SHALL BE FLAME-RETARDANT, MOISTURE AND HEAT
<br />RESISTANT THERMOPLASTIC, SINGLE CONDUCTOR, COPPER, TYPE
<br />A. THE PUBLICATIONS LISTED BELOW FORM PART OF THIS SPECIFICATION. EACH
<br />THHN/THWN-2, 600 VOLT, SIZES AS INDICATED, #12 AWG MINIMUM.
<br />PUBLICATION SHALL BE THE LATEST REVISION AND ADDENDUM IN EFFECT ON THE
<br />DATE THIS SPECIFICATION IS ISSUED FOR CONSTRUCTION UNLESS NOTED
<br />2. #10 AWG AND SMALLER CONDUCTORS SHALL BE SOLID AND #8 AWG AND
<br />OTHERWISE. EXCEPT AS MODIFIED BY THE REQUIREMENTS SPECIFIED HEREIN OR
<br />LARGER CONDUCTORS SHALL BE STRANDED.
<br />THE DETAILS OF THE DRAWINGS, WORK INCLUDED IN THIS SPECIFICATION SHALL
<br />CONFORM TO THE APPLICABLE PROVISIONS OF THESE PUBLICATIONS.
<br />3. SOLDERLESS, PRESSURE -TYPE CONNECTORS CONSTRUCTED OF
<br />HIGH -STRENGTH, NON -CORRODIBLE, TIN-PLATED COPPER DESIGNED TO
<br />1. NEC (NATIONAL ELECTRICAL CODE)
<br />FURNISH HIGH -PULLOUT STRENGTH AND HIGH CONDUCTIVITY JOINTS SHALL BE
<br />USED.
<br />2. ANSI/IEEE (AMERICAN NATIONAL STANDARDS INSTITUTE)
<br />4. SUPPORT GRIPS SHALL BE SINGLE WEAVE, CLOSED MESH, HIGH-GRADE, NON-
<br />3. IEEE (INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS)
<br />MAGNETIC, TIN -COATED BRONZE CAPABLE OF SUPPORTING TEN TIMES THE
<br />CABLE DEAD WEIGHT, HUBBELL KELLEMS OR APPROVED EQUAL.
<br />4. ASTM (AMERICAN SOCIETY FOR TESTING AND MATERIALS)
<br />C. DISCONNECT SWITCHES:
<br />5. ICEA (INSULATED CABLE ENGINEERS ASSOCIATION)
<br />1. DISCONNECT SWITCHES SHALL BE HEAVY DUTY, DEAD -FRONT, QUICK -MAKE,
<br />6. NEMA (NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION)
<br />QUICK -BREAK, EXTERNALLY OPERABLE, HANDLE LOCKABLE AND INTERLOCKED
<br />WITH COVER IN CLOSED POSITION, RATING AS INDICATED, UL LABELED
<br />7. NFPA NATIONAL FIRE PROTECTION ASSOCIATION)
<br />( )
<br />FURNISHED IN NEMA 3R ENCLOSURE, SQUARE D CLASS 3110 OR APPROVED
<br />EQUAL.
<br />8. OSHA (OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION)
<br />D. SYSTEM GROUNDING:
<br />9. UL (UNDERWRITERS LABORATORIES, INC.)
<br />1. GROUNDING CONDUCTOR SHALL BE SOLID TINNED BARE COPPER, SIZE AS
<br />INDICATED, EXCEPT ABOVE GROUND GROUNDING CONDUCTORS SHALL BE
<br />1.4 SCOPE OF WORK:
<br />STRANDED INSULATED.
<br />A. WORK UNDER THIS SECTION SHALL CONSIST OF FURNISHING ALL LABOR, MATERIAL
<br />2. GROUND BUSSES SHALL BE GALVANIZED STEEL BARS OF RECTANGULAR CROSS
<br />AND ASSOCIATED SERVICES REQUIRED TO COMPLETELY CONSTRUCT AND LEAVE
<br />SECTION.
<br />READY FOR OPERATION SYSTEMS AS SHOWN ON THE DRAWINGS AND HEREIN
<br />DESCRIBED.
<br />3. CONNECTORS SHALL BE HIGH -CONDUCTIVITY, HEAVY DUTY, LISTED AND
<br />LABELED AS GROUNDING CONNECTORS FOR THE MATERIALS USED. USE
<br />B. ALL ELECTRICAL EQUIPMENT UNDER THIS CONTRACT SHALL BE PROPERLY TESTED,
<br />TWO -HOLE COMPRESSION LUGS WITH HEAT SHRINK FOR MECHANICAL
<br />ADJUSTED, AND ALIGNED BY THE CONTRACTOR.
<br />CONNECTIONS,
<br />C. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL EXCAVATING, DRAINING,
<br />4. EXOTHERMIC WELDED CONNECTIONS SHALL BE PROVIDED IN KIT FORM AND
<br />TRENCHES, BACKFILLING, AND REMOVAL OF EXCESS DIRT.
<br />SELECTED FOR THE SPECIFIC TYPES, SIZES, AND COMBINATIONS OF
<br />CONDUCTORS AND OTHER ITEMS TO BE CONNECTED.
<br />D. THE CONTRACTOR SHALL FURNISH TO THE OWNER, CERTIFICATES OF FINAL
<br />INSPECTION AND APPROVAL FROM THE INSPECTION AUTHORITIES HAVING
<br />5. GROUND RODS SHALL BE COPPER -CLAD STEEL WITH HIGH -STRENGTH STEEL
<br />JURISDICTION.
<br />CORE AND ELECTROLYTIC -GRADE COPPER OUTER SHEATH, MOLTEN WELDED TO
<br />CORE, 3/4" x 10'-0".
<br />PART 2: PRODUCTS
<br />2.1 GENERAL
<br />E. OTHER MATERIALS:
<br />1. THE CONTRACTOR SHALL PROVIDE OTHER MATERIALS, THOUGH NOT
<br />A. ALL ITEMS OF MATERIALS AND EQUIPMENT SHALL BE NEW, FREE FROM DEFECTS
<br />SPECIFICALLY DESCRIBED, WHICH ARE REQUIRED FOR A COMPLETELY
<br />AND OF THE BEST QUALITY NORMALLY USED FOR THE PURPOSE IN GOOD
<br />OPERATIONAL SYSTEM AND PROPER INSTALLATION OF THE WORK.
<br />COMMERCIAL PRACTICE.
<br />B. ALL MATERIALS AND EQUIPMENT SHALL BE ACCEPTABLE TO THE AUTHORITY HAVING
<br />JURISDICTION AS SUITABLE FOR THE USE INTENDED.
<br />C. ALL EQUIPMENT SHALL BEAR THE UNDERWRITERS LABORATORIES LABEL OF
<br />APPROVAL, AND SHALL CONFORM TO REQUIREMENTS OF THE NATIONAL ELECTRICAL
<br />CODE.
<br />D. ALL OVERCURRENT DEVICES SHALL HAVE AN INTERRUPTING RATING EQUAL TO OR
<br />GREATER THAN THE SHORT CIRCUIT CURRENT TO WHICH THEY ARE SUBJECTED,
<br />10,000 AIC MINIMUM. VERIFY AVAILABLE SHORT CIRCUIT CURRENT DOES NOT
<br />EXCEED THE RATING OF ELECTRICAL EQUIPMENT.
<br />a i riv
<br />r:
<br />Planning and Building Age
<br />11 /10/2025
<br />Q FS d
<br />Sff PAN TVsI AN
<br />KEISLING
<br />_ m
<br />J 24647
<br />as erID:
<br />D TEL/�ECT I AL
<br />2 �Q
<br />Docu Signry/bytJF
<br />S0bla,t LS�In�
<br />EF94D8A5B80B407
<br />ENGINEERING LICENSE:
<br />STATE OF CALIFORNIA
<br />ENGINEER: PE#: DISCIPLINE:
<br />SDK SHELTON D. KEISLING 24647 ELECTRICAL E
<br />DJW DAVID J WALDRON 25608 ELECTR CAL E
<br />TMS TERRANCE M. SUPER 17150 ELECTRICAL E
<br />rjeanHarbo!5
<br />PLANS PREPARED FOR:
<br />AGI 1
<br />PLANS PREPARED BY:
<br />��.
<br />SSC
<br />DRAWING NOTICE:
<br />THIS DRAWING HAS NOT BEEN PUBLISHED AND IS THE SOLE
<br />PROPERTY OF SSC, INC_ AND IS LENT TO THE BORROWER FOR
<br />THEIR CONFIDENTIAL USE ONLY, AND IN CONSIDERATION OF
<br />THE LOAN OF THIS DRAWING, THE BORROWER PROMISES AND
<br />AGREES TO RETURN IT UPON REQUEST AND AGREES THAT IT
<br />WILL NOT BE REPRODUCED, COPIED, LENT OR OTHERWISE
<br />DISPOSED OF DIRECTLY OR INDIRECTLY, NCR USED FOR ANY
<br />PURPOSE OTHER THAN FOR WHICH IT IS FURNISHED.
<br />SUBMITTALS:
<br />DESCRIPTION
<br />DATE
<br />BY
<br />REV
<br />ISSUED FOR REVIEW
<br />11/22/24
<br />ART
<br />0
<br />REVISED PER CLIENT COMMENTS
<br />12/13/24
<br />ART
<br />1
<br />REVISED PER CLIENT COMMENTS
<br />01/28/25
<br />DWO
<br />2
<br />REVISED PER CLIENT COMMENTS
<br />09/05/25
<br />TJM
<br />3
<br />REVISED PER AHJ COMMENTS
<br />11/07/25
<br />EDA
<br />4
<br />APPLICANT SITE NAME:
<br />CLEAN HARBORS (SANTA ANA)
<br />APPLICANT SITE NUMBER:
<br />AGI-EV-0006
<br />SITE ADDRESS.
<br />2120 S YALE STREET
<br />SANTA ANA, CA 92704
<br />SHEET DESCRIPTION:
<br />SHEET#:
<br />SPECIFICATIONS
<br />SP-2 0