ESR-3699 Page 3 of 18 <br /> <br /> <br />4.1.2 Requirements for Static Steel Strength in Tension, Nsa: The nominal static steel strength of a single <br />anchor in tension is calculated in accordance with ACI 318-19 17.6.1.2, ACI 318-14 17.4.1.2 or ACI 318-11 <br />D.5.1.2, as applicable. The Nsa values of a single anchor are given in Table 2 of this report. Strength reduction <br />factors, ïĶ, corresponding to brittle steel elements as defined in ACI 318 (-19 or -14) 2.3 or ACI 318-11 D.1, as <br />applicable, and provided in Table 2, must be used. <br />4.1.3 Requirements for Static Concrete Breakout Strength in Tension, Ncb or Ncbg: The nominal static <br />concrete breakout strength for a single anchor or group of anchors in tension, Ncb or Ncbg, must be calculated in <br />accordance with ACI 318-19 17.6.2, ACI 318-14 17.4.2 or ACI 318-11 D.5.2, as applicable, with modifications as <br />described in this section. The basic concrete breakout strength in tension, Nb, must be calculated in accordance <br />with ACI 318-19 17.6.2.2, ACI 318-14 17.4.2.2 or ACI 318-11 D.5.2.2, as applicable, using the values of hef and <br />kcr as given in Table 2. The nominal concrete breakout strength in tension in regions of concrete where analysis <br />indicates no cracking at service loads in accordance with ACI 318-19 17.6.2.5, ACI 318-14 17.4.2.6 or ACI 318- <br />11 D.5.2.6, as applicable, must be calculated using the values of kuncr as given in Table 2 of this report with ψc,N <br />= 1.0. <br />For 1/2-inch-diameter (12.7 mm) Tapcon+ Screw Anchors installed in the soffit of sand-lightweight or <br />normalweight concrete on steel deck floor and roof assemblies, as shown in Figure 6, calculation of the concrete <br />breakout strength is not required. <br />4.1.4 Requirements for Static Pullout Strength in Tension, Np: The nominal pullout strength of a single <br />anchor in tension in accordance with ACI 318-19 17.6.3.1 and 17.6.3.2.1, ACI 318-14 17.4.3.1 and 17.4.3.2 or <br />ACI 318-11 D.5.3.1 and D.5.3.2, as applicable, in cracked and uncracked concrete, Np,cr and Np,uncr, <br />respectively, is given in Table 2 of this report. For all design cases ð›đ𝑐,𝑃=1.0. In accordance with ACI 318-19 <br />17.6.3, ACI 318-14 17.4.3 or ACI 318-11 D.5.3, as applicable, the nominal pullout strength in cracked concrete <br />may be adjusted for concrete strengths according to Eq-1: <br />𝑁𝑝,𝑓𝑐â€ē=𝑁𝑝,𝑐𝑟(𝑓𝑐â€ē <br />2,500) <br />𝑛 (lb,psi) (Eq-1) <br />𝑁𝑝,𝑓𝑐â€ē=𝑁𝑝,𝑐𝑟(𝑓𝑐â€ē <br />17.2) <br />𝑛 (N, MPa) <br />where fâ€ēc is the specified compressive strength and n is the factor defining the influence of concrete strength <br />on the pullout strength. For the 3/8-inch-diameter anchor in cracked concrete, n is 0.12. For all other diameters, <br />n is 0.5. <br />In regions where analysis indicates no cracking in accordance with ACI 318-19 17.6.3.3, ACI 318-14 17.4.3.6 <br />or ACI 318-11 D.5.3.6, as applicable, the nominal pullout strength in tension may be adjusted for concrete <br />strengths according to Eq-2: <br />𝑁𝑝,𝑓𝑐â€ē=𝑁𝑝,ð‘Ē𝑛𝑐𝑟(𝑓𝑐â€ē <br />2,500) <br />𝑛 (lb,psi) (Eq-2) <br /> 𝑁𝑝,𝑓𝑐â€ē=𝑁𝑝,ð‘Ē𝑛𝑐𝑟(𝑓𝑐â€ē <br />17.2) <br />𝑛 (N, MPa) <br />where fâ€ēc is the specified compressive strength and n is the factor defining the influence of concrete strength <br />on the pullout strength. For all diameters, n is 0.5. <br />Where values for Np,cr or Np,uncr are not provided in Table 2, the pullout strength in tension need not be <br />evaluated. <br />The nominal pullout strength in cracked concrete of the 1/2-inch-diameter (12.7 mm) Tapcon+ Screw Anchor <br />installed in the soffit of sand-lightweight or normalweight concrete on steel deck floor and roof assemblies, as <br />shown in Figure 6, is given in Table 5. In accordance with ACI 318-19 17.6.3.2.1, ACI 318-14 17.4.3.2 or ACI <br />318-11 D.5.3.2, as applicable, the nominal pullout strength in cracked concrete must be calculated in <br />accordance with Eq-1, whereby the value of Np,deck,cr must be substituted for Np,cr and the value of 3,000 psi <br />(20.7 MPa) must be substituted for the value of 2,500 psi (17.2 MPa) in the denominator. In regions where <br />analysis indicates no cracking in accordance with ACI 318-19 17.6.3.3, ACI 318-17.4.3.6 or ACI 318-11 <br />D.5.3.6, as applicable, the nominal strength in uncracked concrete must be calculated according to Eq-2, <br />whereby the value of Np,deck,uncr must be substituted for Np,uncr and the value of 3,000 psi (20.7 MPa) must be <br />substituted for the value of 2,500 psi (17.2 MPa) in the denominator. <br />