Customer S&H Systems <br />Project Collectors.com <br />Job Number 10010 <br />2 TYPICAL SEISMIC Page 2.2 <br />Structure: <br />Project Address - <br />Design Code Site Class D <br />Seismic Design Data <br />Period for Site Class D Seismic Design Cat <br />4 SS = 1.272 g Fa = 1.20 SMS = 1.527 SDS = 1.019 g D Table 11.6-1 <br />4 S1 = 0.455 g Fv = 1.55 SM1 = 0.705 SD1 = 0.470 g D Table 11.6-2 <br />Approximate Fundamental Period <br />Top of platform, h =4.0 Ft Number of stories, N =1 Section 12.8.2.1 <br />TL = 8 ASCE 7-10 pg 171 Ta = Ct*hx 0.085 Sec Equation 12.8-7 <br />Ct = 0.028 Table 12.8-2 Ta = 0.1*N = 0.100 Sec Equation 12.8-8 <br />x = 0.80 Table 12.8-2 Ts = SD1 / SDS 0.461 T = NA Input from STAAD or NA <br />Cu = 1.40 Ta = 0.085 Tu = Cu*Ta 0.119 T = 0.085 <br />Seismic Design Category <br />Risk Category II Ie = 1.00 <br />Table 12.8-1 <br />Section 12.3 <br />No Section 11.6.4 <br />No Section 11.6.4 <br />Seismic Design Category D Reduced SDS per ASCE 7-16 Section 12.8.1.3 <br />Redundance Factor ρ 1.30 Section 12.3.4.2 Are all 6 criteria met No SDS = 1.019 <br />Structural System Selection for R values <br />2.5 <br />AOS-CC R = 1.25 Ωo = 2 Cd = 2.5 Table 15.4-2 <br />Detailed per AISC 360 <br />Limitations <br />Structure Type Non Building Structure NOT Similar to Buildings Ωo Elev=2.00 Table 12.2-1 note g <br />Equivalent Lateral Force Procedure Ωobase =2.00 AISC 341 sect 1.3 <br />Cs = 0.01 If seismic Category A 0.010 *D Section 11.7, 1.4 <br />Cs = SDS / (R / I ) = 1.019/(1.25/1) 0.815 *D Equation 12.8-2 <br />Cs <= SD1 / ( T * ( R / I )) for T <= TL = 0.47/(0.085*(1.25/1)) 4.424 *D Equation 12.8-3 <br />Cs <= SD1 * TL / ( T2 * ( R / I )) for T > TL = 0.47*8/(0.085^2/(1.25/1)) NA *D Equation 12.8-4 <br />Cs >= MAX (0.044*SDS*Ie, 0.03) 0.045 *D Equation 15.4-1 <br />Cs >= 0.8*S1 / (R / I ) for Non Buildings and S1 >0.60 NA *D Equation 15.4-2 <br />Cs = 0.815 *D <br />Base Shear <br />V = Cs*W 0.815 *W <br />Member Design Qe = V or Fp <br />Eh = ρ *Qe = ρ*Cs * W = 1.3*0.815*D 1.060 *W Section 12.4.2.1 <br />Ev = 0.2*SDS*W = 0.2*1.019*D 0.204 *W Section12.4.2.2 <br />ΩoEh = Min (Ωo *Eh / ρ , Cs*R / I)=2*1.0595 / 1.3 1.630 *W Only for SDC B to F <br />Steele <br />Solutions Inc. <br />Moment connection overstrength non req'd in SDC A-C <br />In Seismic Cat. D, E, F Height <= 50 Ft. <br />All other Self- supporting structures not covered, NS to buildings For Cant col <br />Per AISC 341-10 Sec C-E1.6b, Limit seismic forces based on Limiting earthquake force R=1 Which is the Design Earthquake Ground Motion = <br />Cs*R / I, which equals SDS for T< 1 sec <br />Are the diaphragms are rigid as defined in section 12.3.1 <br />Does the distance between vertical elements of the seismic force resisting <br />system exceed 40Ft? (Column side connections, Knee braces, or Braced <br />frames) <br />1610 E St. Andrews Pl, Santa Ana, CA 92705 <br />ASCE 7-16 <br />PLT1 <br />6737 W. Washington St. West Allis, WI 53214