Laserfiche WebLink
CITY OF SANTA ANA <br />39- <br />......................................% ............ <br />:EXAMPLE LOCATION OF 2X8: <br />REINFORCEMENT o <br />FOR FUTURE GRAB BARS <br />L..................... ................ N <br />.4 ............................. <br />WATER CLOSET ADJACENT TO ONE SIDE WALL <br />AND A BACK WALL <br />SIDE WALL <br />BACK WALL <br />39-1/4" <br />32" <br />SHOWER ENCLOSURE <br />EXTERIOR <br />DOORBELL HEIGHT IS FROM <br />FLOOR OR LANDING TO TOP OF <br />DOORBELL ASSEMBLY <br />48" MAX. <br />r_ <br />INTERIOR <br />HEIGHTS ARE TO FINISH FLOOR <br />0 <br />0 <br />'MIN. <br />BOTTOM OF OUTLET BOX <br />AGING -IN -PLACE DESIGN AND FALL <br />PREVENTION REQUIREMENTS CRC R327 <br />54" MIN. ...... ........................ -........... 36" MIN. <br />See Note #6 : '•••* SUGGESTED <br />SUGGESTED :......... .................. <br />339-1 /4" <br />9-1 /4" <br />32" <br />SIDE WALL <br />CONTROLS SIDE <br />1/4 <br />IF <br />BACK WALL <br />HEAD END <br />32" <br />LAV. <br />L . . . . . . . . . <br />.....r...,�... <br />�y <br />D11 <br />�.................... r....... ............ ............% <br />EXAMPLE LOCATION OF <br />_ <br />�j 2X8 REINFORCEMENT <br />;.FOR FUTURE GRAB..........................BARS........• <br />WATER CLOSET ADJACENT <br />TO TWO SIDE WALLS <br />BACK WALL <br />9-t/4 <br />N WE- \1 <br />"ON <br />T32" <br />HE <br />... "" BATHTUB OR TUB/SHOWER <br />CONTROLS END <br />NOTES: <br />See Exception 4 1 1. <br />Reinforcement must be located between the dimensions specified. <br />'••••"""......•"""""'•..... 2. <br />Reinforcement must be continuous in bathtub, bathtub combo and shower wall enclosures, where wall <br />framing is provided. <br />3. <br />Reinforcement may be solid lumber or other construction materials that provide equal height and load <br />capacity. <br />4. <br />The location of the reinforcement must be incorporated in the Operation and Maintenance Manual (e.g., <br />floor plan and elevation details) required by CAL Green Section 4.410.1. <br />48" MAX. TO TOP OF OUTLET BOX 5. <br />Additional back wall reinforcement must be installed with the bottom edge no more than 6-inches above the <br />bathtub rim. <br />6. <br />The suggested dimensions are to accommodate the minimum required 36-inches clearance center to <br />gg q <br />center, at a water closet; and minimum 24-inches clear space in front of water closet (CPC 402.5). At this time <br />CRC R327 does not specify the minimum lengths at these locations. However, please consult with the local <br />jurisdiction. <br />EXCEPTIONS: <br />1. <br />Reinforcement for future floor -mounted, foldaway or similar alternate grab bar may be installed with prior <br />approvals from the enforcing agency. <br />2. <br />Wall reinforcement is not required where pre -fabricated shower & bathtub panels that have integral factory - <br />installed grab bars, or when factory -installed reinforcement for grab bars is provided. <br />3. <br />Reinforcement of floor is not required for bathtubs and water closets installed on concrete floors. <br />NJ <br />4. <br />Dedicated receptacle outlets; floor receptacle outlets; controls mounted on ceiling fans and ceiling lights and <br />HEIGHTS FOR ELECTRICAL RECEPTACLE OUTLETS, SWITCHES, controls located on appliances; and required receptacles on a wall space that has a built-in feature above <br />DOORBELL BUTTONS, INCLUDING HVAC CONTROLS finish floor less than 15-inches. <br />EFFECTIVE JULY, 2024 AT LEAST ONE BATHROOM AND ONE BEDROOM ON THE ENTRY LEVEL MUST PROVIDE A DOORWAY WITH A NET CLEAR OPENING OF NOT LESS <br />THAN 32-INCHES MEASURED WITH THE DOOR POSITIONED AT AN 90 DEGREE ANGLE. IN A 2- OR 3- STORYSFD, ON THE SECOND OR THIRD FLOOR IF A BATHROOM OR <br />BEDROOM IS NOT LOCATED ON THE ENTRY LEVEL. CRC R327.1.3 <br />OUTLET FOR <br />WP/G.F.C.I. <br />240V <br />(N) MINI SPLIT <br />CONDENSER <br />UTILITY PLAN - ADU <br />SCALE: 1/4" = 1'-0" <br />OUTLET FOR <br />D.WD.W.& DISPOSAL <br />SWITCH FOR <br />GAR. DISPOSAL <br />WHOLE -BUILDING VENTILATION REQUIREMENTS (FROM ASHRAE 62.2) <br />AT LEAST ONE MECHANICAL VENITLATION SYSTEM IN THE BUILDING MUST BE DESIGNATED FOR USE <br />IN COMPLIANCE WITH THE WHOLE -BUILDING VENTILATION REQUIREMENT. ALTERNATIVELY, THE SUM <br />OF THE RATED AIRFLOWS FROM MULTIPLE FANS CAN BE UTILIZED TO MEET THE REQUIRED <br />WHOLE-BUILDNG VENTILATION AIRFLOW. THE SYSTEM(S) MUST DELIVER CONTINUOUS VENTILATION <br />AIRFLOW AT A RATE GREATER THAN OR EQUAL TO THE RATE SPECIFIED IN EQUATION 4.1 a AND FAN <br />SONE RATING MUST NOT EXCEED 1.0. FOR DWELLING OCCUPANT DENSITIES KNOWN TO BE <br />GREATER THAN (Nbr + 1), THE RATE SHALL BE INCREASED BY 7.5 FOR EACH ADDITIONAL PERSON. <br />EQUATION 4.1 a 0.01 (799) + 7.5(2 + 1) = 30.49 <br />Qfan = 0.01Afloor + 7.5(Nbr + 1) Qfan 31 cfm <br />Afloor = conditioned floor are, ft' Nbr = number of bedrooms; not to be less than 1 <br />Qfan = ventilation air requirement = fan flow rate, (cfm) <br />NOTE: <br />The whole -building ventilation exhaust fan will operate continuously and is required to be <br />rated for sound at a maximum of 1 sone. This exhaust fan can be controlled by a standard <br />on/off switch but the switch must be labeled to inform the occupant that the exhaust fan is <br />the whole -building ventilation exhaust fan and is intended to operate continuously. No specific <br />wording is mandated, but the wording needs to make clear what the control is for and the <br />importance of operating the system. This may be as simple as "Ventilation Control" or might <br />include wording such as: "Operate when the house is in use" or "Keep on except when gone <br />over 7 days" or "Fan is to be left on to ensure indoor air quality." <br />anning a <br />UTILITY SYMBOLS <br />OUTLET <br />Al <br />rt�­ A.F.C.I 110 V DUPLEX OUTLET <br />Lt�= G.F.C.I 110 V G.F.C.I. DUPLEX OUTLET <br />FOR <br />PE <br />139- G.F.C.I 110 V WEATHERPROOF G.F.C.I. <br />UTLET <br />W.P. 220 V OUTLET <br />SWITCHES <br />i <br />0- 2- WAY SWITCH DIMMER S11 <br />ITMaster� <br />I D. <br />ID3 3- WAY SWITCH 3- WAY DIM <br />3D <br />date. <br />ID 4- WAY SWITCH IDp 4- WAY DIMMER <br />10- VACANCY SENSOR S AIR SWITC <br />v.s. <br />I- MOTION SENSOR AND <br />M.s. PHOTO -SENSOR <br />COMBINATIONS <br />COMBINATION SMOKE/CARBON MONOXIDE <br />sio ALARM, CEILING MOUNTED, HARD WIRED <br />AND W/ BATTERY BACK UP.ICC APPROVED <br />0 SMOKE DETECTOR, HARD WIRED <br />AND W/ BATTERY BACK UP.ICC APPROVED <br />(INSTALL AS PER 2022 CBC) INTERCONNECTED <br />LIGHTING/EXHAUST FANS <br />WALL MOUNT LIGHT: LED LIGHT FIXTURE <br />CEILING RECESSED LED LIGHT FIXTURE <br />BATH ROOM EXHAUST FAN - 50 CFM MIN.: <br />VENT TO OUTSIDE AIR. <br />KITCHEN EXHAUST FAN - 280 CFM MIN.: <br />VENT TO OUTSIDE AIR. <br />ELECTRICAL NOTE: <br />1. Water Heating. Systems using gas or propane water heaters to serve individual dwelling units shall include the <br />following components [150.0(N)]: <br />a. A dedicated 125V, 20A (10 AWG copper branch circuit) electrical receptacle that is within 3 feet from the <br />water heater and accessible to the water heater with no obstructions. There shall be a reserved single pole <br />breaker space in the electrical panel labeled "Future 240V Use". Both ends of the unused conductor shall be <br />labeled with the word "spare" and be electrically isolated. <br />b. A condensate drain that is no more than 2 inches higher than the base of the installed water heater, and <br />allows natural draining without pump assistance. <br />c. Designate a space at least 2.5 ft. by 2.5 ft. wide and 7 ft. tall suitable for the future installation of a heat pump <br />water heater (HPWH). <br />d. If designated space is more than 3 feet from water heater, comply with 150.0(n)B. <br />2. In addition to the local exhaust fans in the bathrooms and kitchens, an exhaust fan shall be sized to provide <br />ventilation for the whole house. The minimum ventilation rate for the whole -building exhaust fan shall be <br />calculated according to ASHRAE Standard 62.2 Equation 4.1(a). The conditioned floor area and the number of <br />bedrooms in the home (the existing house and the addition) will determine the minimum ventilation rate. One of <br />the local exhaust fans in the bathrooms or kitchens may be used to meet the whole -building ventilation, provided <br />the exhaust fan meets the minimum ventilation rated for both the Local Exhaust and Whole -Building Ventilation <br />requirements. The ducting for the whole building exhaust fan shall be sized according to ASHRAE Standard <br />62.2 Table 7.1 and this exhaust fan shall operate continuously. Identify fan manufacturer, model and sone rating <br />(1 sone for continuous, may be 3 sone for intermittent) on plans. <br />3. The whole -building ventilation exhaust fan will operate continuously and is required to be rated for sound at a <br />maximum of 1 sone. This exhaust fan can be controlled by a standard on/off switch but the switch must be <br />labeled to inform the occupant that the exhaust fan is the whole -building ventilation exhaust fan and is intended <br />to operate continuously. No specific wording is mandated, but the wording needs to make clear what the control <br />is for and the importance of operating the system. This may be as simple as "Ventilation Control" or might <br />include wording such as: "Operate when the house is in use" or "Keep on except when gone over 7 days" or <br />"Fan is to be left on to ensure indoor air quality." <br />4. Access to attic furnace must be within 20 feet of unit and shall have a continuous solid walkway at least 24 <br />inches wide. A switch controlled light is also required. [CIVIC 304.4.1]. <br />5. Countertops in the kitchen, dining area and similar areas require a receptacle be provided for each counter <br />space wider than 12 inches so that no point is more than 24" from an outlet. [CEC 210.52(C)] Additional outlet <br />required between cooktop and sink to meet spacing requirements. <br />6. Outlets to be tamper resistant per CEC 406.12. <br />7. Bathroom outlet(s) shall be on a dedicated 20 amp circuit. <br />8. A kitchen is defined as any room containing cooking appliances. Each kitchen is required to have an exhaust fan <br />ducted to the outside with a minimum ventilation rate and capture efficiency per Table 150.0-G or Table 160.2-G <br />(multi -family). The range hood over the stove may be used to meet this requirement but the range hood must <br />vent to the outside; recirculating range hoods cannot be used. The ducting for the exhaust fan shall be sized <br />according to ASHRAE Standard 62.2 Table 7.1. This local exhaust fan may operate continuously or <br />intermittently. Installing this local exhaust fan in the kitchen will allow the home occupant to regulate the indoor <br />air quality when needed. <br />9. Provide the following Electric -Ready requirements: [150.0] <br />A. Heat Pump Space Heater Ready. Systems using gas or propane furnace to serve individual dwelling units <br />shall include the following: <br />1. A dedicated 240 volt branch circuit wiring shall be installed within 3 ft. from the furnace and accessible to the <br />furnace with no obstructions. The branch circuit conductors shall be rated at 30 amps minimum. The blank <br />cover shall be identified as "240V ready". <br />2. The main electrical service panel shall have a reserved space to allow for the installation of a double pole <br />circuit breaker for a future heat pump space heater installation. The reserved space shall be permanently <br />marked as "For Future 240V use." <br />B. Electric Cooktop Ready. Systems using gas or propane cooktop to serve individual dwelling units shall <br />include the following: <br />1. A dedicated 240 volt branch circuit wiring shall be installed within 3 ft. from the cooktop and accessible to <br />the cooktop with no obstructions. The branch circuit conductors shall be rated at 50 amps minimum. The <br />blank cover shall be identified as "240V ready". <br />2. The main electrical service panel shall have a reserved space to allow for the installation of a double pole <br />circuit breaker for a future electric cooktop installation. The reserved space shall be permanently marked <br />as "For Future 240V use." <br />C. Electric Clothes Dryer Ready. Clothes dryer locations with gas or propane plumbing to serve individual <br />dwelling units shall include the following: <br />1. A dedicated 240 volt branch circuit wiring shall be installed within 3 ft. from the clothes dryer location and <br />accessible to the clothes dryer location with no obstructions. The branch circuit conductors shall be rated <br />at 30 amps minimum. The blank cover shall be identified as "240V ready." <br />2. The main electrical service panel shall have a reserved space to allow for the installation of a double pole <br />p P <br />circuit breaker for a future electric clothes dryer installation. The reserved space shall be permanently <br />marked as "For Future 240V use." <br />9. All single-family residences that include one or two dwelling units shall meet the following: [150.0(s)] <br />A. At least one of the following shall be provided: <br />1. ESS ready interconnection equipment with a minimum backed -up capacity of 60 amps and a minimum of <br />four ESS-supplied branch circuits; or <br />2. A dedicated raceway from the main service to a panelboard (subpanel) that supplies the branch circuits <br />in Sec. 150.0(s)(2). All branch circuits are permitted to be supplied by the main service panel prior to the <br />installation of an ESS. The trade size of the raceway shall be not less than 1 inch. The panelboard that <br />supplies the branch circuits (subpanel) must be labeled "Subpanel shall include all backed -up load circuits." <br />B. A minimum of four branch circuits shall be identified and have their source of supply collocated at a single <br />panelboard suitable to be supplied by the ESS. At least one circuit shall supply the refrigerator, one lighting <br />circuit shall be located near the primary egress and at least one circuit shall supply a sleeping room receptacle <br />outlet. <br />C. The main panelboard shall have a minimum busbar rating of 225 amps. <br />D. Sufficient space shall be reserved to allow future installation of a system isolation equipment/ transfer <br />switch within 3 ft. of the main panelboard. Raceways shall be installed between the panelboard and the <br />system isolation equipment/transfer switch location to allow the connection of backup power source. <br />is �suuai�g ncy <br />e <br />raVds& <br />qsKS"AfftE <br />10211 MALINDA LN, <br />GARDEN GROVE, CA 92840 <br />TEL: 714 - 487 - 7926 <br />APDESIGNCA@GMAIL.COM <br />%\ 1 A /A / 1-Y9 _ <br />HUNG TRAN <br />AND LISA PHAM <br />. - - - • • -. ._ .-. _ _ , <br />SANTA ANA, CA 92703 <br />714 - 260 - 2801 <br />REVISIONS <br />NO: DATE REVISIONS <br />1. 12/14/2024 PLAN CHECK <br />Q <br />N <br />H <br />Z <br />co <br />� <br />�o <br />ti <br />rn <br />Q <br />W <br />Q <br />� <br />U <br />W <br />�z <br />2 <br />V <br />mQ <br />Q <br />o <br />�- <br />Q <br />Q <br />�U) <br />i <br />4O <br />U <br />a� <br />O <br />QL <br />PREPARED: <br />ANH PHAN <br />SHEET DESCRIPTION: <br />UTILITY PLANS <br />-ADU <br />Date 5/4/25 <br />Job # 23148 <br />Scale <br />Sheet No.: <br />El <br />