GENERAL NOTES
<br />1. DRAWINGS HEREIN ARE THE PROPERTY OF ES ENGINEERING SOLUTIONS AND SHALL
<br />NOT BE USED FOR ANY OTHER THAN THE LOCATION SHOWN HEREON NOR ALTERED,
<br />COPIED, OR DUPLICATED WITHOUT ES ENGINEERING SOLUTIONS PERMISSION.
<br />2. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR TO
<br />ORDERING ANY MATERIALS, AND NOTIFY ENGINEER IMMEDIATELY IF ANY DISCREPANCIES.
<br />3. ALL WORK SHALL BE PERFORMED IN ACCORDANCE TO CALIFORNIA BUILDING CODE 2022 (CBC 2022), AND
<br />ALL APPLICABLE LOCAL CODES.
<br />4. CONTRACTOR SHALL BE RESPONSIBLE FOR THE CONSTRUCTION MEANS, METHODS, AND SEQUENCE AND
<br />FOR THE SAFETY OF THE WORKERS, CONSTRUCTION SITE AND THE BUILDING DURING CONSTRUCTION.
<br />CONTRACTOR SHALL PROVIDE PROPER SHORING, BRACING, SCAFFOLDING AND ALL MEASURES REQUIRED BY
<br />ALL NATIONAL, STATE AND LOCAL SAFETY PROVISIONS.
<br />5. CONTRACTOR SHALL CAREFULLY STUDY THE PLANS, AND NOTIFY THE ENGINEER IN CASE OF UNCLEAR OR
<br />ANY MISSING DETAILS BEFORE START OF THE CONSTRUCTION OR ORDERING ANY MATERIALS.
<br />6. ENGINEER WILL NOT BE RESPONSIBLE FOR ANY WORK DONE NOT ACCORDING TO PLANS AND
<br />SPECIFICATIONS HEREIN.
<br />7. ALL MATERIALS SHALL CONFORM TO THE PLANS AND SPECIFICATIONS.
<br />8. ALL MANUFACTURED MEMBERS OR HARDWARE SHALL BE INSTALLED PER MANUFACTURER REQUIREMENTS.
<br />9. WHEN DRILLING IN EXISTING CONCRETE, CONTRACTOR SHALL VERIFY THAT ALL EXISTING REINFORCEMENT,
<br />OR TENSION CABLES SHALL REMAIN UNDAMAGED.
<br />10. PRIOR TO ANY EXISTING CONCRETE SAW CUTTING OR REMOVAL, CONTRACTOR SHALL CHECK IF EXISTING
<br />CONCRETE CONTAINS ANY TENSION CABLES AND NOTIFY ENGINEER BEFORE STARTING THE CUTTING OR
<br />REMOVAL PROCESS.
<br />11. DURING THE EXISTING CONCRETE SAW CUTTING OR REMOVAL PROCESS, IF TENSION CABLES ARE
<br />ENCOUNTERED, CONTRACTOR SHALL STOP THE PROCESS IMMEDIATELY AND CONSULT WITH THE ENGINEER
<br />BEFORE PROCEEDING.
<br />12. ANY WORK PERFORMED IN CONFLICT WITH PLANS, SPECIFICATIONS, OR ANY APPLICABLE CODE SHALL BE
<br />CORRECTED BY THE CONTRACTOR AT NO EXPENSE TO THE ENGINEER OR THE OWNER. ALSO, THE ENGINEER
<br />WILL BE COMPENSATED FOR ANY ADDITIONAL DESIGN WORK RESULTED THEREOF.
<br />13. DO NOT SCALE DRAWINGS, CONTRACTOR SHALL ONLY USE WRITTEN DIMENSIONS.
<br />14. CONTRACTORS SHALL NOT START CONSTRUCTION UNLESS PLANS ARE APPROVED BY THE APPROVING
<br />AGENCIES. CONTRACTOR SHALL ONLY USE APPROVED PLANS FOR CONSTRUCTION.
<br />15. DETAILS DESIGNATED AS TYPICAL OR STANDARD SHALL BE APPLIED TO ALL SITUATIONS THAT ARE THE
<br />SAME OR SIMILAR TO THOSE SPECIFICALLY DETAILED. TYPICAL OR STANDARD DETAILS SHALL BE APPLIED
<br />WETHER OR NOT THEY ARE REFERENCED ON THE PLANS.
<br />16. CONTRACTOR SHALL COORDINATE ARCHITECTURAL, STRUCTURAL, MECHANICAL, ELECTRICAL, AND
<br />PLUMBING PLANS AND NOTIFY ENGINEER IF ANY CONFLICT BEFORE START OF THE CONSTRUCTION OR
<br />ORDERING ANY MATERIALS.
<br />17. CONTRACTOR SHALL CHECK THE BUILDING LOCATION WITH RESPECT TO PROPERTY LINES, AND VERIFY
<br />ALL EXISTING CONDITIONS BEFORE EXCAVATION, AND NOTIFY ENGINEER IF ANY DISCREPANCIES.
<br />18. IN CASE OF CONTRADICTION BETWEEN THE DRAWINGS, THE SPECIFICATIONS, AND THE CODES, OR IF ANY
<br />CHANGE IS REQUIRED, THE CONTRACTOR SHALL INFORM THE ENGINEER IMMEDIATELY. NO CHANGE SHALL BE
<br />MADE WITHOUT WRITTEN APPROVAL OF THE ENGINEER.
<br />FOUNDATION NOTES
<br />1. FOUNDATION DESIGN IS BASED ON 1500 PSF ALLOWABLE BEARING CAPACITY (PER
<br />CBC TABLE 1806.2)
<br />2. FOUNDATION SHALL BE PLACED A MINIMUM OF 24" (UNLESS NOTED OTHERWISE)
<br />BELOW FINISH GRADE DIRECTLY ON UNDISTURBED VIRGIN SOIL, OR CERTIFIED
<br />COMPACTED FILL.
<br />3. ALL IMPORTED SOIL SHALL BE TESTED AND APPROVED BY THE SOIL ENGINEER
<br />BEFORE BEING DELIVERED TO THE SITE.
<br />4. CONTRACTOR SHALL PROVIDE PROPER SHORING, UNDERPINNING AND ALL MEASURES
<br />REQUIRED BY ALL NATIONAL, STATE AND LOCAL SAFETY PROVISIONS TO PROTECT ANY ADJACENT
<br />EXISTING FOUNDATIONS, PROPERTIES, STRUCTURES, STREETS, AND UTILITIES PRIOR TO
<br />ANY EXCAVATION
<br />5. FINISH GRADE IMMEDIATELY ADJACENT TO THE BUILDING SHALL BE SLOPED MINIMUM
<br />2% AWAY FROM THE BUILDING UNLESS NOTED OTHERWISE.
<br />6. CONTRACTOR SHALL NOT POUR THE CONCRETE UNLESS ALL REINFORCEMENT,
<br />ANCHOR BOLTS, FRAMING HARDWARE, UTILITY CONDUITS AND PIPES, ETC., AND
<br />FORMWORK ARE PROPERLY PLACED, SECURED, AND INSPECTED BY THE BUILDING
<br />OFFICIAL OR BUILDING INSPECTOR.
<br />7. FOOTING STEPS SHALL BE CONSTRUCTED AT MAXIMUM SLOPE OF 1 (VERTICAL) : 2 (HORIZONTAL) WHERE
<br />NECESSARY.
<br />8. WHEN WATER IS ENCOUNTERED, EXCAVATIONS SHALL BE DEWATERED TO ALLOW INSTALLATION OF
<br />FOOTINGS IN DRY ATMOSPHERE.
<br />STEEL REINFORCEMENT NOTES
<br />1. ALL STEEL REINFORCEMENT SHALL BE DEFORMED, CLEAN, FREE OF RUST AND
<br />CONFORM TO ASTM A615, GRADE 60.
<br />2. WELDING OF STEEL REINFORCEMENT IS PROHIBITED (UNLESS NOTED OTHERWISE)
<br />3. ALL WELDED WIRE MESH SHALL CONFORM WITH ASTM A185.
<br />4. ALL STEEL REINFORCEMENT DETAILING SHALL CONFORM WITH ACI 318 CHAPTER 25.
<br />5. ALL SPLICES SHALL BE CLASS "B".
<br />6. ALL REINFORCEMENT BAR BENDS SHALL BE MADE COLD. HEATING BARS IS NOT
<br />PERMITTED.
<br />7. ALL REINFORCEMENT SHALL BE SECURED IN PLACE AND INSPECTED BY THE BUILDING
<br />OFFICIAL OR BUILDING INSPECTOR BEFORE POURING THE CONCRETE.
<br />REINFORCED CONCRETE NOTES :
<br />1. CONCRETE WILL HAVE A MINIMUM COMPRESSIVE STRENGTH AS FOLLOWS:
<br />A. SLAB ON GRADE......................2500 PSI 0 28 DAYS
<br />B. SPREAD FOOTINGS...................2500 PSI ® 28 DAYS
<br />C. CONTINUOUS FOOTINGS ..........2500 PSI ® 28 DAYS
<br />DESIGN CALCULATIONS ARE BASED ON 2500 PSI CONCRETE AND FOOTINGS ARE
<br />DESIGNED IN ACCORDANCE WITH CBC TABLE 1809.7; THEREFORE, SPECIAL INSPECTION
<br />IS NOT REQUIRED.
<br />2. ALL CONCRETE SHALL BE NORMAL WEIGHT CONCRETE.
<br />3. MAXIMUM WATER-CEMENTITIOUS MATERIAL RATIO (W/CM RATIO) =0.55
<br />4. MAXIMUM CONCRETE SLUMP SHALL BE 4"f1" FOR SLAB ON GRADE, SPREAD
<br />FOOTINGS, AND CONTINUOUS FOOTINGS.
<br />5. ALL STEEL REINFORCEMENT SHALL BE PLACED TO PROVIDE MINIMUM CLEAR COVER
<br />PER CBC SECTION 1808.8.2 AND ACI 318 SECTION 20.6 AS FOLLOWS
<br />A. SLAB ON GRADE......................11" MINIMUM CLEAR COVER
<br />B. SPREAD FOOTINGS...................3" MINIMUM CLEAR COVER
<br />C. CONTINUOUS FOOTINGS ..........3" MINIMUM CLEAR COVER
<br />6. ALL CONCRETE SHALL BE MIXED, TRANSPORTED, AND PLACED IN ACCORDANCE WITH
<br />ACI STANDARDS 318, 3014, AND 301.
<br />7. ALL STEEL REINFORCEMENT SHALL CONFORM TO ASTM A615, GRADE 60.
<br />8. WELDING OF STEEL REINFORCEMENT IS PROHIBITED (UNLESS NOTED OTHERWISE)
<br />9. ALL WELDED WIRE MESH SHALL CONFORM TO ASTM A185.
<br />10. ALL CONCRETE WORK SHALL CONFORM WITH CBC CHAPTER 19
<br />11. ALL CEMENT SHALL BE PORTLAND CEMENT AND SHALL CONFORM WITH ASTM C150.
<br />12. ALL AGGREGATE SHALL CONFORM WITH ASTM C33
<br />13. WATER SHALL CONFORM WITH ASTM C1602.
<br />14. ADMIXTURE SHALL CONFORM WITH ASTM C494, ASTM C1017, ASTM C260, AND
<br />ASTM C1582.
<br />15. CONTRACTOR SHALL NOT POUR THE CONCRETE UNLESS ALL REINFORCEMENT,
<br />ANCHOR BOLTS, FRAMING HARDWARE, UTILITY CONDUITS AND PIPES, ETC., AND
<br />FORMWORK ARE PROPERLY PLACED, SECURED, AND INSPECTED BY THE BUILDING
<br />OFFICIAL OR BUILDING INSPECTOR.
<br />16. CONTRACTOR SHALL PROVIDE THE ENGINEER WITH THE LOCATION OF
<br />CONSTRUCTION JOINTS AND CONTROL JOINTS (IF NOT SHOWN ON PLANS) FOR
<br />APPROVAL PRIOR TO FORMING.
<br />17. UNLESS SPECIFIED ON PLANS, CONTRACTOR SHALL NOT DRILL OR CORE IN
<br />EXISTING OR NEW CONCRETE TO RUN UTILITY CONDUIT OR PIPES OR ANY OTHER
<br />REASON WITHOUT THE ENGINEER'S APPROVAL.
<br />18. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING, MAINTAINING, AND REMOVAL
<br />OF FORM WORK, AND CONCRETE POURING IN ACCORDANCE TO ALL NATIONAL, STATE AND
<br />LOCAL SAFETY PROVISIONS.
<br />19. IN CASE OF EXPOSURE TO SULFATE, OR OTHER SPECIAL EXPOSURE AS DEFINED IN ACI 318 TABLE
<br />19.3.1.1, CONCRETE DESIGN SHALL BE IN ACCORDANCE WITH ACI 318 TABLE 19.3.2.1.
<br />20. BEFORE POURING NEW CONCRETE AGAINST EXISTING CONCRETE, EXISTING CONCRETE SURFACE SHALL BE
<br />ROUGHENED TO f" AMPLITUDE.
<br />FASTENER TABLE
<br />FRAMING LUMBER NOTES :
<br />1. ALL STRUCTURAL LUMBER SHALL BE DOUGLAS FIR -LARCH AND CONFORM TO WEST
<br />COAST LUMBER INSPECTION BUREAU.
<br />2. STRUCTURAL LUMBER SHALL CONFORM TO THE FOLLOWING GRADES UNLESS NOTED
<br />OTHERWISE:
<br />A.
<br />STUDS............................................NO.2
<br />B.
<br />JOISTS AND
<br />RAFTERS....................NO.2
<br />C.
<br />POSTS............................................NO.1
<br />D.
<br />BEAMS AND
<br />HEADERS...................NO.1
<br />E.
<br />TOP PLATES..................................NO.2
<br />F.
<br />SILL PLATES
<br />..................................NO.2 PRESSURE TREATED
<br />G.
<br />BLOCKING.......................................CONSTRUCTION
<br />GRADE
<br />3. ALL WOOD MEMBERS IN DIRECT CONTACT WITH CONCRETE SHALL BE PRESSURE
<br />TREATED WOOD.
<br />4. ALL WOOD MEMBERS EXPOSED TO WEATHER SHALL BE PRESSURE TREATED AND
<br />PAINTED WITH WEATHER PROOF PAINT.
<br />5. MAXIMUM LATERALLY UNSUPPORTED STUD LENGTH, SIZE, AND SPACING SHALL BE
<br />AS FOLLOWS
<br />STUD SIZE LATERALLY UNSUPPORTED LATERALLY UNSUPPORTED
<br />AND SPACING STUD HEIGHT (ONE STORY) STUD HEIGHT (TWO STORY)
<br />2X4 @ 16" O.C. 10'-0" 10'-0"
<br />2X6 ® 16" O.C. 16'-0" 16'-0"
<br />6. PROVIDE CONTINUOUS DOUBLE BLOCKING OR DOUBLE JOISTS AS APPLICABLE UNDER
<br />ANY NON -BEARING WALL BEARING ON FLOOR JOISTS (SEE PLANS FOR BEARING
<br />WALLS).
<br />7. ALL NAILING SHALL BE IN ACCORDANCE TO CALIFORNIA BUILDING CODE, CHAPTER
<br />23.
<br />8. BOLT HOLES SHALL BE T�" LARGER THAN BOLT DIAMETER. ALL BOLTS SHALL HAVE
<br />WASHERS AND NUTS.
<br />9. CONTRACTOR SHALL NOT CUT OR NOTCH EXISTING OR NEW WOOD MEMBERS UNLESS
<br />SPECIFIED ON PLANS.
<br />10. HOLD-DOWN CONNECTOR BOLTS INTO WOOD FRAMING REQUIRE 0.229"X3"X3"
<br />PLATE WASHER ON THE SUPPORTING MEMBER. HOLD-DOWN SHALL BE TIGHTENED TO
<br />FINGER TIGHT PLUS ONE-HALF WRENCH TURN JUST PRIOR TO COVERING THE WALL
<br />FRAMING.
<br />11. ALL HOLD-DOWN, BOLTS, WASHER PLATES, NAILS, OR ANY STEEL FASTENER IN
<br />CONTACT WITH PRESSURE TREATED WOOD SHALL BE HOT -DIPPED GALVANIZED.
<br />12. ALL BEAM AND JOIST HANGERS SHALL BE THE FULL DEPTH OF THE SUPPORTED
<br />MEMBER AND SHALL HAVE ALL HOLES FILLED IN WITH FASTENERS PER MANUFACTURER
<br />REQUIREMENTS TO ACHIEVE THE MAXIMUM CAPACITY OF THE HANGER.
<br />13. ALL STRAPS, HOLD-DOWN, AND ANY HARDWARE CONNECTION SHALL HAVE ALL
<br />HOLES FILLED IN WITH FASTENERS PER MANUFACTURER REQUIREMENTS TO ACHIEVE
<br />THE MAXIMUM CAPACITY.
<br />14. ALL LUMBER SHALL BE DRY TO 19% AND PLYWOOD SHALL BE DRY TO 15% AT
<br />TIME OF INSTALLATION AND WILL BE KEPT DRY AND PROTECTED AT ALL TIMES DURING
<br />CONSTRUCTION.
<br />15. ALL POSTS EXTENDING TO LOWER FLOOR SHALL BE CONTINUOUS BETWEEN UPPER
<br />FLOOR BOTTOM PLATE AND BOTTOM FLOOR TOP PLATES WITH BLOCKING SAME SIZE
<br />AS THE POST OR AS SPECIFIED ON PLAN.
<br />16. IF NOT SHOWN ON PLANS, PROVIDE A POST UNDER EACH END OF ANY BEAM,
<br />DOUBLE JOISTS, OR 3X MEMBER (SAME SIZE AS THE SUPPORTED MEMBER).
<br />17. PROVIDE FULL DEPTH SOLID 2X BLOCKING AT 8'-0" O.C. MAXIMUM FOR FLOOR
<br />JOISTS AND ROOF RAFTERS.
<br />18. USE CBC TABLE 2304.10.1 FOR FASTENERS.
<br />CONNECTION FASTENING REMARKS
<br />ROOF
<br />BLOCKING BETWEEN JOISTS OR RAFTERS TO TOP PLATE
<br />4-81) BOX (2-1/2" X 0.113")
<br />TOE NAIL
<br />CEILING JOIST TO PLATE
<br />4-81) BOX (2-1/2" X 0.113"
<br />TOE NAIL
<br />CEILING JOIST NOT ATTACHED TO PARALLEL RAFTER, LAPS OVER PARTITIONS
<br />4-1 OD BOX 3" X 0.128"
<br />FACE NAIL
<br />COLLAR TIE RAFTER, FACE NAIL OR 1 X" 20-GAGE RIDGE STRAP
<br />4-1 OD BOX 3 X 0.128
<br />FACE NAIL
<br />RAFTER OR ROOF TRUSS TO PLATE
<br />3-16D BOX NAILS (3-1/2" X 0.135 OR
<br />3-10D COMMON NAILS 3" X 0.148"
<br />2 TOE NAILS ON ONE SIDE AND 1 TOE NAIL
<br />ON OPPOSITE SIDE OF EACH RAFTER OR TRUSS
<br />ROOF RAFTERS TO RIDGE, VALLEY OR HIP RAFTERS
<br />OR ROOF RAFTER TO MINIMUM 2" RIDGE BEAM:
<br />4-16D BOX (3-1/2- X 0.135 , OR
<br />3-10D COMMON (3-1/2 "X 0.148"
<br />TOE NAIL
<br />3-16D BOX (3-1/2- X 0.135" , OR
<br />2-16D COMMON (3-1/2" X 0.162"
<br />END NAIL
<br />WALL
<br />STUD TO STUD (NOT BRACED WALL PANELS)
<br />16D COMMON (3-1/2" X 0.162
<br />24" O.C. FACE NAIL
<br />10D BOX 3" X 0.128"
<br />16" O.C. FACE NAIL
<br />STUD TO STUD AND ABUTTING STUDS AT INTERSECTING
<br />WALL CORNERS (AT BRACED WALL PANELS)
<br />16D BOX 3-1 2" X 0.135"
<br />12" O.C. FACE NAIL
<br />16D COMMON (3-1/2- X 0.162
<br />16" O.C. FACE NAIL
<br />ABUTTING STUDS AT INTERSECTING WALL CORNERS, FACE NAIL
<br />16D (3-1/2- X 0.135 "
<br />12" O.C.
<br />BUILT -UP HEADER (2" TO 2" HEADER WITH %" SPACER)
<br />16D COMMON (3-1/2" X 0.162"
<br />16" O.C. EACH EDGE FACE NAIL
<br />16D BOX (3-1/2" X 0.135"
<br />12" O.C. EACH EDGE FACE NAIL
<br />CONTINUOUS HEADER TO STUD
<br />5-81) BOX (2-1/2" X 0.113"
<br />TOE NAIL
<br />4 8D COMMON (2-1/2- X 0.131"
<br />TOE NAIL
<br />TOP PLATE TO TOP PLATE
<br />16 COMMON (3-1/2 " X 0.162"
<br />16" O.C. FACE NAIL
<br />10D BOX 3 X 0.128
<br />12" O.C. FACE NAIL
<br />DOUBLE TOP PLATE SPLICE
<br />8-16D (3-1/2" X 0.135")
<br />FACE NAIL ON EACH SIDE OF END JOINT
<br />MINIMUM 24" LAP SPLICE LENGTH EACH SIDE OF JOINT
<br />BOTTOM PLATE TO JOIST, RIM JOIST, BAND JOIST OR BLOCKING (NOT
<br />AT BRACED WALL PANELS)
<br />16D COMMON (3-1/2" X 0.162"
<br />16" O.C. FACE NAIL
<br />16D BOX (3-1/2" X 0.135 "
<br />12" O.C. FACE NAIL
<br />BOTTOM PLATE TO JOIST, RIM JOIST, BAND JOIST OR
<br />BLOCKING AT BRACED WALL PANEL
<br />3-16D BOX (3-1/2" X 0.135"), OR
<br />2-16D COMMON (3-1/2" X 0.162"
<br />3 EACH 16" O.C. FACE NAIL
<br />2 EACH 16" O.C. FACE NAIL
<br />TOP OR BOTTOM PLATE TO STUD
<br />4-81) BOX (2-1/2" X 0.113"), OR
<br />3-16D BOX (3-1 /2"X 0.135"), OR
<br />4-81) COMMON (2-1/2" X 0.131)"
<br />TOE NAIL
<br />3-16D BOX 3-1 2 X 0.135 , OR
<br />END NAIL
<br />2-16D COMMON 3 3F X 0.135 , OR
<br />2-10D (3" X 0.162"), OR
<br />3-10D BOX 3" X 0.128"
<br />END NAIL
<br />TOP PLATES, LAP AT CORNERS AND INTERSECTIONS
<br />3-10D BOX (3" X 0.128"), OR
<br />2-16D COMMON 3 1 2" X 0.162"
<br />FACE NAIL
<br />FLOOR
<br />JOIST TO SILL, TOP PLATE OR GIRDER
<br />4-81) BOX (2-1/2- X 0.113 , OR
<br />3-81) COMMON (2-1/2" X 0.131), OR
<br />3-10D BOX 3" X 0.128"
<br />TOE NAIL
<br />RIM JOIST, BAND JOIST OR BLOCKING TO SILL OR TOP PLATE
<br />(ROOF APPLICATIONS ALSO)
<br />8D BOX (2-1/2- X 0.113"
<br />4" O.C.
<br />8D COMMON (2-1/2" X 0.131"), OR
<br />10D BOX 3" X 0.128"
<br />6" O.C.
<br />BAND OR RIM JOIST TO JOIST
<br />3-16D COMMON (3-1/2- X 0.162 , OR
<br />4-10D BOX 3" X 0.128"
<br />END NAIL
<br />BUILT-UP GIRDERS AND BEAMS, 2-INCH LUMBER LAYERS
<br />20D COMMON (4" X 0.192"), OR
<br />NAIL EACH LAYER AS FOLLOWS: 32" O.C. AT
<br />TOP AND BOTTOM AND STAGGERED.
<br />10D BOX (3" X 0.128"), OR
<br />24" O.C. FACE NAIL AT TOP AND BOTTOM
<br />STAGGERED ON OPPOSITE SIDES
<br />AND:
<br />2-20D COMMON (4" X 0.192"), OR
<br />3-10D BOX 3" X 0.128" ,
<br />FACE NAIL AT ENDS AND AT EACH SPLICE
<br />LEDGER STRIP SUPPORTING JOISTS OR RAFTERS
<br />4-16D BOX (3-1/2 "X 0.135"), OR
<br />3-16D COMMON (3-1/2- X 0.162), OR
<br />4-10D BOX 3" X 0.128"
<br />AT EACH JOIST OR RAFTER, FACE NAIL
<br />BRIDGING TO JOIST
<br />2-10D 3" X 0.128"
<br />EACH END, TOE NAIL
<br />DESIGN CRITERIA:
<br />1. BUILDING CODE :
<br />PLANS ARE PREPARED IN ACCORDANCE TO CALIFORNIA BUILDING CODE 2022 (CBC 2022).
<br />ALL WORK SHALL BE PERFORMED IN ACCORDANCE TO THIS CODE, AND LOCAL REQUIREMENTS.
<br />2. GRAVITY LOADS:
<br />ROOF DEAD LOAD = 17 PSF
<br />ROOF LIVE LOAD = 20 PSF
<br />FLOOR DEAD LOAD = 15 PSF
<br />FLOOR LIVE LOAD = 40 PSF
<br />3. SEISMIC DESIGN PARAMETERS (GOVERNING THE DESIGN)
<br />RISK CATEGORY = II
<br />SITE CLASS = D
<br />SEISMIC DESIGN CATEGORY = D
<br />SS = 1303g
<br />S, = 0.464g
<br />Fa = 1.2
<br />SpS = 1.042g
<br />SEISMIC RESISTING SYSTEM = LIGHT -FRAME (WOOD) WALLS SHEATHED WITH WOOD STRUCTURAL
<br />PANELS RATED FOR SHEAR RESISTANCE
<br />R = 6.5
<br />CS = 0.16
<br />ANALYSIS PROCEDURE USED = EQUIVALENT LATERAL FORCE
<br />REDUNDANCY FACTOR = 1.3
<br />4. WIND LOAD PARAMETER (NOT GOVERNING THE DESIGN)
<br />WIND RISK CATEGORY =11
<br />WIND EXPOSURE = C
<br />WIND SPEED = 95 MPH
<br />SPECIAL INSPECTION NOTES
<br />SPECIAL INSPECTION IS REQUIRED FOR THE FOLLOWING ITEMS) PER CBC CHAPTER 17
<br />1. CONTINUOUS SPECIAL INSPECTION IS REQUIRED FOR ADHESIVE ANCHORS INSTALLED
<br />IN HARDENED CONCRETE MEMBER (CBC TABLE 1705.3).
<br />SYMBOL LEGEND
<br />NUMBER OF DETAIL HORIZONTAL STRAP
<br />S# # MSTXX
<br />SHEET WHERE DETAIL IS
<br />DETAIL REFERENCE LOCATED
<br />® VERTICAL STRAP
<br />10, SIMPSON HDU HOLDOWN
<br /># NUMBER OF DETAIL
<br />S# # SHEET WHERE DETAIL IS
<br />SECTION CUT LOCATED ###- BEAM OR HEADER
<br /># NUMBER OF DETAIL LIMIT OF JOISTS OR RAFTER
<br />S# # SHEET WHERE DETAIL IS
<br />ELEVATION VIEW LOCATED DIRECTION OF JOISTS OR RAFTERS
<br />NUMBER OF DETAIL
<br />S#.
<br />SHEET WHERE DETAIL IS
<br />LOCATED
<br />-_j
<br />DETAIL CALLOUT
<br /># SHEAR WALL TYPE
<br />Is (PER SCHEDULE)
<br />SW SHEAR WALL LENGTH
<br />;;;SHEAR WALL DESIGNA11ON
<br />SHEARWALL SYMBOL
<br />ABBREVIATIONS
<br />LIMIT OF JOISTS OR RAFTER
<br />DIRECTION OF EXISTING JOISTS OR
<br />EXISTING RAFTERS
<br />@
<br />AT
<br />TOT
<br />TOTAL
<br />B.N.
<br />BOUNDARY NAILING
<br />LINO
<br />UNLESS NOTED OTHERWISE
<br />BM
<br />BEAM
<br />W/
<br />WITH
<br />CENTER LINE
<br />W/0
<br />WITHOUT
<br />CLR
<br />CLEAR
<br />CBC
<br />CALIFORNIA BUILDING CODE
<br />DF
<br />DOUGLAS-FIR LARCH
<br />DIA
<br />DIAMETER
<br />EQ
<br />EQUAL
<br />E
<br />EXISTING
<br />FG
<br />FINISH GRADE
<br />FT
<br />FOOT
<br />HDR
<br />HEADER
<br />IN
<br />INCH
<br />Le
<br />BOLT EMBEDMENT
<br />MAX
<br />MAXIMUM
<br />N
<br />NEW
<br />MIN
<br />MINIMUM
<br />O.C.
<br />ON CENTER
<br />PSF
<br />POUND PER SQUARE FOOT
<br />PLF
<br />POUND PER LINEAR FOOT
<br />SQ.FT.
<br />SQUARE FOOT
<br />SIM
<br />SIMILAR
<br />TYP
<br />TYPICAL
<br />Ir
<br />ningpffm� 8u
<br />Om
<br />A00ox - Aff
<br />R I%VC
<br />T
<br />EXCEPT THE I,QRD GUILD THE NDUS
<br />THEY LABC 14 VAIN TNAT 10110 17
<br />M ter 16" RIMPAU "[, SUITE 210
<br />CORONA, C A MN
<br />Date,: lei. ( fl560-1385
<br />eolioeeriogsolutioos,info@lmoil.com
<br />Drawings and written material appearing herein constitute
<br />original and unpublished work of ES Egineering Solutions and
<br />may not be duplicated used or disclosed without written
<br />consent of ES Engineering Solutions.
<br />eWESS/441
<br />� c
<br />George F Endrawes
<br />w m
<br />O C915o6$
<br />1 1
<br />PROJECT:
<br />GARAGE CONVERSION
<br />TO ADUs
<br />PROJECT ADDRESS:
<br />1313 N SPURGEON ST. UNIT A-H,
<br />SAN TA AN A, CA 92701
<br />1322 FRENCH ST,
<br />SANTA ANA, CA 92701
<br />No. Date Issue
<br />Project No. 282023
<br />scale NOTED
<br />Drawing Title STRUCTURE NOTES
<br />DESIGNED BY: G.E.
<br />CHECKED BY:
<br />DATE:
<br />11/12/2025
<br />Drawing No