Laserfiche WebLink
REGISTEREDPROFESSIONALENGINEER <br />STATE <br />OF <br />CALIFO <br />Ex <br />p <br />. <br /> <br />0 <br />3 <br />- <br />3 <br />1 <br />- <br />2 <br />7 <br />ODNALD <br />J. <br /> <br />PHILLIPPI <br />STRUCTURAL <br />S <br />3 <br />0 <br />5 <br />3 <br />RNIA <br />Water (Drinking) Fountains <br />1. Where water fountains are provided, they shall comply with this section. <br />2. Water fountains shall be located completely within alcoves or otherwise positioned so as not to encroach into <br />pedestrian ways. The alcove in which the water fountain is located shall not be less than 36" in width and 24" <br />in depth. Barriers, if used, shall project horizontally at least as far as the drinking fountain and within 6" of the <br />floor. <br />3. Where only one drinking fountain area is provided on a floor, there shall be a drinking fountain that is <br />accessible to individuals who use wheelchairs and one accessible for standing persons. This can be <br />accommodated by the use of "hi-low" fountains, or by such other means as would achieve the required <br />accessibility for each group on each floor. <br />4. The spout shall be located 15 inches minimum from the vertical support and 5 inches maximum from the front <br />edge of the unit, including bumpers. <br />5. Spouts shall provide a flow of water 4 inches high minimum and shall be located 5 inches maximum from the <br />front of the unit. The angle of the water stream shall be measured horizontally relative to the front face of the <br />unit. Where spouts are located less than 3 inches from the front of the unit, the angle of the water stream shall <br />be 30 degrees maximum. Where spouts are located between 3 inches and 5 inches maximum from the front <br />of the unit, the angle of the water stream shall be 15 degrees maximum. <br />Gypsum Wallboard <br />1. Gypsum wallboard shall not be installed on exterior surfaces. Gypsum wallboard shall not be installed until <br />weather protection for the installation has been provided. <br />2. Supports shall be spaced not to exceed the spacing set forth in Table 25-G for single-ply application and Table <br />25-H for two-ply application. Vertical assemblies shall conform with Section 2503 and horizontal assemblies <br />shall conform with Section 2504 of the CBC. <br />3. For a single-ply application, all edges and ends of gypsum wallboard shall occur on the framing members, <br />except those edges and ends which are perpendicular to the framing members. All edges and ends of <br />gypsum wallboard shall be in moderate contact except in concealed spaces where fire-resistive construction <br />or diaphragm action is not required. <br />4. The size and spacing of fasteners shall conform with Table 25-G of the CBC except where modified by <br />fire-resistive construction meeting the requirements of Section 703.2. Fasteners shall be spaced not less than <br />3/8" from edges and ends of gypsum wallboard. Fasteners may be omitted at the top and bottom of vertical <br />assemblies or the edges and ends of horizontal assemblies perpendicular to supports, and at the wall line, <br />except on shear-resisting elements or fire-resistive assemblies. Fasteners shall be applied in such a manner <br />as not to fracture the face paper with the fastener head. <br />5. For a two-ply application, the base of gypsum wallboard shall be applied with fasteners of the type and size as <br />required for a application single-ply gypsum wallboard. Fastener spacings shall be accordance with Table <br />25-H except as modified by fire-resistive construction meeting the requirements of Section 703.2. <br />6. Gypsum wallboard single-layer fire-rated assemblies shall have joints treated (except where permitted to be <br />untreated per Section 2511.5 of the CBC). <br />7. Wallboard must be attached to full height on both sides of studs with Type S Bugle Head Drywall Screws <br />(Type S-12 for 20 gauge studs) spaced not more than 12" o.c. on all studs when framing is 24" o.c. and 16" <br />o.c. if framing is 16" o.c. or less. Screw lengths must be not less than 3/8" greater than the total thickness of <br />the wallboard being fastened. <br />Entrances, Doors, and Doorways <br />All primary entrances to buildings and facilities shall be made accessible to the physically handicapped. <br />Doors <br />1. Hand activated door-opening hardware to be mounted 34" to 44" above the floor and be operable with a single <br />effort by lever type hardware. <br />2. Maximum effort to operate doors shall not exceed 5 pounds for exterior doors and 5 pounds for interior doors. <br />3. The bottom 10" of all doors (except sliding and automatic) shall have a smooth uninterrupted surface. <br />4. All required exit doorways shall have a minimum 32" clear opening with the door at 90 degrees to the closed <br />position. <br />5. One door of a pair of doors shall meet the minimum width requirements. <br />6. Maximum height of a door threshold shall be 1/2". Maximum vertical change at edge is 1/4" with a maximum <br />bevel of 1:2. <br />7. Hand-activated doors in a path of travel shall operate without requiring the ability to grasp the opening <br />hardware. <br />Structural Steel <br />1. Structural steel and miscellaneous iron shall conform to ASTM A36. (Or ASTM A572 grade 50 where noted on <br />drawings.) <br />2. Steel pipe columns and other steel pipe structural members shall conform to ASTM specifications A53 Grade <br />B. <br />3. Structural steel tubing shall conform to ASTM A500, grade B, Fy=46 ksi. <br />4. All bolts shall conform to ASTM A307 unless noted otherwise. Where high strength (H.S.) bolts conforming to <br />ASTM A325 are specified, installation shall be inspected by an inspector approved by the building department. <br />5. "Nelson" studs shall be manufactured from C1015, C1017, and C1020 cold drawn steel conforming to ASTM <br />A108-58T. <br />6. Light gauge structural steel members shall conform to ASTM standards A246 grade C. <br />7. All structural steel shall be fabricated and erected in accordance with the latest edition of the AISC <br />specifications. <br />8. Fabricator shall be licensed and approved by the building dept. <br />9. Fabricator shall verify all dimensions with architectural and structural drawings. <br />10. Fabricate beam elements with natural camber up. <br />11. Per AISC specifications, bolt holes shall be of "standard hole diameter" except for holes at anchor bolts which <br />may be "oversized holes", U.N.O. <br />12. Steel joists shall be fabricated and erected in accordance with the latest edition of the Steel Joist Institute <br />specifications. <br />13. All exposed structural and miscellaneous steel shall receive one coat of standard shop primer paint. <br />14. Contractor shall provide temporary shoring and bracing per state and local requirements for erection of steel <br />frames and girders. <br />Exits <br />1. The path of travel to and within exits shall be identified by exit signs conforming to the requirements of Section <br />1003.2.8. Exit signs shall be readily visible from any direction of approach and be located as necessary to <br />clearly indicate the direction of egress travel. No point shall be more than 100' from the nearest visible sign. <br />2. Exit signs shall be internally or externally illuminated. When the face of an exit sign is illuminated from an <br />external source, it shall have an intensity of not less than 5 foot candles from either of two electric lamps. <br />Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. <br />3. The exit signs shall also be connected to an emergency electrical system provided from storage batteries, unit <br />equipment or an on-site generator, and shall be installed in accordance with the Electrical Code. <br />4. Floors or landings are required on each side of an exit door. The landing shall have a length of not less than 5' <br />except when opening in to the stairs of a smoke-proof enclosure. The floor or landing shall not be more than <br />1/2" lower than the threshold of the door. <br />5. Exits shall be openable from inside without the use of a key or any special knowledge or effort. Special locking <br />devices shall be of an approved type. <br />6. Provide exit signs with 6" high letters on a contrasting background, as perCBC section 1003.2.8.3. <br />7. Panic hardware shall be provided on exit doors serving rooms, corridors, and stairways handling an occupant <br />load of 50 or more people in Groups A, E, and I Occupancies. <br />8. All exitways shall be illuminated with a minimum of 1 foot candle per square foot, as per CBC section <br />1003.2.9.1. <br />9. A minimum of 44" aisles to an exit shall be maintained to a public way. <br />Concrete <br />1. All concrete mix designs, conforming to CBC Section 1905, shall be submitted to the engineer before any <br />concrete is placed. <br />2. Concrete shall have a minimum compressive strength of 2500 psi at 28 days, U.N.O. <br />3. Portland cement shall be type I or II, U.N.O., conforming to ASTM 150 and shall be tested. Combined <br />aggregates shall be normal weight (145 pcf) U.N.O. conforming to ASTM C33 with shrinkage characteristics of <br />less than 0.04%. Where specified, lightweight concrete for walls shall have an in-place density of 110 pcf. <br />Lightweight aggregate shall be expanded shale or approved equal conforming to ASTM C330. <br />4. Concrete test samples shall be taken in accordance with ASTM and CBC standards if noted on plan or <br />required by General Requirements Notes. Results of the 7 and 28 day tests shall be submitted to the <br />engineer for his records. Slump tests are required for all test samples and must also be reported. <br />Additionally, all lightweight concrete samples must have their in-place densities determined and reported. <br />5. Sides of footing pads may be poured against stable earth. <br />6. Trowel and re-trowel slab for smooth finish with no trowel marks showing wherever concrete floor is exposed. <br />7. See architectural notes for colored or textured concrete. <br />8. Concrete form work tolerances shall be in accordance with CBC and ACI standards. <br />9. All steel reinforcing, anchor bolts, dowels, and other inserts shall be secured in position and inspected by the <br />local building department inspector prior to the pouring of any concrete. <br />10. All necessary braces, strong-backs, pick-up inserts, bolts, etc., for pre-cast concrete panels shall be designed <br />by others for safe erection of the panels. <br />11. Where noted, sound insulating cellular concrete shall be 100 pcf (13 psf at 1-1/2" thickness) for second floor <br />fill. All areas are to be troweled to a smooth flat finish suitable for interior coverings. Provide waterproof paper <br />and mesh. <br />12. All concrete to be cured for a minimum of 7 days by a method acceptable to the engineer. A liquid membrane <br />forming curing compound is acceptable. The curing compound shall be of a type that leaves no permanent <br />discoloration and shall not interfere with the application of any surface treatment. <br />13. Grout shall be within the following proportions: 1 part Portland cement, 2-1/4 to 3 parts dry, loose sand with 1 <br />to 2 parts pea gravel. Grout shall be of fluid consistency and obtain minimum ultimate compressive strength of <br />2000 psi at 28 days. <br />14. Drypack shall be 1 part cement, 2 parts sand, plus enough water for a stiff mix. <br />Foundation <br />1. The contractor shall establish all building lines and proceed with the excavation of all footings as called for on <br />the drawings. <br />2. Footings shall bear on natural undisturbed uniform earth or engineered compacted fill. <br />3. No reinforcing steel and no concrete shall be placed in any excavation prior to approval by the building <br />department. <br />4. The top of all excavations shall be protected against heavy surcharge loads and from erosion due to rainfall or <br />surface run-off during the entire construction period. <br />5. Slabs on grade shall be poured on firm, moistened, compact earth. Construction or crack-control joints shall <br />be spaced no farther than 20' apart and slab area shall not exceed 400 sq. ft. <br />6. Utility trench backfill and any other backfill must be mechanically compacted. Jetting and flooding shall not be <br />permitted. <br />7. All backfill shall conform to the soil engineer's report and recommendations. <br />8. Where walls are back-filled on one side only, provide shoring or other approved means of lateral support until <br />resisting elements are all in place and have attained their required strength. Resisting elements must be <br />concrete slabs or other permanent building components. <br />9. Refer to civil drawings and soil report for grading and compacted fill requirements. <br />10. Foundations shall be inspected by the soil engineer just prior to pouring concrete, ensuring that they are into <br />satisfactory soil, are of proper dimensions, and are clean and free of loose soil. <br />11. Compaction report must be submitted to and be approved by the building department. <br />Reinforcing Steel <br />1. All reinforcing steel, unless noted otherwise, shall conform to the ASTM specifications A615 and shall be <br />intermediate grade 60 for bars #5 and greater, and grade 40 for bars less than #5. <br />2. Refer to typical details for minimum lap length of splice bars. <br />3. Reinforcing steel shall be accurately placed and secured in position with metal or concrete blocks, chairs, <br />spacers, etc., before pouring concrete. <br />4. Welded wire fabric for slabs on grade shall conform to ASTM A185, be in flat sheets, and have min. lap of one <br />parallel strand plus 2". <br />5. Minimum concrete cover shall be: <br />3". . . . . . . Concrete poured against earth (footings, etc.) <br />2". . . . . . . Formed concrete which will remain in contact with earth. <br />1-1/2". . . . Beams measured to main steel, columns, measured to ties or spirals. <br />3/4". . . . . . Structural slabs and precast walls. <br />6. Reinforcing bars that are to be welded (such as chord bars in precast construction) shall be A-706. <br />General Requirements <br />1. All materials and workmanship shall conform to the requirements of both local and International Building Code <br />(CBC) standards. <br />2. Contractor shall check and verify all dimensions and conditions on the job site and report any errors, <br />omissions, or possible discrepancies to the engineer prior to proceeding with the work. Special care shall be <br />given to site and building layouts. <br />3. Typical details and notes shall apply unless shown otherwise on the plans. <br />4. Where "continuous" or "special inspection" is required, a registered deputy inspector, approved by and <br />responsible to the engineer and building department, shall be employed by the owner. Continuous inspection <br />is required for: <br />a. Placing of all concrete with an f'c in excess of 2500 psi. <br />b. All field welding or welding performed in an unlicensed fabricating shop. <br />c. All certified compacted fill. <br />d. Such other items as may be required on plans. <br />5. The contractor shall provide safe and adequate braces and connections to support the component parts of the <br />structure until the structure, including the floor and roof diaphragms, is fully connected and capable of <br />supporting the design loading. <br />6. Where reference is made to various test standards for materials, such standards shall be the latest edition <br />and/or addendum. <br />7. As a convenience to the contractor, the engineer shall review shop drawings as to their general conformance <br />to the design concept. Contractor shall be responsible, nonetheless, for compliance and dimensions and shall <br />submit shop drawings, if applicable, for the following (rebar placing drawings not required): <br />a. Glu-lam beams and panelized roof framing. <br />b. Structural steel and tapered steel girders, including erection bracing. <br />c. Pre-cast concrete elements, including pickup points, strong-backs, and bracing, all certified by a registered <br />civil or structural engineer. <br />d. Concrete pouring sequence, shoring details and special construction techniques (certification may be <br />required). <br />e. Such other items as may be required on plans. Contractor shall submit shop drawings and compliance <br />certificates to the building department when required. <br />8. Where design and details of plate girders, trusses, etc., is to be provided by a fabricator, the contractor shall <br />submit calculations prepared by a civil or structural engineer, to the engineer and to the building department <br />for review prior to the fabrication. <br />9. Options, if provided on the drawings, are for contractor's convenience. He shall be responsible for all changes <br />necessary, shall coordinate all details, and shall obtain all required approvals. <br />10. Costs of additional design work necessitated by selection of an option or due to errors or omissions in <br />construction shall be borne by the contractor. <br />11. Notes and details on drawings shall take precedence over these general notes. <br />12. Written dimensions (not scaled dimensions) shall be used. <br />13. The contractor agrees that he shall assume sole and complete responsibility for job site conditions during the <br />course of construction of this project, including safety of all persons and property; that this requirement shall <br />apply continuously and not be limited to normal working hours; and that the contractor shall defend, indemnify, <br />and hold the owner and the engineer harmless from any and all liability, real or alleged, in connection with the <br />performance of work on this project, excepting from liability arising from the sole negligence of the owner or <br />the engineer. <br />14. Protection of adjoining property (if applicable): Before commencing any excavation the owner shall notify the <br />owners of the adjoining buildings, in writing, not less than 10 days before the excavation is to be made and <br />that the adjoining building should be protected. <br />15. Contractor shall investigate to determine the existence of any and all easements, on the site and on any <br />adjoining property, which the work may affect, and report findings not shown on the drawings to the engineer, <br />prior to proceeding with the work. <br />16. Contractor shall provide barricades and pedestrian protection as required by state and local codes. <br />17. Contractor shall consult with representatives of the city and utility companies concerning available facilities <br />before commencing work or connecting to sewer, piping, or wiring, etc., and report any problems to the <br />engineer. <br />18. Contractor shall install temporary toilets before the start of the job. <br />Welding <br />1. Welding shall be performed by certified operators in a shop licensed by the local authority. <br />2. Welding shall conform to the latest edition of AWS specifications. Welding shall be done by process approved <br />by the building department. Welding electrodes shall be E-7018 (low hydrogen type). <br />3. All field welding shall be continuously inspected. Welders shall be licensed by the local authority. <br />4. All butt welds shall be full penetration unless otherwise detailed on the plans. <br />5. A certificate of fabrication from the shop performing the welding or a report from the special inspector must be <br />furnished to the job inspector prior to framing. <br />Restroom Notes <br />1. Restroom ceiling to be 8'-1" from floor to rough framing. <br />2. Restroom walls shall be 1/2" water resistant gypsum board. Provide a 4' high wainscot of FRP or ceramic tile <br />with trim at a height of 4'. If FRP is used, trim shall also be installed at door jambs. <br />3. Restrooms shall be provided with vents through the roof (100 square inches plus 50 square inches for each <br />additional toilet facility) or by mechanical ventilation providing four air changes per hour. <br />4. Plumbing fixtures shall be Pro-flo, Kohler, or equal (see plumbing drawings). <br />5. Restroom floors shall have a smooth, hard, non-absorbent surface of approved material which extends up the <br />walls at least 6". Seal joint between the 6" flooring vertical extension and the wainscot. <br />1 <br />A0.1 <br />Drinking fountain w/ side barrier rails <br />DRAWN <br />CHECKED <br />DATE <br />JOB NO. <br />SHEET <br />REVISIONS BY <br />4 <br />1 <br />2 <br />3 <br />5 <br />Fe <br />r <br />g <br />u <br />s <br />o <br />n <br /> <br />E <br />n <br />t <br />e <br />r <br />p <br />r <br />i <br />s <br />e <br />s <br />Wa <br />t <br />e <br />r <br />w <br />o <br />r <br />k <br />s <br /> <br />S <br />a <br />t <br />e <br />l <br />l <br />i <br />t <br />e <br /> <br />R <br />e <br />n <br />o <br />. <br /># <br />1 <br />0 <br />8 <br />2 <br />0 <br />0 <br />13 <br />0 <br />1 <br /> <br />E <br />. <br /> <br />H <br />u <br />n <br />t <br />e <br />r <br /> <br />A <br />v <br />e <br />n <br />u <br />e <br />Sa <br />n <br />t <br />a <br /> <br />A <br />n <br />a <br />, <br /> <br />C <br />a <br />l <br />i <br />f <br />o <br />r <br />n <br />i <br />a <br /> <br />9 <br />2 <br />7 <br />0 <br />5 <br />DI <br />A <br />M <br />O <br />N <br />D <br /> <br />P <br />A <br />C <br />I <br />F <br />I <br />C <br />St <br />r <br />u <br />c <br />t <br />u <br />r <br />a <br />l <br /> <br />E <br />n <br />g <br />i <br />n <br />e <br />e <br />r <br />i <br />n <br />g <br /> <br />S <br />e <br />r <br />v <br />i <br />c <br />e <br />s <br />24 <br />7 <br />2 <br /> <br />E <br />a <br />s <br />t <br />m <br />a <br />n <br /> <br />A <br />v <br />e <br />n <br />u <br />e <br />, <br /> <br /># <br />3 <br />2 <br />Ve <br />n <br />t <br />u <br />r <br />a <br />, <br /> <br />C <br />A <br /> <br />9 <br />3 <br />0 <br />0 <br />3 <br />Te <br />l <br />. <br /> <br />( <br />8 <br />0 <br />5 <br />) <br /> <br />6 <br />5 <br />4 <br />- <br />1 <br />3 <br />5 <br />9 <br />DP <br />12-10-24 <br />24009 <br />A0.1 <br />Ge <br />n <br />e <br />r <br />a <br />l <br /> <br />N <br />o <br />t <br />e <br />s