<br />SIGNAGE
<br />PV-5.0
<br />#ESTAMP
<br />NOTES AND SPECIFICATIONS:
<br />·SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE 2013 CEC ARTICLE
<br />110.21(B), UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY SECTION 690, OR
<br />IF REQUESTED BY THE LOCAL AHJ.
<br />·SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE
<br />WORDS, COLORS AND SYMBOLS.
<br />·LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING
<br />METHOD AND SHALL NOT BE HAND WRITTEN.
<br />·LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
<br />INVOLVED.
<br />·SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011, PRODUCT SAFETY
<br />SIGNS AND LABELS, UNLESS OTHERWISE SPECIFIED.
<br />·DO NOT COVER EXISTING MANUFACTURER LABELS.
<br />WARNING!
<br />SOURCES: UTILITY GRID
<br />AND PV SOLAR ELECTRIC
<br />SYSTEM
<br />DUAL POWER SUPPLY
<br />LABEL LOCATION:
<br />UTILITY SERVICE METER AND MAIN
<br />SERVICE PANEL.
<br />PER CODE(S): CEC 2016: 705.12(D)(3),
<br />NEC 2014: 705.12(D)(3), NEC 2011:
<br />705.12(D)(4)
<br />WARNING: PHOTOVOLTAIC
<br />POWER SOURCE
<br />WARNING: PHOTOVOLTAIC
<br />POWER SOURCE
<br />LABEL LOCATION:
<br />INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT,
<br />AT EACH TURN, ABOVE AND BELOW PENETRATIONS,
<br />ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS.
<br />PER CODE(S): CEC 2016: 690.31(G)(3), 690.31(G)(4), NEC
<br />2014: 690.31(G)(3), 690.31(G)(4), NEC 2011: 690.31(E)(3),
<br />690.31(E)(4), IFC 2012: 605.11.1.4
<br />PHOTOVOLTAIC SYSTEM
<br />EQUIPPED WITH
<br />RAPID SHUTDOWN
<br />LABEL LOCATION:
<br />UTILITY SERVICE ENTRANCE/METER, INVERTER/DC
<br />DISCONNECT IF REQUIRED BY LOCAL AHJ, OR
<br />OTHER LOCATIONS AS REQUIRED BY LOCAL AHJ.
<br />PER CODE(S): CEC 2016: 690.12, NEC 2014: 690.12, IFC
<br />2012: 605.11.1
<br />PHOTOVOLTAIC DC DISCONNECT
<br />RATED MAXIMUM POWER-POINT CURRENT:
<br />RATED MAXIMUM POWER-POINT VOLTAGE:
<br />MAXIMUM SYSTEM VOLTAGE:
<br />MAXIMUM SHORT CIRCUIT CURRENT:
<br />ADC
<br />VDC
<br />VDC
<br />ADC
<br />25.96
<br />218.47
<br />280.32
<br />34.68
<br />LABEL LOCATION:
<br />INVERTER(S), DC DISCONNECT(S).
<br />PER CODE(S): CEC 2016: 690.53, NEC 2014: 690.53, NEC
<br />2011: 690.53
<br />INVERTER 1
<br />ELECTRICAL SHOCK HAZARD
<br />DO NOT TOUCH TERMINALS.
<br />TERMINALS ON LINE AND LOAD
<br />SIDES MAY BE ENERGIZED IN
<br />THE OPEN POSITION
<br />WARNING!
<br />LABEL LOCATION:
<br />INVERTER(S), AC/DC DISCONNECT(S),
<br />AC COMBINER PANEL (IF APPLICABLE).
<br />PER CODE(S): CEC 2016: 690.17(E), NEC
<br />2014: 690.17(E), NEC 2011: 690.17(4)
<br />LABEL LOCATION:
<br />INSTALLED WITHIN 3' OF RAPID SHUT DOWN SWITCH
<br />PER CODE(S): CEC 2016: 690.12, NEC 2014: 690.12,
<br />NEC 690.56, IFC 2012: 605.11.1
<br />RAPID SHUTDOWN SWITCH
<br />FOR SOLAR PV SYSTEM
<br />THE DC CONDUCTORS OF THIS
<br />PHOTOVOLTAIC SYSTEM ARE
<br />UNGROUNDED AND MAY BE
<br />ENERGIZED
<br />ELECTRICAL SHOCK HAZARD
<br />WARNING!
<br />LABEL LOCATION:
<br />INVERTER(S), DC DISCONNECTS.
<br />PER CODE(S): CEC 2016: 690.35(F), NEC
<br />2014: 690.35(F), NEC 2011: 690.35(F)
<br />!
<br />DO NOT ADD LOADS
<br />PHOTOVOLTAIC SYSTEM
<br />COMBINER PANEL
<br />WARNING
<br />LABEL LOCATION:
<br />PHOTOVOLTAIC AC COMBINER (IF
<br />APPLICABLE).
<br />PER CODE(S): CEC 2016:
<br />705.12(D)(2)(3)(c), NEC 2014:
<br />705.12(D)(2)(3)(c), NEC 2011: 705.12(D)(4)
<br />MAXIMUM AC OPERATING CURRENT:
<br />NOMINAL OPERATING AC VOLTAGE:
<br /> 20 AMPS
<br /> 240 VAC
<br />PHOTOVOLTAIC AC DISCONNECT
<br />LABEL LOCATION:
<br />AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF
<br />INTERCONNECTION.
<br />PER CODE(S): CEC 2016: 690.54, NEC 2014: 690.54, NEC
<br />2011: 690.54
<br />WARNING!
<br />DO NOT RELOCATE THIS
<br />OVERCURRENT DEVICE
<br />POWER SOURCE OUTPUT CONNECTION
<br />LABEL LOCATION:
<br />ADJACENT TO PV BREAKER (IF
<br />APPLICABLE).
<br />PER CODE(S): CEC 2016:
<br />705.12(D)(2)(3)(b), NEC 2014:
<br />705.12(D)(2)(3)(b), NEC 2011: 705.12(D)(7)
<br />POWER TO THIS BUILDING IS
<br />ALSO SUPPLIED FROM THE
<br />FOLLOWING SOURCES WITH
<br />DISCONNECTS AS SHOWN
<br />CAUTION:
<br />1227 W RIVER LN, SANTA ANA, CA, 92706
<br />SOLAR PANELS ON ROOF
<br />SERVICE ENTRANCE AND PV
<br />BREAKER DISCONNECT
<br />AC DISCONNECT
<br />SUNRUN METER
<br />INVERTER (EXT)
<br />RAPID SHUTDOWN SWITCH
|