Soil Pressure Factors <br />Earth Pressure Factors <br />28 <br />Maximum Dry Density = <br />Active Earth Pressure <br />Ka= <br />Pa= <br />Passive Earth Pressure <br />Kp= <br />Pp= <br />At Rest <br />Kat= <br />Pat= <br />117.8 y= 106. <br />0.3610334834 <br />38.27676991 <br />2.7698261953 <br />293.6569732257 <br />0.5305284373 <br />56.2466249225 <br />Seismic Factors <br />PGAM: 0.66 <br />TL: <br />8 <br />SMs: 1.76 <br />Ss: <br />1.48 <br />Smi: 1.22 <br />Si: <br />0.53 <br />SDs: 1.17 <br />Vs30: <br />260 <br />SD1: 0.81 <br />A full list of Seismic factors is in the Attachment `G' <br />CITY OF SANTA ANA <br />Plannin jjB6Ajlgtng Agency <br />;anti Ana _1CA 92703 <br />Approved <br />FOR PERMIT ISSUANCE <br />Master ID: <br />Date: <br />Soluble Sulfates <br />The results of the limited in-house laboratory tests indicate that the on -site soils tested contain a <br />water-soluble sulfate content of. 16 by weight. Based on Table 19.3.1.1 ofACI 318-14, the Exposure <br />Class S1 is appropriate for onsite soils. Water cement ratio (0.50) shall be adjusted to produce a low <br />slump (<3inches>) mix. Concrete specifications may be changed by the Structural Engineer. <br />Type V cement is not required but is recommended for use. Strength should be 4000 psi. <br />Expansive Soil <br />The soil found on this site consists of silty sand. The soil found on the site is not expansive. A <br />modified test in the laboratory and the condition of the concrete paving and foundations on site show <br />no signs of expansive reaction in the soil. <br />3 <br />