4' - 0"8' - 0" <br />12' - 0" <br />6' - 0" <br />FIXED END <br />FREE END <br />FREE END <br />FIXED END <br />FROM SPLAY <br />WIRE TO WALL <br />CROSS RUNNERS,TYP. <br />CONT. MAIN RUNNER <br />AT 4'-0" O.C., TYP. <br />4 WAY 45 DEG. DIAGONAL 12 <br />GA. WIRE BRACING W/ <br />COMPRESSION STRUT <br />LOCATED ON MAIN RUNNER <br />PER DETAIL: <br />12 GA. <br />VERTICAL <br />HANGER WIRES <br />AT 4'-0" EA. WAY <br />NOTE: <br />1. CEILING GRID MAY BE ATTACHED TO NOT MORE THAN TWO (2) ADJACENT WALLS AND MUST <br />BE AT LEAST 3/4" FREE OF OTHER WALLS. <br />2. LOCATE COMPRESSION STRUT FOR EA. 96 S.F. <br />03/A5-03 <br />FIXTURE SUSPENSION <br />PER DETAIL:04/A5-03 <br />06 <br />A5-03 24 GA. CONT. WALL <br />ANGLE, TYP. <br />8" MAX <br />STABILIZER BARS, <br />CROSS TEES OR <br />STRUTS 8" MAX. FROM <br />WALL TYP. ALONG <br />FREE JOINTS <br />4' - 0" MAX. <br />TYP. <br />AT EXIT WAYS 11/A5-03 <br />SUSPENDED CEILINGS: SEISMIC DESIGN FOR CATEGORIES D THROUGH F (ASCE 7): <br />1. SUSPENSION SYSTEM COMPONENTS SHALL COMPLY WITH ASTM C635 AND E580 SECTION 5.1 AS MODIF IED BY CBC 1616A.1.21: <br />• THE CEILING GRID SYSTEM SHALL BE RATED HEAVY DUTY AS DEFINED BY ASTM C635 <br />• HANGER AND BRACING WIRES SHALL BE #12 GAGE (0.106" DIAMETER), SOFT ANNEALED, AND GALVANIZED STEEL WIRES <br />WITH CLASS 1 COATING. THEY MAY BE USED FOR UP TO AND INCLUDING 4'-0"x 4'-0" GRID SPACING ALONG AND <br />ATTACHED TO MAIN RUNNERS. SPLICES ARE NOT PERMITTED IN ANY HANGER WIRE. <br />• MAIN RUNNERS AND CROSS RUNNERS ALONG WITH THEIR SPLICES, INTERSECTION CONNECTORS, AND EXPANSION <br />DEVICES SHALL BE DESIGNED AND CONSTRUCTED TO CARRY A MEAN ULTIMATE TEST LOAD OF NOT LESS THAN 180 <br />LBS. IN COMPRESSION & TENSION, IN ACCORDANCE WITH ASTM 580 SECTION 5.1.2. <br />2. SUSPENSION SYSTEM INSTALLATION, SHALL COMPLY WITH ASTM C636 AND E580 SECTION 5.2: <br />• PROVIDE #12 GAGE HANGER WIRES AT THE ENDS OF ALL MAIN AND CROSS RUNNERS WITHIN EIGHT (8) INCHES OF THE <br />SUPPORT OR WITHIN ONE-FOURTH (1/4) OF THE LENGTH OF T HE END TEE, WHICHEVER IS LESS, FOR THE PERIMETER <br />OF THE CEILING AREA. PERIMETER WIRES ARE NOT REQUIRED WHEN THE LENGTH OF THE END T EE IS EIGHT (8) INCHES <br />OR LESS. <br />• CEILING GRID MEMBERS SHALL BE ATTACHED TO T WO (2) ADJACENT WALLS, IN ACCORDANCE WITH ASTM E580 SECTION <br />5.2.3. CEILING GRID MEMBERS SHALL BE AT LEAST 3/4" INCH CLEAR OF OTHER WALLS. IF WALLS RUN DIAGONAL T O THE <br />CEILING GRID SYSTEM RUNNERS, ONE END OF MAIN AND CROSS RUNNERS SHOULD BE FREE, AND A MINIMUM OF 3/4 <br />INCH CLEAR OF WALL. <br />• THE WIDTH OF THE PERIMETER SUPPORTING CLOSURE ANGLE SHALL BE NOT LESS THAN TWO (2) INCHES. USE OF <br />ANGLES WITH SMALLER WIDTHS IN CONJUNCTION WITH PERIMETER CLIPS SHALL REQUIRE AN ALTERNATE MET HOD OF <br />COMPLIANCE WITH ADEQUATE JUSTIFICATION AND ARE OUTSIDE THE SCOPE OF T HIS PROJECT. <br />• AT THE PERIMETER OF THE CEILING AREA WHERE MAIN OR CROSS RUNNERS ARE NOT CONNECTED TO THE ADJACENT <br />WALL, PROVIDE INTERCONNECTION BETWEEN THE RUNNERS AT THE FREE END TO PREVENT LATERAL SPREADING. A <br />METAL STRUT OR A #16 GAGE WIRE WIT H A POSITIVE MECHANICAL CONNECTION TO RUNNER MAY BE USED. WHERE <br />THE PERPENDICULAR DISTANCE FROM THE WALL TO T HE F IRST PARALLEL RUNNER IS EIGHT (8) INCHES OR LESS, THIS <br />INTERCONNECTION IS NOT REQUIRED. <br />3. EXPANSION JOINTS, SEISMIC SEPARATIONS, AND PENETRATIONS: <br />• EXPANSION JOINTS SHALL BE PROVIDED IN THE CEILING AT INTERSECTIONS OF CORRIDORS AND AT JUNCTIONS OF <br />CORRIDORS WIT H LOBBIES OR OTHER SIMILAR AREAS. <br />• FOR CEILING AREAS EXCEEDING 2500 SQUARE FEET, A SEISMIC SEPARATION JOINT SHALL BE PROVIDED TO DIVIDE THE <br />CEILING INTO AREAS NOT EXCEEDING 2500 SQ. F T. <br />• PENETRATIONS THROUGH THE CEILING FOR SPRINKLER HEADS AND OTHER SIMILAR DEVICES THAT ARE NOT <br />INTEGRALLY TIED TO THE CEILING SYSTEM IN THE LATERAL DIRECTION SHALL HAVE A T WO (2) INCH OVERSIZED RING, <br />SLEEVE OR ADAPTER THROUGH THE CEILING TILE TO ALLOW FREE MOVEMENT OF ONE (1) INCH IN ALL HORIZONT AL <br />DIRECTIONS. A FLEXIBLE SPRINKLER HOSE FITTING THAT CAN ACCOMMODATE ONE (1) INCH OF CEILING MOVEMENT <br />SHALL BE PERMITTED TO BE USED IN LIEU OF THE OVERSIZED RING, SLEEVE OR ADAPTER. SUCH FLEXIBLE SPRINKLER <br />HOSE SHALL BE ADEQUATELY SUPPORTED FROM SOFF IT SO AS NOT TO EXCEED THE MAXIMUM TRIBUTARY WEIGHT OF <br />THE CEILING. <br />4. CHANGES IN CEILING PLAN ELEVATION SHALL BE PROVIDED WITH POSITIVE BRACING. <br />5. CABLE TRAYS AND ELECTRICAL CONDUITS SHALL BE SUPPORTED INDEPENDENTLY OF THE CEILING. <br />6. SUSPENDED CEILINGS SHALL BE SUBJECT TO THE SPECIAL INSPECTION REQUIREMENTS OF CBC 1707A.6 IN ACCORDANCE <br />WITH ASCE 7-05 SECTION 11A.1.3.9. <br />CEILING FIXTURES, TERMINALS, AND DEVICES: <br />a. CEILING PANELS SHALL NOT SUPPORT ANY LIGHT FIXTURES, AIR T ERMINALS/GRILLS, OR OTHER DEVICES(REFERRED <br />TO ALL BY COMMON T ERM FIXTURES HERE AF TER). <br />b. ALL FIXTURES SHALL BE MOUNTED IN A MANNER THAT WILL NOT COMPROMISE CEILING PERF ORMANCE. <br />c. ALL F IXTURES SHALL BE ATTACHED TO THE SUSPENDED CEILING SYSTEM BY MECHANICAL MEANS, UNLESS <br />INDEPENDENTLY SUPPORTED. T HE ATT ACHMENT DEVICE SHALL HAVE THE CAPACITY OF 100% OF FIXTURE WEIGHT <br />ACTING IN ANY DIRECTION. A MINIMUM OF T WO ATT ACHMENT DEVICES ARE REQUIRED FOR EACH F IXTURE. <br />d. SURFACE MOUNTED FIXTURES SHALL BE ATT ACHED TO THE MAIN RUNNER WITH POSITIVE CLAMPING DEVICES MADE <br />OF MATERIAL WITH A MINIMUM 14 GAGE. A NO.12 GAUGE SAF ETY WIRES SHALL BE ATT ACHED BETWEEN T HE <br />CLAMPING DEVICE AND TO T HE STRUCTURE ABOVE. IN NO CASE SHALL THE FIXT URES EXCEED THE DESIGN <br />CAPACITY OF THE SUPPORTING MEMBERS. <br />e. ALL FIXTURES WEIGHING LESS THAN OR EQUAL T O 10 LB. SHALL HAVE ONE NO. 12 GAUGE SAFETY WIRE CONNECTED <br />FROM F IXTURE HOUSING TO STRUCTURE ABOVE. IT IS NOT NECESSARY FOR THESE SAFETY WIRES TO BE TAUT . <br />f. ALL F IXTURES WEIGHING GREATER THAN 10 LB BUT LESS THAN OR EQUAL TO 56 LB. SHALL HAVE TWO NO. 12 GAUGE <br />SAFETY WIRE CONNECTED FROM FIXT URE HOUSING TO ST RUCTURE ABOVE. IT IS NOT NECESSARY FOR THESE <br />SAFETY WIRES TO BE T AUT. <br />g. ALL F IXTURES WEIGHING GREATER THAN 56 LB. SHALL BE SUPPORTED DIRECTLY FROM STRUCTURE ABOVE BY <br />APPROVED HANGERS. <br />h. PENDENT-HUNG FIXTURES SHALL BE SUPPORTED DIRECTLY F ROM THE STRUCTURE ABOVE USING NO LESS THAN N0. <br />9-GAUGE WIRE OR AN APPROVED ALTERNATE SUPPORT. THE CEILING SUSPENSION SYST EM SHALL NOT PROVIDE <br />ANY DIRECT SUPPORT. <br />i. ALL RECESSED OR DROP -IN F IXTURES SHALL BE SUPPORT ED DIRECTLY F ROM F IXTURE HOUSING TO T HE <br />STRUCTURE ABOVE WIT H A MINIMUM OF T WO NO. 12 GAUGE WIRES LOCATED AT DIAGONALLY OPPOSITE CORNERS. <br />LEVELING OR POSITIONING OF FIXTURES MAY BE PROVIDED BY CEILING GRID. FIXT URE SUPPORT WIRES MAY BE <br />SLIGHT LY LOOSE TO ALLOW THE FIXTURE T O SEAT IN T HE GRID SYST EM. FIXT URES SHALL NOT BE SUPPORT ED <br />FROM MAIN RUNNERS OR CROSS RUNNERS IF THE WEIGHT OF THE FIXT URES CAUSES T OT AL DEAD LOAD T O <br />EXCEED THE DEFLECTION CAPABILITY OF THE CEILING SUSPENSION SYSTEM. <br />(2) 12 GA. SLACK WIRE HANGERS FOR DEVICES THAT <br />WEIGH LESS T HAN 56 LBS. (HEAVY DUTY GRID SYSTEM <br />REQUIRED), PLACE ON DIAGONAL CORNERS <br />(2) #8 SMS EA. SIDE <br />HEAVY DUTY GRID SYSTEM <br />HEAVY DUTY GRID SYSTEM HANGER WIRE (WHERE OCCURS)CEILING FIXTURE, <br />TERMINAL, OR <br />DEVICE (56# MAX) <br />LATERAL FORCE BRACING: <br />a. PROVIDE LATERAL-F ORCE BRACING ASSEMBLIES CONSISTING OF A STRUT AND FOUR (4) #12 GAGE <br />BRACING WIRES ORIENTED 90 DEGREES FROM EACH OTHER. <br />b. LATERAL-FORCE BRACING ASSEMBLIES SHALL BE SPACED IN ACCORDANCE WITH AND FROM <br />EACH WALL AND AT THE EDGES OF ANY CHANGE OF ELEVATION OF T HE CEILING. <br />c. THE SLOPE OF BRACING WIRES MAY BE FROM 10 T O 45 DEGREES BUT MAY NOT EXCEED 45 DEGREES <br />FROM THE PLANE OF THE CEILING AND WIRES SHALL BE TAUT. <br />d. STRUTS SHALL BE ADEQUATE TO RESIST THE VERTICAL COMPONENT INDUCED BY THE BRACING <br />WIRES, AND SHALL NOT BE MORE THAN 1 (HORIZONTAL) IN 6 (VERTICAL) OUT OF PLUMB. <br />EXCEPTION: LATERAL FORCE BRACING MAY BE OMITTED FOR SUSPENDED ACOUSTICAL CEILING SYSTEMS WITH <br />A CEILING AREA OF 144 SQ. F T. OR LESS, WHEN PERIMETER SUPPORT IN ACCORDANCE WITH ASTM E580 ARE <br />PROVIDED AND PERIMETER WALLS ARE DESIGNED TO CARRY THE CEILING LATERAL FORCES. <br />4 WAY 45 DEG. DIAGONAL <br />12 GA. WIRE BRACING FOR <br />TOP ATTACHMENT SEE <br />DETAIL: <br />12 GA. VERTICAL HANGER <br />WIRES AT 4'-0" EA. WAY - <br />FOR TOP ATTACHMENT <br />SEE DETAIL: <br />08/A5-03 <br />08 /A5-03 <br />1-1/2" MAX.1-1/2" MAX. <br />TYP. <br />3/4" MIN. <br />1" MAX <br />400S137-33 (20 GA) CENTERED <br />OVER CROSS RUNNER -SLOT END <br />AS NOTED. FOR TOP ATTACHMENT <br />SEE DETAIL:09/A5-03 <br />CROSS RUNNER <br />MAIN RUNNER <br />(2) 1/4" DIA. MACHINE BOLT <br />TYP. <br />3/4" MIN. <br />TYP. <br />10 TO 45° <br />02/A5-03 <br />FOR ATT ACHMENT TO <br />WALL SEE &07/A5-03 12/A5-03 <br />MAXIMUM OF 8"MAXIMUM OF 8" <br />NOTE: <br />1. PROVIDE 12 GAGE HANGER WIRES AR T HE ENDS OF ALL MAIN AND CROSS RUNNERS WITHIN EIGHT (8) INCHES <br />OF T HE SUPPORT OR WITHIN ONE-FOURTH (1/4) OF THE LENGTH OF T HE END TEE, WHICHEVER IS LESS, FOR <br />THE PERIMETER OF THE CEILING AREA. PERIMETER WIRES ARE NOT REQUIRED WHEN THE LENGTH OF T HE <br />END TEE IS EIGHT (8) INCHES OR LESS. <br />2. NAILS AT ENDS OF HORIZONTAL STRUTS ARE TO BE PLACED WITH NAIL HEAD TOWARD CENTER LINE OF SPAN <br />OF STRUT. <br />3. SPACERS MAY BE SLOTTED APPROVED ANGLES OR CHANNELS WITH "DIAMOND POINTS" OF SPRING STEEL <br />WHICH SNAP TIGHT TO PREVENT MOVEMENT OF STRUT. <br />4. STEEL POP RIVETS SHALL HAVE MINIMUM ALLOWABLE SHEAR STRENGTH OF 120# AND ULTIMATE SHEAR <br />STRENGTH OF 300#. <br />STEEL POP RIVET AT <br />ATTACHED SIDE ONLY <br />TO RUNNER <br />3/4" MIN. CLR. <br />MAIN OR <br />CROSS <br />RUNNER <br />HANGER <br />WIRE <br />CEILING <br />PANEL <br />15/16"X15/16" 24 GA <br />CONT. PERIMETER <br />ANGLE W/ (1) #10 SMS <br />INTO WALL STUDS (24" <br />O.C. MAX) <br />CONT. SLOTTED ANGLE <br />STRUT SPACER W/ <br />HORIZ. 6d RINGSHANK <br />NAIL <br />FREE <br />END <br />FIXED <br />END <br />WALL STUD (20 GA. MIN.) <br />5/8" GYP. BD. <br />(2) #10 SMS TO FRAMING <br />1"x1"x3/4" 12 GA. HOCL -11 ANGLE <br />12 GA. CEILING HANGER WIRE <br />WITH 3 TIGHT TURNS IN 3" BOTH <br />ENDS OF WIRE PER DETAIL 02 /A5-03 <br />1 TO 6 MAX. SLOPE FROM VERTICAL <br />NOTE: <br />1. APPLY DETAIL FOR PERIMETER WIRE ATT ACHMENT OR WHERE OBST RUCTIONS PREVENTS <br />ATT ACHMENT TO STRUCTURE ABOVE. <br />2. WALLS SHALL BE DESIGN F OR HANGER F ORCES. <br />BRACING WIREHANGER WIRE <br />ATT ACHMENT OF HANGER AND BRACING WIRES: <br />a. HANGER WIRE LOOPS SHALL BE TIGHTLY WRAPPED AND SHARPLY BENT TO PREVENT ANY VERTICAL MOVEMENT OR <br />ROT AT ION OF THE MEMBER WITHIN THE LOOPS. <br />b. SPLICES OF WIRES ARE NOT PERMITTED. <br />c. HANGER OR BRACING WIRE ANCHORED TO THE STRUCTURE SHOULD BE INSTALLED IN SUCH A MANNER THAT THE <br />DIRECTION OF THE ANCHOR ALIGNS AS CLOSELY AS POSSIBLE WITH THE DIRECTION OF THE WIRE. <br />d. SEPARATE ALL CEILING HANGER AND BRACING WIRES AT LEAST SIX (6) INCHES FROM ALL UNBRACED DUCTS, PIPES <br />CONDUITS, ETC. <br />e. HANGER WIRES SHALL NOT BE ATTACHED TO OR BEND AROUND INTERFERING MATERIAL OR EQUIPMENT. PROVIDE <br />TRAPEZE OR OTHER SUPPLEMENTARY SUPPORT MEMBERS AT OBST RUCTIONS TO TYPICAL HANGER SPACING. <br />PROVIDE ADDITIONAL HANGERS, STRUTS OR BRACES AS REQUIRED AT ALL CEILING BREAKS, SOFFITS, OR <br />DISCONTINUOUS AREAS. <br />f. HANGER WIRES THAT ARE MORE T HAN 1 (HORIZ ONTAL) IN 6 (VERTICAL) OUT OF PLUMB SHALL REQUIRE PROJECT <br />SPECIFIC DESIGN. <br />g. WHEN DRILLED-IN CONCRETE ANCHORS OR PAF ARE USED IN REINFORCED CONCRETE FOR HANGER WIRES, 1 OUT <br />OF 10 WIRE/ ANCHOR ASSEMBLIES SHALL BE FIELD TESTED FOR 200 LBS. IN TENSION. WHEN DRILLED-IN CONCRETE <br />ANCHORS ARE USED FOR BRACING WIRES, 1 OUT OF 2 WIRE/ANCHOR ASSEMBLIES SHALL BE FIELD T ESTED FOR 440 <br />LBS. IN TENSION IN T HE DIRECTION OF THE WIRE. PAF IN CONCRETE ARE NOT PERMITTED FOR BRACING WIRES. <br />1-1/2"x1-1/2"x12GAx 2" <br />CEILING CLIP, T YP. OR <br />ALT HILT I Hilti X-CX ALH32 <br />HILTI KB -TZ2 3/8" DIA X 2" <br />MIN. EFF. EMBED <br />EXPANSION ANCHOR, TYP. <br />(ICC ESR-4266) <br />LWC/NWC OVER 20 GA <br />MIN. METAL DECK <br />12GA WIRE (ASTM A641 <br />WITH CLASS 1 COATING) <br />WITH 4 TIGHT TURNS <br />WITHIN 1-1/2" OF EACH <br />END <br />1-1/2"x1-1/2"x12GAx 1" <br />CEILING CLIP, T YP. OR <br />ALT HILT I Hilti X-CX ALH32 <br />HILTI X-U SHOT PIN <br />0.157" DIA. W/ 3/4" <br />EMBED <br />(ESR-2269) <br />LWC/NWC OVER 20 GA <br />MIN. METAL DECK <br />12GA WIRE (ASTM A641 <br />WITH CLASS 1 COATING) <br />WITH 3 TIGHT TURNS <br />WITHIN 3" OF EACH END <br />10 to 45° <br />1/2" MAX. <br />1/2" TYP. <br />1/2" TYP. <br />CENTER OF BOLT AND <br />FLUTE <br />1/2" MAX <br />1" <br />3/4"3/4" <br />1-1/2"x1-1/2"x12GA ANGLE <br />OR 162T125-16 TRACK <br />HILTI KB-TZ2 3/8" DIA X 2" MIN. <br />EFF. EMBED EXPANSION <br />ANCHOR, TYP. (ICC ESR-4266) <br />400S137-33 (20 GA) -CUT <br />FLANGES AND BEND <br />HILTI KB2-T Z 3/8" DIA X 2" MIN. <br />EFF. EMBED EXPANSION <br />ANCHOR, TYP. (ICC ESR-4266) <br />400S137-33 (20 GA) - <br />ATTACHED WITH (2) #10 SMS <br />MIN. <br />LWC/NWC OVER 20 GA <br />MIN. METAL DECK <br />CENTER OF BOLT AND <br />FLUTE <br />LWC/NWC OVER 20 GA MIN. <br />METAL DECK <br />CENTER OF BOLT AND FLUTE <br />MIN. 5/8" <br />DIRECTLY TO STUDS <br />BETWEEN STUDS <br />WALL STUD (20 GA. MIN.) <br />5/8" GP. BD. <br />1"x1"x3/4" 12 GA. HOCL -11 ANGLE W/ (2) <br />#10 X 1-1/4" SMS DIRECTLY TO STUD <br />FRAMING <br />12 GA. CEILING BRACE WIRE WITH 4 TIGHT <br />TURNS IN 1-1/2" BOTH ENDS OF WIRE PER <br />DET AIL: <br />10° TO 45° <br />10° TO 45° <br />WALL STUD (20 GA. MIN.) <br />5/8" GP. BD. <br />1"x1"x3/4" 12 GA. HOCL -11 ANGLE W/ (2) <br />#10 X 1-1/4" SMS DIRECTLY TO STUD <br />FRAMING <br />12 GA. CEILING BRACE WIRE WITH 4 TIGHT <br />TURNS IN 1-1/2" BOTH ENDS OF WIRE PER <br />DET AIL: <br />600S137-54 METAL STUD SPAN (2) WALL STUDS <br />MINIMUM, ANCHOR WITH (5) #10 X 1-1/4" SMS <br />02/A5-03 <br />02/A5-03 <br />NOTE: <br />1. PROVIDE 12 GAGE HANGER WIRES AR THE ENDS OF ALL MAIN AND CROSS RUNNERS WITHIN EIGHT (8) INCHES <br />OF THE SUPPORT OR WITHIN ONE-FOURTH (1/4) OF THE LENGTH OF THE END TEE, WHICHEVER IS LESS, FOR <br />THE PERIMETER OF THE CEILING AREA. PERIMETER WIRES ARE NOT REQUIRED WHEN THE LENGTH OF T HE <br />END TEE IS EIGHT (8) INCHES OR LESS. <br />2. NAILS AT ENDS OF HORIZONTAL STRUTS ARE TO BE PLACED WITH NAIL HEAD TOWARD CENTER LINE OF SPAN <br />OF STRUT. <br />3. SPACERS MAY BE SLOTTED APPROVED ANGLES OR CHANNELS WITH "DIAMOND POINTS" OF SPRING STEEL <br />WHICH SNAP TIGHT TO PREVENT MOVEMENT OF STRUT. <br />4. STEEL POP RIVETS SHALL HAVE MINIMUM ALLOWABLE SHEAR STRENGTH OF 120# AND ULTIMATE SHEAR <br />STRENGTH OF 300#. <br />STEEL POP RIVET AT <br />4'-0" O.C. MAX <br />MAIN OR <br />CROSS <br />RUNNER <br />HANGER <br />WIRE <br />CEILING <br />PANEL <br />15/16"X15/16" 24 GA <br />CONT. PERIMETER <br />ANGLE W/ (1) #10 SMS <br />INTO WALL STUDS (24" <br />O.C. MAX) <br />CONT. SLOTTED ANGLE <br />STRUT SPACER W/ <br />HORIZ. 6d RINGSHANK <br />NAIL <br />FREE <br />END <br />FIXED <br />END <br />8" MAX 8" MAX <br />TYP. <br />HANGER <br />WIRE @ <br />4'-0" O.C. <br />TYP. <br />HANGER <br />WIRE @ <br />4'-0" O.C. <br />3/4" <br />MIN. CLR. <br />1/2" MIN. TYP. <br />12 GA. HANGER WIRE WITH (4) TIGHT <br />TURNS WITHIN 1 1/2" FROM BOT H ENDS. <br />LOCATE HANGER WIRE AT CROSS <br />RUNNER RECEIVING CONNECTION TO <br />CURTAIN (4'-0" O.C. MAX.) SPLICES NOT <br />PERMITTED. CONNECTION @ <br />UNDERSIDE OF DECK PER <br />T-BAR GRID <br />CURTAIN TRACK, 15 LBS/LF MAX. <br />ACOUSTIC CEILING <br />TILE (2) #8 S.M.S. PARALLEL AND <br />CENTERED ON TRACK @ 48"O.C. <br />AND 12" MAX. FROM EACH END <br />OF TRACK ATTACHED TO <br />CEILING GRID MEMBERS ONLY. <br />24" MAX. <br />WHERE DISTANCE T O CROSS <br />RUNNER EXCEEDS 6" ADD <br />ADDITIONAL HANGER WIRES @ <br />4'-0" O.C. MAX. <br />MAIN RUNNER <br />08 /A5-03 <br />R <br />No.No.No.No. <br />FFFF <br />LLLLIIIICCCCEEEENNNNSSSSEEEE <br />SSSSTTTTAAAATTTTEEEE <br />DDDD <br />OOOO <br />AAAA RRRRCCCCHHHHIIIITTTTEEEECCCCTTTT <br />CCCC AAAALLLL IIIIFFFFOOOORRRRNNNNIIIIAAAA <br />SSSSTTTTEEEEPPPPHHHHEEEE WWWWHHHHIIIITTTTEEEE <br />R ENEWAL R ENEWAL R ENEWAL R ENEWAL <br />D AT EDATEDATEDATE <br />CCCC ----34829348293482934829 <br />NNNN <br />08/31 /2708/31 /2708/31 /2708/31 /27 <br />SHEET TITLE <br />PROJECT <br />FACILITY <br />FAC NO:BLDG NO:FLOOR LEV:SECTION: <br />KP PROJ. NO. <br />PERMIT NO. <br />555 W. Fifth Street Suite 2950 | Los Angeles, CA 90013 USA <br />ARCHITECT <br />CONSULTANT <br />ARCHITECT SEAL CONSULTANT SEAL <br />KAISER FOUNDATION HOSPITALS <br />NATION AL FACILITIES SERVICES <br />1800 HARRISON STREET OAKLAND, <br />CALIFORN IA 94612 <br />ISSUE / REVISION LOG <br />NO.ISSUED DATE <br />0 <br />5' <br />50' <br />GRAPHIC SCALES: <br />1/16" = 1'-0" <br />0 <br />25' <br />1/8" = 1'-0" <br />5' <br />0 <br />12' <br />1/4" = 1'-0" <br />1' <br />0 <br />6' <br />1/2" = 1'-0" <br />1' <br />0 <br />2' <br />1-1/2" = 1'-0" <br />0 <br />1' <br />3" = 1'-0" <br />IF THIS SHEET IS NOT <br />30"x42", IT IS A REDUCED <br />PRINT - <br />SCALE <br />ACCORDINGLY <br />AGENCY APPLICATION NUMBER <br />AGENCY APPROVAL STAMP <br />THIS DOCUMENT IS THE PROPERTY OF THE OWNER AND IS <br />NOT TO BE USED WITHOUT OWNER'S WRITTEN PERMISSION. <br />HZ PROJ. NO. <br />www.huitt-zollars.com <br />Phone 310.820.4600 | Fax 310.207.4215 <br />C:\Users\lrobinson\OneDrive - Huitt-Zollars, Inc\Documents\R314412.35 KP HBM KPOJ_A24_lrobinsonL2MDX.rvt <br />1/6/2026 2:42:47 PM <br />SOCC 2022 R HBM 1st Fl KPOJ <br />REMODEL <br />A5-03 <br />DETAILS -TYPICAL CEILING -ACT <br />CA394-1 - <br />CAP027721R314412.35 <br />HARBOR/MacARTHUR MEDICAL OFF <br />3401 S. HARBOR BLVD. <br />SANTA ANA, CALIFORNIA 92704 <br />101125520, 20187249, 40140902 <br />1/8" = 1'-0"ACT DIAGRAMATIC CEILING PLAN 02 <br />N/AACT SUSPENDED CEILING NOTES 01 <br />3" = 1'-0"ACT FIXTURE SUSPENSION 04 <br />3" = 1'-0"ACT COMPRESSION STRUT 03 <br />3" = 1'-0"ACT PERIMETER ATTACHMENT 06 <br />3" = 1'-0"CEILING WIRE AT PERIMETER OBSTRUCTION 07 <br />3" = 1'-0"HANGER AND BRACE WIRE CONNECTIONS 08 <br />3" = 1'-0"COMPRESSION STRUT ANCHORAGE 09 <br />3" = 1'-0"BRACE WIRE AT WALL 12 <br />3" = 1'-0"ACT PERIMETER ATTACHMENT @ EXITWAYS 11 <br />3" = 1'-0"CURTAIN TRACK MOUNTING 13 <br />CITY SUBMITTAL / BID SET 11/03/2025