Laserfiche WebLink
POST-INSTALLED ANCHOR ANALYSIS PER ACI 318-19(ACI 318-14), CHAPTER 17 Configuration 1 <br />Bay 1 - 120" (Option 1) <br />Assumed cracked concrete application <br />Anchor Type 0.5" dia., 3.25 hef, 5.5" min, slab <br />ICC Report Number ESR-4266 1.5 . hef = 4.875 in. <br />Slab Thickness (h)= 5.5 in.Ca1 = 12 useCa1,adj = 4.875 in. <br />Min. Slab Thickness (h)= 5.5 in.Ca2 = 12 useCa2,adj = 4.875 in. <br />Concrete Strength (fc)= 8600 psi <br />Diameter (da)= 0.5 in.3 . hef = 9.75 in. <br />Nominal Embedment (hnom)= 3.75 in. <br />Effective Embedment (hef)= 3.25 in.S1 = 8 in.Use S1,adj = 8 in. <br />Number of Anchors (n)= 6 S2 = 4 in.Use S2,adj = 4 in. <br />e`N = 0 <br />e`V = 0 <br />From ICC ESR Report <br />Ase = 0.099 sq.in. <br />f`uta = 114000 psi <br />Smin = 2 in. <br />Cmin = 2.25 in. <br />Cae = 8 in. <br />Np,cr = 9999 lbs <br />fSeismic Adj. Strength <br />Tension Capacity = 3854 lbs 0.75 2891 lbs <br />Shear Capacity = 4468 lbs 0.75 3351 lbs <br />PROJECT: <br />FOR: <br />ADDRESS: <br />SHEET#: <br />CALCULATED BY: <br />DATE: <br />Behr Process Corp <br />Interlake-Mecalux_Gabr <br />1995 S Standard Av <br />Santa Ana, CA <br />19 <br />kelvira <br />4/11/2024 <br /> TEL:(909)869-0989 <br /> 1130 E. CYPRESS ST, COVINA, CA 91724 <br />PN:20240411_15