LANDING
<br />FOUNDATION PLAN SCHEDULE SYMBOL DESCRIPTIONS
<br />SCALE: 1/4"=1'-0"FOUNDATION PLAN1
<br />INDICATES SHEARWALL TYPE
<br />FOR SHEARWALL SCHEDULE
<br />SEE 1/S1.21
<br />INDICATES MINIMUM
<br />LENGTH OF SHEARWALL
<br />SWXX
<br />(#'-#")
<br />INDICATES HOLDOWN TYPE X
<br />INDICATES STEEL SECTION POST
<br />MARK, ALL POSTS ARE
<br />STEEL SECTION UNO ON PLANS
<br />INDICATES WOOD POST MARK,
<br />SEE POST SCHEDULE
<br />C#
<br />HDU
<br />X
<br />#
<br />S#.##INDICATES SECTION
<br />INDICATES SHEET NUMBER
<br />INDICATES DETAIL
<br />NUMBER ON THE SHEET
<br />INDICATES TYP. 12" WIDE
<br />FOUNDATION UNO ON PLAN
<br />INDICATES HANGER
<br />S#.##
<br />#
<br />INDICATES CALLOUT
<br />#INDICATES REVISION ON
<br />DRAWINGS
<br />INDICATES VIEW#
<br />S#.##
<br />INDICATES LOAD BEARING WALL
<br />BW
<br />SOG REQUIREMENT NOTES
<br />FOUNDATION PLAN NOTES
<br />SW1
<br />(13'-10")
<br />SW1
<br />(2'-8")
<br />WS
<br />P
<br />(1
<br />7
<br />'
<br />-
<br />3
<br />"
<br />)
<br />SW
<br />1
<br />(1
<br />3
<br />'
<br />-
<br />0
<br />"
<br />)
<br />WS
<br />P
<br />(2
<br />5
<br />'
<br />-
<br />9
<br />"
<br />)
<br />12"
<br />12
<br />"
<br />12"
<br />12
<br />"
<br />12"
<br />12
<br />"
<br />12"
<br />12"
<br />SEE NOTE A
<br />SW1
<br />(8'-2")16
<br />"
<br />1
<br />S1.01
<br />TYP
<br />5
<br />S1.01
<br />TYP
<br />1
<br />S1.01
<br />TYP
<br />S1.01
<br />2
<br />REVIEW THE PLAN NOTES AND
<br />PERFORM FIELD CONDITION
<br />ASSESSMENT AND VERIFICATION
<br />PRIOR TO COMMENCING THE WORK.
<br />1. SOIL SUBGRADE REQUIREMENTS, ELEVATION AND SLOPING OF FOUNDATIONS AND SOG, AND
<br />CONSTRUCTION REQUIREMENTS ARE NOT PART OF THIS SCOPE OF WORK OR THE LIABILITY OF THE
<br />STRUCTURAL ENGINEER.
<br />2. IF GEOTECHNICAL REPORT OR CIVIL DWGS. ARE AVAILABLE, CONTRACTOR SHALL REVIEW AND FOLLOW
<br />THE GEOTECHNICAL REPORT AND CIVIL DWG. FOR THE CONSTRUCTION OF SOIL SUBGRADE AND SOG.
<br />3. IN THE ABSENCE OF GEOTECHNICAL REPORT, OR CIVIL REPORT AND DWGS. THE DETAILS SHOWN ON
<br />THESE DWGS. MAY BE CONSIDERED BY THE OWNER/GC ON THEIR OWN RISK. STRUCTURAL ENGINEER
<br />SHALL NOT BE RESPONSIBLE FOR ANY DAMAGES THAT MAY OCCUR DUE TO USING THESE
<br />RECOMMENDATIONS.THESE ARE GENERAL RECOMMENDATIONS FOR THE CONSTRUCTION OF SOIL
<br />SUBGRADE. THESE DETAILS DO NOT CONSIDER THE ACTUAL FIELD CONDITIONS.
<br />3.1. SOG AND FOUNDATIONS SHALL BE CONTINUOUSLY SUPPORTED ON UNDISTURBED OR ENGINEERED
<br />FILL SOIL.
<br />3.2. THE AREA WITHIN THE SOG AND FOUNDATION WALLS SHALL HAVE ALL VEGETATION, TOP SOIL AND
<br />FOREIGN MATERIAL REMOVED.
<br />3.3. FILL MATERIAL SHALL BE FREE OF VEGETATION AND FOREIGN MATERIAL. THE FILL SHALL BE
<br />COMPACTED TO ENSURE UNIFORM SUPPORT OF THE SOG, FOUNDATION, AND THE FILL DEPTHS SHALL NOT
<br />EXCEED 24 IN FOR CLEAN SAND OR GRAVEL AND 8 IN FOR EARTH.
<br />3.4. AT SOG AREA, REINFORCING STEEL SHALL BE SUPPORTED TO REMAIN IN PLACE FROM THE CENTER TO
<br />MIDDLE FOURTH OF THE SLAB FOR THE DURATION OF THE CONC. PLACEMENT.
<br />3.5. SCARIFY TOP 12" OR RECOMPACT 4' OVEREXCAVATION PRIOR TO TRENCHING FOR THE UTILITY
<br />AND/OR FOUNDATION. 90% COMPACTION REPORT IS REQUIRED AT THE OF FOUNDATION INSPECTION.
<br />DAMP PROOFING, BASE COURSE AND PRE-SATURATION ARE REQUIRE.
<br />3.6. PROVIDE 5" SLAB ON GRADE REINFORCED WITH #4 AT 18" ON CENTERS EACH WAY OVER 4" BASE OF
<br />1
<br />2" OR LARGER CLEAN AGGREGATE WITH 10 MIL VAPOR RETARDER IN DIRECT CONTACT WITH CONCRETE.
<br />SLAB SHAL BE TIED-IN TO CONTINUOUS 12" WIDE x 24" (MINIMUM EMBEDMENT INTO FIRM SOIL)
<br />FOUNDATION.
<br />4. PROVIDE CONTROL JOINTS AT CL. OF CONC. OR STEEL COLUMNS IF NO CONSTRUCTION JOINTS OCCUR.
<br />5. CONTRACTOR TO SUBMIT A JOINTING PLAN TO ARCHITECT FOR REVIEW.
<br />6. THE TOP SURFACE OF FOUNDATIONS SHALL BE LEVEL ,UNO ON ARCH. DWG.
<br />7. THE BOTTOM SURFACE OF FOUNDATION AND SOG SHALL NOT HAVE A SLOPE EXCEEDING ONE UNIT VER.
<br />IN 12 UNITS HOR.
<br />8. UNO ON PLANS OR TYPICAL DETAILS, NO HOR. CONSTRUCTION SHALL BE PERMITTED IN THE
<br />FOUNDATIONS. ALL OTHER CONSTRUCTION JOINTS SHALL BE SUBMITTED TO SEOR AND ARCH FOR
<br />REVIEW.
<br />POST SCHEDULE UNO ON PLAN
<br />MARK POST SIZE
<br />C44 4x4
<br />C44
<br />W/B
<br />C
<br />4
<br />0
<br />C44
<br />W/B
<br />C
<br />4
<br />0
<br />C44
<br />W/B
<br />C
<br />4
<br />0
<br />C44
<br />HDU
<br />2HDU
<br />2
<br />C44
<br />C44
<br />HDU
<br />2
<br />HDU
<br />2
<br />HDU
<br />2
<br />C44
<br />C44
<br />W/B
<br />C
<br />4
<br />0
<br />C44
<br />W/B
<br />C
<br />4
<br />0
<br />C44
<br />W/B
<br />C
<br />4
<br />0
<br />C44
<br />W/B
<br />C
<br />4
<br />0
<br />C44
<br />W/B
<br />C
<br />4
<br />0
<br />C44
<br />W/B
<br />C
<br />4
<br />0
<br />C44
<br />W/B
<br />C
<br />4
<br />0
<br />C44
<br />W/B
<br />C
<br />4
<br />0
<br />C44
<br />W/B
<br />C
<br />4
<br />0
<br />C44
<br />W/B
<br />C
<br />4
<br />0
<br />C44
<br />C44
<br />W/B
<br />C
<br />4
<br />0
<br />HDU
<br />2C44
<br />C44
<br />HDU
<br />2
<br />HDU
<br />2
<br />C44HDU
<br />2
<br />HDU
<br />2
<br />C44
<br />C44HDU
<br />2
<br />12
<br />"
<br />1
<br />A
<br />B
<br />C
<br />D
<br />2 3 4
<br />NOTE A:
<br />5" SOG W/#4@18"O.C. EACH WAY. SEE SOG REQUIREMENT NOTES FOR CAPILLARY
<br />BREAK REQUIREMENTS.
<br />12
<br />"
<br />LANDING SEE DETAIL 9/S1.01
<br />C44
<br />C44
<br />W/B
<br />C
<br />4
<br />0
<br />1 . T HES E D R A W I N G AR E BASE D O N T HE B EST A VAI L AB L E SO U R C E S AND D O N O T A DD R ES S T HE F IELD
<br />CONDITIONS. THE CONTR ACTOR SHALL V ERIFY ALL FIELD CONDITIONS AND ALL EXISTING STRUCTURAL
<br />E L E M E N T S S P E C I F I E D A S V E R I F I E D I N F I E L D (V .I .F .) P R I O R T O C O M M E N C I N G T H E W O R K . A N Y
<br />DISCREPANCIES BETWEEN THESE DRAWINGS AND FIELD CONDITIONS SHALL BE REPORTED TO THE AEOR
<br />AND SEO R . N O W OR K SHAL L BE P E RFOR MED IN T HE AFF E CT ED A REAS UNTIL TH E DIS CR EP ANC I E S AR E
<br />RESOLVED.
<br />2. NO CUTTING, DRILLING, DEMOLITION OR DESTRUCTIVE WORK ON CONCRETE OR WOOD ELEMENTS SHALL
<br />BE PERMITTED UNLESS ALL REINFORCING STEEL INCLUDING PT TENDONS, BEARING WALLS, SHEAR WALLS,
<br />BEAMS,AND DIRECTIONS OF JOISTS AND RAFTERS THAT WILL BE AFFECTED ARE POSITIVELY IDENTIFIED.
<br />3 . CO NT R A C T O R I S S O L E L Y R E S P O NS IB L E F O R P R O T E C T I O N O F A L L ST R U C T U R AL, N O N S T R U C T UR A L ,
<br />ARCHITECTURAL, FINISHING, ELECTRICAL AND MECHANICAL COMPONENTS WHICH ARE NOT DESIGNATED
<br />FOR DEMOLITION OR NEW CONSTRUCTION. ANY DAMAGES CAUSED BY THE CONTRACTOR OR
<br />SUBCONTRACTORS SHALL BE REPAIRED BY THE CONTRACTOR AT NO COSTS TO THE ENGINEERS OR OWNER.
<br />4. STRUCTURAL DRAWINGS ARE NOT STAND-ALONE DOCUMENTS AND ARE INTENDED TO BE USED IN
<br />CONJUNCTION WITH CIVIL, ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND DRAWINGS FROM OTHER
<br />DISCIPLINES. THE CONTRACTOR SHALL COORDINATE ALL REQUIREMENTS OF THE CONTRACT DOCUMENTS
<br />INTO THE SHOP DRAWINGS AND FIELD WORK.
<br />5. ALL ELEVATIONS, SLOPES, DRAINAGE, DIMENSIONS OF OPENINGS, PENETRATIONS, DEPRESSIONS, AND
<br />LAYOUT AND GEOMETRY OF NONSTRUCTURAL ELEMENT SUCH AS BUT NOT LIMITED TO PARTITION,
<br />WINDOWS, PLUMBING, ARE NOT INCLUDED IN THE STRUCTURAL ENGINEERING SCOPE OF WORK AND SHALL
<br />NOT BE THE RESPONSIBILITY OF THE STRUCTURAL ENGINEER. REFER TO THE DRAWINGS FROM OTHER
<br />PROFESSIONS FOR THE INFORMATION MENTIONED ABOVE.
<br />6. FOR CONSTRUCTION NOTES AND TYPICAL SYMBOLS DESCRIPTIONS, SEE S0 SERIES SHEETS.
<br />7. FOR TYPICAL DETAILS, SEE S1 SERIES SHEETS. DETAILS AND SCHEDULES INDICATED AS 'TYPICAL' MAY
<br />NOT BE SPECIFICALLY REFERENCED ON DRAWINGS. DETERMINE WHERE EACH TYPICAL DETAIL OR
<br />SCHEDULE APPLIES BEFORE PROCEEDING WITH WORK.
<br />8. SEE ARCH./CIVIL DWGS. FOR CONCRETE SLAB ELEVATIONS, DEPRESSIONS, SLOPES, OPENINGS, CURBS,
<br />DRAINS, TRENCHES, SLAB EDGE LOCATIONS, ETC., AND FOR WALL OVERALL DIMENSIONS, LOCATIONS OF
<br />OPENINGS, ETC., NOT INDICATED ON STRUCTURAL DWGS.
<br />9. HOLD-DOWNS& ANCHORS HARDWARE MUST BE SECURED IN PLACE PRIOR TO CALLING FOR FOUNDATION
<br />INSPECTION. WET SETTING ANCHORS IS PROHIBITED.
<br />10. APPROVED PLATE WASHERS SHALL BE USED FOR HOLD-DOWN CONNECTOR BOLTS INTO WOOD FRAMING.
<br />HOLD-DOWNS SHALL BE FINGER TIGHT AND 1/2 WRENCH TURN JUST PRIOR TO COVERING WALL FRAMING.
<br />11. STANDING WATER SHALL BE REMOVED FROM THE FOUNDATION EXCAVATIONS PRIOR TO THE CONCRETE
<br />PLACING.
<br />12. UNO IN ARCH./CIVIL DWGS. SURFACE OUTSIDE THE HOUSE NEEDS TO HAVE 5% SLOPE (UNPAVED
<br />SURFACE) & 2% SLOPE (PAVED SURFACE) AWAY FROM THE STRUCTURE.
<br />13. ANCHOR BOLTS IN CONTACT WITH PRESSURE TREATED SILL PLATE SHALL BE OF HOT-DIPPED
<br />ZINC-COATED GALVANIZED STEEL, STAINLESS STEEL, SILICON BRONZE OR COPPER.
<br />14. MINIMUM EDGE DISTANCE FOR ANCHOR BOLTS SHALL BE 1-3/4". ALL ANCHOR BOLTS SHALL INCLUDE A
<br />MINIMUM 0.229"X3"X3" STEEL PLATE WASHER. THE HOLE IN THE PLATE WASHER SHALL BE PERMITTED TO
<br />BE DIAGONALLY SLOTTED WITH A WIDTH OF UP TO 3/16" LARGER THAN THE BOLT DIAMETER AND A SLOT
<br />LENGTH NOT TO EXCEED 1-3/4", PROVIDED A STANDARD CUT WASHER IS PLACED BETWEEN THE PLATE
<br />WASHER AND THE NUT. THE PLATE WASHER SHALL EXTEND TO WITHIN 1/2" OF THE EDGE OF THE BOTTOM
<br />PLATE ON THE SIDE(S) FOR SHEATHING WITH SHEAR DESIGN VALUES EXCEEDING 400PLF.
<br />15. THE FOUNDATION PLAN SHOWS THE GENERAL LAYOUT OF THE FOUNDATION. FOR LOCALIZED SIZE
<br />CHANGES AT THE HOLD-DOWNS, REFER TO TYPICAL DETAILS. AT ALL HOLD-DOWN LOCATIONS,
<br />FOUNDATION SHALL BE CONSTRUCTED WITH THE DIMENSIONS SPECIFIED IN TABLE FOR HOLD-DOWN
<br />ANCHOR SCHEDULE SEE SHEET S1.01.
<br />16. ALL WOOD MEMBERS IN CONTACT WITH MASONRY AND CONCRETE SHALL BE PRESSURE-TREATED AND
<br />CONFORM TO THE REQUIREMENT OF "AWPA U1" FOR CATEGORY UC4A OR BETTER.
<br />17. WOOD AND WOOD BASED MATERIALS USED RAISED FLOOR SYSTEMS INCLUDING JOISTS AND BEAMS
<br />SHALL CONFORM TO THE REQUIREMENTS OF "AWPA U1" FOR CATEGORY UC3B OR HIGHER.
<br />18. NO HORIZONTAL COLD JOINTS OTHER THAN THE LOCATIONS SHOWN ON THESE DRAWINGS SHALL BE
<br />PERMITTED IN FOUNDATION CONSTRUCTION. ALL CONSTRUCTION JOINTS SHALL BE SUBMITTED TO SEOR
<br />FOR REVIEW.
<br />19. BEARING WALLS SHALL BE SHEATHED ON NOT LESS THAN ONE SIDE OR BRIDGING SHALL BE INSTALLED
<br />NOT GREATER THAN 4 FEET APART MEASURED VERTICALLY FROM EITHER END OF THE STUD. 2x BLKG SHALL
<br />BE PROVIDED AT PLYWD JOINTS FOR ALL WALLS.
<br />20. SPECIAL SOIL CONDITIONS AND PROPERTIES SUCH AS LIQUEFACTION ZONES; ADJACENT TO OR WITHIN
<br />AREAS PRONE TO LANDSLIDE, SLOPED LOTS GREATER THAN 1 UNIT VERTICAL UNITS HORIZONTAL ARE NOT
<br />INCLUDED IN THIS SCOPE OF WORKS AND NOT CONSIDERED FOR FOUNDATION DESIGN. OWNER SHALL
<br />HIRE A SOIL ENGINEER TO VERIFY THESE CONDITIONS AND THEIR EFFECTS ON STRUCTURAL ELEMENTS.
<br />21. CONSTRUCTION BELOW THE RAISED FLOOR AND AT CRAWL SPACE INCLUDING LUMBERS AND TIMBERS
<br />SHALL BE GRADE 1 OR BETTER , JOISTS & BEAM THAT ARE AT LEAST 18" ABOVE GROUND SHALL BE
<br />CATEGORY 3B OR HIGHER AND POSTS, SILL PLATES AND BEAMS AND JOISTS LESS THAN 18" ABOVE THE
<br />GROUND SHALL BE CATEGORY 4A OR HIGHER AS SPECIFIED BY AWPA STANDARD U1.
<br />22. ALL CRIPPLE WALLS SHALL BE BRACED.
<br />23. ALL TOP AND BOTTOM CONTINUAL/ LONGITUDINAL BARS IN STRIP FOUNDATIONS SHALL HAVE
<br />STANDARD HOOKS AT THE ENDS.
<br />24. ALL TOP AND BOTTOM DISCONTINUED/ LOCAL BARS ( IN BOTH DIRECTIONS ) AT THE PAD/
<br />ISOLATED FOUNDATIONS SHALL HAVE STANDARD HOOKS AT THE ENDS.
<br />25. ALL SOG BARS SHALL HAVE STANDARD HOOKS AT THE ENDS.
<br />26. FOR DRAINAGE LAYOUT AND REQUIREMENTS, SEE ARCHITECTURAL/CIVIL DRAWINGS. DRAINAGE IS NOT
<br />INCLUDED IN STRUCTURAL ENGINEER'S SCOPE OF WORK.
<br />27. WHERE THE STEEL COLUMNS ARE EXPOSED TO WEATHER, BASE PLATES AND COLUMNS UP TO 12" ABOVE
<br />THE CONCRETE SLAB SHALL BE COATED WITH MIN. 2 COATS OF MACROPOXY 646.
<br />28. ALL PERMANENT STEELS IN CONTACT WITH WEATHER SHALL BE PROTECTED FOR CORROSION.
<br />29.ALL HANGERS ,COLUMN CAPS ,AND COLUMN BASES ARE MINIMUM REQUIREMENTS ,PRIOR TO ORDER ALL
<br />OF THEM SHALL BE CHECKED BY THE CONTRACTOR / FRAMER ANY DISCREPANCY SHALL BE REPORTED TO
<br />SEOR.
<br />30. FOR ALL BASE PLATES AND STEELS THAT ARE OUTSIDE OR UNDER GROUND, APPLY MIN. 2 COATS OF
<br />MACROPOXY 646 WITH MINIMUM 8 MILS THICKNESS.
<br />31. THE LOCATION, DIMENSIONS, AND SPECIFIC REQUIREMENTS FOR MECHANICAL EQUIPMENT PADS,
<br />INCLUDING HEAT PUMP UNITS AND CONDENSERS, SHALL BE COORDINATED BY THE ARCHITECT WITH THE
<br />MECHANICAL ENGINEER, EQUIPMENT MANUFACTURER, AND OTHER RELEVANT DISCIPLINES. FINAL PAD
<br />DIMENSIONS, CLEARANCES, ANCHORAGE REQUIREMENTS, AND EQUIPMENT LOADS SHALL BE PROVIDED BY
<br />THE MECHANICAL ENGINEER AND/OR MANUFACTURER.
<br />32. THE STRUCTURAL ENGINEER OF RECORD (SEOR) SHALL PROVIDE THE STRUCTURAL DESIGN OF THE PAD
<br />(E.G., THICKNESS, REINFORCEMENT) BASED SOLELY ON THE MECHANICAL LOADING AND LOCATION
<br />INFORMATION FURNISHED BY OTHERS. THE SEOR ASSUMES NO RESPONSIBILITY FOR DETERMINING
<br />EQUIPMENT LOCATION, UTILITY COORDINATION, ACCESSIBILITY, SERVICE CLEARANCE, VIBRATION
<br />ISOLATION, OR CONFORMANCE WITH MECHANICAL/ELECTRICAL CODES.
<br />33. ANY CHANGE IN EQUIPMENT WEIGHT, CONFIGURATION, OR LAYOUT SHALL BE COMMUNICATED TO THE
<br />SEOR FOR VERIFICATION OF STRUCTURAL ADEQUACY PRIOR TO CONSTRUCTION.
<br />C44HDU
<br />2
<br />MI
<br />N
<br />.
<br />
<br />3
<br />'
<br />-
<br />0
<br />"
<br />UN
<br />O
<br />
<br />O
<br />N
<br />
<br />H
<br />D
<br />U
<br />
<br />D
<br />E
<br />T
<br />A
<br />I
<br />L
<br />FOUNDATION
<br />WIDENING AT
<br />HOLD-DOWNS(TYP.)
<br />SEE HDU DETAIL
<br />HDU
<br />2
<br />C44
<br />SW1
<br />(8'-6")
<br />C44
<br />W/B
<br />C
<br />4
<br />0
<br />C44
<br />W/B
<br />C
<br />4
<br />0
<br />1
<br />DATE:
<br />P.M.:
<br />DRAWN BY:
<br />JOB NO.:
<br />30211 Avenida de las Banderas, Suite 200, Rancho Santa
<br />Margarita, California, 92688
<br />909-257-7040 WWW.BNDESIGNBUILDINC.COM
<br />THESE DRAWINGS AND SPECIFICATIONS ARE THE PROPERTY OF BN
<br />DESIGN BUILD AND SHALL NOT BE USED FOR ANY OTHER WORK
<br />EXCEPT BY AGREEMENT WITH BN DESIGN BUILD.
<br />D E SI GN
<br />B U I L D
<br />CNI
<br />UNIT 2, 606 S VAN
<br />NESS AVE,
<br />SANTA ANA,
<br />CA 92701
<br />ACCESSORY
<br /> DWELLING
<br /> UNIT
<br />REV DATE REMARKS
<br />M.A.
<br />ISSUED FOR PERMIT12.17.20240
<br />07.13.2025
<br />20241149
<br />ISSUED PER CITY COMMENT07.13.20251
<br />S2.01
<br />FOUNDATION PLAN
<br />07/15/2025
<br />EXP. 06-30-2026
|