CITY OF SANTA ANA <br />Planning and Building Agency <br />- FOUNDATION: <br />1. THE MINIMUM ULTIMATE COMPRESSIVE STRENGTH AT 28 DAYS SHALL BE 2500 PSI <br />UNO. <br />2. ALL CEMENT USED SHALL CONFORM TO A.S.T.M. C-150 TYPE V. <br />3. FINE AND COARSE AGGREGATE SHALL CONFORM TO A.S.T.M. C-33. <br />4. ALL CONCRETE UNLESS OTHERWISE NOTED ON PLANS WILL BE REGULAR WEIGHT <br />HARD ROCK TYPE (150 LB./CU.FT.) AGGREGATE SHALL CONFORM TO A.S.T.M. C-33 <br />WITH PROVEN SHRINKAGE CHARACTERISTICS PER A.S.T.M. C-157. <br />5. MAXIMUM SLUMP OF CONCRETE USED IN FLOOR SLAB AT FLAT WORK SHALL BE <br />FOUR (41 INCHES. <br />6. VIBRATION: VIBRATION OF CONCRETE SHALL BE IN ACCORDANCE WITH GENERAL <br />PROVISION OUTLINED IN PORTLAND CEMENT ASSOCIATION SPECIFICATIONS ST26. <br />7. CURING: CONCRETE SHALL BE MAINTAINED IN MOIST CONDITION FOR A MINIMUM OF <br />FIVE (5) DAYS AFTER ITS PLACEMENT. APPROVED CURING COMPOUND MAY BE <br />USED IN LIEU OF MOIST CURING. <br />8. STRENGTH TEST OF CONCRETE SHALL BE REQUIRED AS PER CODE AND OUTLINED IN <br />SPECIFICATION REPORT SHALL BE FORWARDED TO THE STRUCTURAL ENGINEER. <br />9. ANCHOR BOLTS, DOWELS, INSERT, ETC. SHALL BE SECURELY TIED IN PLACE PRIOR TO <br />POURING CONCRETE. <br />10. THE ENGINEER MUST APPROVE LOCATION OF CONSTRUCTION OR POUR JOINTS. <br />11. PIPES OR DUCTS EXCEEDING ONE THIRD THE SLAB, OR WALL THICKNESS SHALL NOT <br />BE PLACED IN STRUCTURAL CONCRETE UNLESS SPECIFICALLY DETAILED. SEE <br />MECHANICAL AND/OR ELECTRICAL DRAWINGS FOR LOCATION OF SLEEVES, ACCESSORIES <br />ETC. <br />12. PIPES MAY PASS THROUGH STRUCTURAL CONCRETE IN SLEEVES, BUT SHALL NOT BE <br />EMBEDDED THEREIN. <br />13. PROVIDE 3/4 INCH CHAMFER AT ALL EXPOSED CORNERS. <br />14. REFER TO ARCHITECTURAL DRAWINGS FOR MOLDS, GROOVES, ORNAMENTS, CLIPS, OR <br />GROUNDS REQUIRED TO BE CAST IN CONCRETE, AND FOR LOCATIONS OF FLOOR <br />FINISHED AND SLAB DEPRESSIONS. <br />15. CONTINUOUS INSPECTION BY A DEPUTY INSPECTOR IS REQUIRED FOR ALL CONCRETE <br />DESIGNED WITH F'C GREATER THAN 2500 PSI. <br />- CONCRETE <br />1. FOUNDATIONS SHALL BE OF THE SIZE AND TYPE AS INDICATED ON THE DRAWINGS. <br />2. FOOTINGS ARE TO BE CARRIED A MINIMUM OF 24" INTO FIRM UNDISTURBED, NATURAL <br />SOIL OR APPROVED COMPACTED -FILL. <br />3. DESIGN BEARING PRESSURE IS 1500 PSF IN UNDISTURBED NATURAL SOIL PER TABLE <br />1806.2. <br />4. DESIGN LATERAL BEARING PRESSURE IS 200 PSF./FT WITH A 33% FOR WINDS, THE <br />FOOTINGS OF THE PROPOSED STRUCTURES SHALL BE SUPPORTED COMPLETELY BY A <br />UNIFORM THICKNESS OF NON -EXPANSIVE COMPACTED SOIL. THE STRUCTURES SHALL <br />NOT BE SUPPORTED OVER A CUT/FILL TRANSITION. <br />5. CONTRACTOR TO PROVIDE FOR DE -WATERING OF EXCAVATIONS FROM EITHER SURFACE <br />WATER, GROUND WATER OR SEEPAGE, <br />6. ALL EXCAVATIONS SHALL BE PROPERLY BACK FILLED. DO NOT PLACE BACKFILL <br />BEHIND RETAINING WALLS BEFORE CONCRETE HAS ATTAINED FULL DESIGN STRENGTH. <br />CONTRACTOR SHALL BRACE OR PROTECT ALL INSTALLATION OF SUCH BRACING. <br />7. ALL ABANDONED FOOTINGS, UTILITIES, ETC., THAT INTERFERE WITH NEW <br />CONSTRUCTION SHALL BE REMOVED, NEW FOOTINGS MUST EXTEND INTO UNDISTURBED <br />SOILS. <br />8. FOUNDATION PLATES OR SILLS SHALL BE BOLTED TO THE FOUNDATION OR <br />FOUNDATION WALL WITH NOT LESS THAN 5/8" NOMINAL DIAMETER STEEL BOLTS <br />EMBEDDED AT LEAST 7" INTO THE CONCRETE OR MASONRY AND SPACED NOT MORE <br />THAN 4'-0" APART. THERE SHALL BE A MINIMUM OF TWO BOLTS PER PIECE WITH <br />ONE BOLT LOCATED WITHIN 12" OF EACH END OF EACH PIECE. A PROPERLY SIZED <br />NUT AND WASHER SHALL BE TIGHTENED ON EACH BOLT TO THE PLATE, USE <br />3"X3"X1/4" SQUARE WASHER SPECIFIED IN SECTION 2306, ALL INTERIOR NON -SHEAR <br />WALLS TO HAVE HILTI X-CR (WITH A MINIMUM PENETRATION OF 1-1/4" INTO SLAB) <br />AT 24 ON CENTER, UNLESS NOTED OTHERWISE, TO BE INSTALLED IN ACCORDANCE <br />WITH ICC ES# ESR-1663 AND LARR# 25646. ACTUAL SLAB THICKNESS TO BE MINIMUM <br />OF 3Y2". <br />9. CONTINUOUS FOOTING IN ADDITION (1) #4 BAR EXTRA FOR ELECTRICAL GROUND, <br />LOCATION TO BE VERIFIED WITH ELECTRICAL CONTRACTOR. <br />10. PROVIDE 2-#4 REINFORCING BAR TOP & BOTTOM OF ALL CONTINUOUS FOOTINGS. <br />- REINFORCING STEEL <br />0 <br />3 <br />4 <br />5 <br />6 <br />7 <br />Pal <br />0 <br />10, <br />ALL TYPICAL REINFORCING BARS SHALL CONFORM TO ASTM A-615, GRADE 60, <br />UNLESS NOTED OTHERWISE. <br />WELDED REBAR TO COMPLY WITH ASTM A-706 [Fy=60 KS11 AND WELDING <br />SHALL CONFORM TO AWS D1.4. WELDING TO BE DONE BY WELDERS CERTIFIED <br />BY BUILDING DEPARTMENT. <br />WELDED WIRE FABRIC SHALL BE MADE OF COLD DRAWN WIRE AND SHALL <br />CONFORM TO ASTM A-185 [Fy=65 KS11. MINIMUM LAP AT SPLICES OF 12 INCHES. <br />PROVIDE MESH IN FLAT SHEETS ONLY. ROLLED MESH IS NOT ACCEPTABLE. <br />OFFSET END -LAPS IN ADJACENT SHEETS TO PREVENT CONTINUOUS LAPS. <br />SPLICES : VERTICAL WALL BARS SHALL BE SPLICED AT NEAR FLOOR LINES. <br />SPLICE BARS IN MEMBERS SUCH AS SPANDRELS BEAMS, ETC. AS FOLLOWS: TOP <br />BARS AT CENTERLINE OF SPAN, BOTTOM BARS AT THE SUPPORT. ALL <br />REINFORCING STEEL SHALL BE SECURELY WIRED AND PROPERLY SUPPORTED <br />ABOVE GROUND AND AWAY FROM THE FORMS. SPLICES IN HORIZONTAL WALL <br />BARS SHALL BE CLASS B (30" MIN. & SHALL BE STAGGERED BY 5'-0" MIN. <br />HORIZONTAL SPLICES IN TWO CURTAINS WHERE USED SHALL NOT OCCUR IN THE <br />SAME LOCATION AND SHALL BE STAGGERED 5'-0" MIN. <br />- TOLERANCES FOR REBAR PLACEMENT: TOLERANCE FOR LONGITUDINAL <br />LOCATION OF BENDS AND ENDS OF REINFORCEMENT SHALL BE PLUS OR <br />MINUS TWO (2) INCHES, EXCEPT AT DISCONTINUOUS ENDS OF MEMBERS <br />WHERE TOLERANCES SHALL BE +/- 1/2 INCH. <br />REINFORCEMENT MAY NOT BE WET SET IN CONCRETE POUR. <br />NO ADMIXTURE SHALL BE ADDED TO THE CONCRETE WITHOUT THE APPROVAL <br />OF THE ENGINEER, UNLESS NOTED OTHERWISE. <br />CURING: CONCRETE SHALL BE MAINTAINED IN MOIST CONDITION FOR A MINIMUM <br />OF FIVE (5) DAYS AFTER ITS PLACEMENT. APPROVED CURING COMPOUND MAY <br />BE USED IN LIEU OF MOIST CURING. <br />BARS SHALL BE FIRMLY SUPPORTED AND ACCURATELY PLACED AS REQUIRED <br />BY THE ACI STANDARDS, USING TIE AND SUPPORT BARS IN ADDITION TO <br />REINFORCEMENT SHOWN WHERE NECESSARY FOR FIRM AND ACCURATE PLACING. <br />PROVIDE DOWELS TO MATCH ALL REINFORCEMENT AT POUR JOINTS, UNLESS <br />SHOWN OR NOTED OTHERWISE. ALL DOWELS AND BOLTS SHALL BE <br />ACCURATELY SET IN PLACE BEFORE PLACING CONCRETE. NO WELDING OF <br />REINFORCEMENT (INCLUDING TACK WELDING) SHALL BE DONE UNLESS SHOWN ON <br />THE DRAWINGS OR APPROVED BY THE ENGINEER. <br />REINFORCING STEEL SHALL HAVE THE FOLLOWING MINIMUM COVERAGE. PLACE BARS AS NEAR TO <br />THE CONCRETE SURFACE AS THESE MINIMUMS PERMIT WHEREVER POSSIBLE, UNLESS NOTED OTHERWISE: <br />STRUCTURAL ELEMENT <br />CONCRETE COVER <br />CONCRETE POURED AGAINST EARTH <br />3" <br />FORMED CONCRETE IN CONTACT WITH EARTH <br />2" <br />EXTERIOR FACE OF WALLS <br />2" <br />ALL OTHER WALL FACES <br />1 > <br />BEAMS <br />1-1/2" <br />(2" FOR <br />EXTERIOR) <br />REINF. SLABS <br />1-1/2" <br />(2" FOR <br />EXTERIOR) <br />COLUMNS <br />1-1/2" <br />(2" FOR <br />EXTERIOR) <br />- MECHANICAL ANCHORS AND ADHESIVES <br />1. MECHANICAL ANCHORS INTO CONCRETE: HILTI CARBON STEEL KWIK-BOLT TZ2 (ESR-4266) <br />OR RAMSET RED HEAD TRUBOLT (ESR-1799). <br />2. ADHESIVE ANCHORS AND DOWELS INSTALLED INTO CONCRETE AND GROUT -FILLED <br />MASONRY UNITS: EPDXY -TIE 'SET-XP' BY SIMPSON STRONG -TIE (ESR-2508). <br />3. ADHESIVE ANCHORS AND DOWELS INSTALLED INTO HOLLOW MASONRY UNITS AND <br />UNREINFORCED BRICK MASONRY (URM): EPDXY -TIE 'SET-XP' BY SIMPSON STRONG -TIE <br />(ESR-2508). USE SCREENS AS SPECIFIED BY THE MANUFACTURER. <br />4. MECHANICAL FASTENERS: STAINLESS STEEL FOR EXTERIOR USE OR WHEN EXPOSED TO <br />WEATHER. PROVIDE GALVANIZED CARBON STEEL ANCHORS AT OTHER LOCATIONS, UNLESS <br />OTHERWISE NOTED. <br />5. ADHESIVE ANCHORS: ASTM A36 THREADED RODS WITH ASTM A 563 GRADE A NUTS <br />AND ANSI B18.22.1 TYPE A WASHERS, UNLESS OTHERWISE NOTED. ANCHORS DESIGNATED <br />AS ASTM A193 GRADE B7 THREADED RODS TO USE ASTM A 563 GRADE DH HEAVY HEX <br />NUTS AND ASTM F 436 WASHERS. <br />6. ADHESIVE DOWELS: ASTM A615 GRADE 60 REINFORCING STEEL. <br />7. ALL ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH ICC ESR REPORT AND <br />MANUFACTURERS RECOMMENDATIONS. <br />8. UNLESS OTHERWISE NOTED, PROVIDE MINIMUM EMBEDMENT OF ANCHORS PER ICBO, COLA <br />REPORTS & MANUFACTURERS RECOMMENDATIONS. <br />9. PRIOR TO ALL DRILLING OR CORING, THE CONTRACTOR SHALL (1) VERIFY THE EXISTING <br />CONCRETE OR MASONRY THICKNESS TO PREVENT DAMAGE TO THE OPPOSITE FACE OF <br />CONCRETE AND MAINTAIN 1-1/2" CLEAR COVER U.N.O., AND (2) IDENTIFY EXISTING <br />REINFORCING LOCATIONS BY PACHHOMETER, PROBING, CHIPPING, ETC. TO AVOID DAMAGE <br />EXISTING REINFORCING. <br />10. IF REINFORCEMENT IS ENCOUNTERED DURING DRILLING, ABANDON AND SHIFT THE HOLE <br />LOCATION TO AVOID THE REINFORCEMENT. PROVIDE A MINIMUM OF 2 ANCHOR DIAMETERS <br />OR 1 INCH, WHICHEVER IS LARGER, OF SOUND CONCRETE BETWEEN THE DOWEL AND THE <br />ABANDONED HOLE. FILL THE ABANDONED HOLE WITH NON -SHRINK GROUT. IF THE ANCHOR <br />OR DOWEL MAY NOT BE SHIFTED AS NOTED ABOVE, THE ENGINEER WILL DETERMINE A <br />NEW LOCATION. <br />11. IF REINFORCEMENT IS ENCOUNTERED DURING DRILLING, ABANDON AND SHIFT THE HOLE <br />LOCATION TO AVOID THE REINFORCEMENT. PROVIDE A MINIMUM OF 2 ANCHOR DIAMETERS <br />OR 1 INCH, WHICHEVER IS LARGER, OF SOUND CONCRETE BETWEEN THE DOWEL AND THE <br />ABANDONED HOLE, FILL THE ABANDONED HOLE WITH NON -SHRINK GROUT. IF THE ANCHOR <br />OR DOWEL MAY NOT BE SHIFTED AS NOTED ABOVE, THE ENGINEER WILL DETERMINE A <br />NEW LOCATION. <br />STRUCTURAL STEEL <br />1. STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED AND ERECTED BY AN APPROVED AND <br />LICENSED FABRICATOR IN ACCORDANCE WITH PART I, PART III AND SUPPLEMENT NO.2 OF THE <br />SEISMIC PROVISIONS FOR STRUCTURAL STEEL BUILDINGS, APRIL 15, 1997, PUBLISHED BY (AISC). <br />THESE PROVISIONS SHALL BE APPLIED IN CONJUNCTION WITH CHAPTER 22, DIVISION II <br />2. ALL STRUCTURAL STEEL SHALL CONFORM TO THE ASTM DESIGNATION AS INDICATED BELOW <br />(UNO): <br />WF SHAPES A572, GRADE 50 <br />PIPE COLUMNS A-53, GRADE B <br />TUBE SECTIONS A-500, GRADE B <br />BOLTS A-325 <br />BOLTS IN CONCRETE/MASONRY A-307 <br />ANGLES, CHANNELS, WT SHAPES A-36 <br />3. THE STRUCTURAL STEEL FABRICATOR SHALL FURNISH SHOP DRAWINGS TO THE ARCHITECT OF <br />ALL STEEL FOR ARCHITECTS AND STRUCTURAL ENGINEERS REVIEW AND APPROVAL BEFORE <br />FABRICATION. <br />4. BOLT HOLES USED IN STEEL SHALL BE 1/16" LARGER IN DIAMETER THAN NOMINAL SIZE OF <br />BOLT USED, EXCEPT AS NOTED. <br />5. ALL STRUCTURAL STEEL SURFACES THAT ARE ENCASED IN CONCRETE, OR MASONRY, SPRAY ON <br />FIREPROOFING, OR ARE ENCASED BY BUILDING FINISH, SHALL BE LEFT UNPAINTED. <br />6. ALL WELDING IS TO BE DONE BY CERTIFIED WELDERS USING E70XX ELECTRODES (UNO). ALL <br />WELDS SHALL BE IN CONFORMITY WITH THE PROJECT SPECIFICATIONS AND THE CODE FOR <br />WELDING IN BUILDING CONSTRUCTION (AWS D1.1 LATEST REVISION) OF THE AMERICAN WELDING <br />SOCIETY. SEE SPECIAL INSPECTIONS SECTION FOR WELDING INSPECTION REQUIREMENTS. <br />7. WELD LENGTHS CALLED FOR ON PLANS ARE THE NET EFFECTIVE LENGTH REQUIRED. WHERE <br />FILLET WELD SYMBOL IS GIVEN WITHOUT INDICATION OF SIZE, USE MINIMUM SIZE WELDS AS <br />SPECIFIED IN AISC MANUAL OF STEEL CONSTRUCTION 9TH EDITION, SECTION J2.1b <br />8. ALL EXPOSED STRUCTURAL STEEL AND MISCELLANEOUS METAL SHALL BE HOT DIP GALVANIZED <br />AFTER FABRICATION. <br />9. ALL BOLTS USED IN SEISMIC FORCE RESISTING SYSTEM SHALL BE FULLY TENSIONED, HIGH <br />STRENGTH BOLTS. <br />10. LADBS LICENSED FABRICATOR IS REQUIRED FOR STRUCTURAL STEEL. <br />11. STRUCTURAL <br />STEEL USED IN SEISMIC <br />LOAD RESISTING (SLRS) SHALL MEET REQUIREMENTS OF <br />AISC <br />360 SECTION <br />A 3.1A EXCEPT AS MODIFIED <br />BY AISC 341. THE MINIMUM YIELD STRESS OF STEEL <br />TO BE USED <br />FOR MEMBERS IN WHICH <br />INELASTIC BEHAVIOR IS EXPECTED SHALL NOT EXCEED <br />50 <br />KSI FOR SMF <br />AND IMF, NOR EXCEED <br />55 KSI FOR OMF, UNLESS THE SUITABILITY OF THE <br />MATERIAL IS <br />DETERMINED BY TESTING <br />OR OTHER RATIONAL CRITERIA. THIS LIMITATION DOES <br />NOT <br />APPLY TO COLUMNS FOR WHICH THE <br />ONLY EXPECTED INELASTIC BEHAVIOR IS YIELDING AT <br />THE <br />COLUMN BASE. <br />- WELDING: <br />1. WELDING SHALL BE PERFORMED IN ACCORDANCE WITH A WELDING PROCEDURE <br />A <br />SPECIFICATION (WPS) AS REQUIRED IN AWS D1.1, 2000 AND APPROVED B <br />ENGINEER <br />OF RECORD. <br />FOR <br />CE <br />2, THE CONTRACTOR SHALL PROVIDE WELDING PROCEDURE SPECIFICATION (WFS) <br />FOR <br />a I <br />REVIEW AND APPROVAL PRIOR TO STARTING OF FABRICATION. THE WELD <br />NG <br />Engineering <br />ELECTRODE MANUFACTURERS' SPECIFICATIONS SHOULD BE ATTACHED TO T <br />E WPS ON <br />15041 Genoa Cir, <br />ALL JOBS. ALL WELDERS AND INSPECTORS SHALL BE INFORMED OF AND <br />MUST ADHERE <br />TO THE WPS AND SHALL RETAIN A COPY. <br />Master I <br />Huntinggton Beach, CA 92647 <br />T: (714) 519-5027 <br />E: atefg®fastructural.com <br />3. ALL COMPLETE -JOINT -PENETRATION GROOVE WELDS USED IN SEISMIC FORC <br />6ITe.G <br />www.fastructural.com <br />SYSTEM SHALL BE MADE WITH A FILLER METAL THAT HAS A MINIMUM <br />V 0 <br />TOUGHNESS OF 20 FT-LBS AT MINUS 20°F. <br />4. WELDING OF STRUCTURAL STEEL SHALL BE BY MANUAL SHIELD METAL ARC OR <br />SUBMERGED ARC PROCESS USING E70XX ELECTRODES. <br />5. LENGTHS OF WELDS ARE EFFECTIVE LENGTHS AS SPECIFIED IN THE UNIFORM BUILDING <br />CODE, WHERE LENGTH OF WELD IS NOT SHOWN IT SHALL BE FULL LENGTH OF JOINT. <br />ALL BUTT WELDS SHALL BE FULL PENETRATION UNLESS NOTES OTHERWISE. <br />6. WELDERS SHALL BE QUALIFIED FOR THE WORK THEY WILL BE DOING AND SHALL <br />HAVE CERTIFICATIONS CURRENT. <br />7. FACES OF FILLET WELDS EXPOSED TO VIEW SHALL HAVE AS -WELDED SURFACES THAT <br />ARE REASONABLY SMOOTH AND UNIFORM. NO FINISHING OR GRINDING SHALL BE <br />REQUIRED, EXCEPT WHERE CLEARANCES OR FIT OF OTHER ITEMS MAY SO NECESSITATE <br />8. ALL PARTIAL AND FULL PENETRATION WELDS THAT ARE EXPOSED TO VIEW SHALL BE <br />GROUND SMOOTH AND FLUSH WITH FINISH SURFACE OF STEEL. HOLES SHALL BE <br />FILLED WITH WELD METAL OR BODY SOLDER AND SMOOTHED BY GRINDING OR FILING, <br />9. CLEAN GROOVE PREPARATION THERMAL CUTS BY GRINDING. <br />10. WELDS SHALL BE TERMINATED AT THE END OF A JOINT IN A MANNER THAT WILL <br />ENSURE SOUND WELDS. WHENEVER NECESSARY THIS SHALL BE DONE BY USE OF <br />EXTENSION BARS AND RUN OFF TABS. RUN OFF TABS USED AT BEAM FLANGE <br />CONNECTION SHALL BE REMOVED AND THE WELDS FINISHED TO A SMOOTH CONTOUR <br />(1" RADIUS). NO WELD DAMS ARE ALLOWED. <br />11. AFTER FULL PENETRATION WELDING, THE BACKING BAR IS TO BE REMOVED, THE WELD <br />ROOT INSPECTED AND TESTED FOR IMPERFECTIONS,WHICH IF FOUND, ARE TO BE <br />REMOVED BY BACKGOUGING TO SOUND MATERIAL. THE BACKGOUGED AREA IS TO BE <br />WELDED AND A FILLET WELD SHALL BE APPLIED TO REINFORCE THE JOINT. THE SIZE <br />OF THE REINFORCING FILLET WELD SHALL BE EQUAL TO 1/4 THE PLATE THICKNESS, <br />BUT NOT LESS THAN 1/4" NOR MORE THAN 3/8". <br />12. TO ASSURE THE PROPER AMPERAGE AND VOLTAGE OF THE WELDING PROCESS, THE <br />USE OF A HAND HELD CALIBRATED AMP AND VOLT METER SHALL BE USED. THIS <br />EQUIPMENT SHALL BE USED BY THE FABRICATOR, ERECTOR AND THE INSPECTORS. <br />AMPERAGE AND VOLTAGE SHALL BE MEASURED AT THE ARC WITH THIS EQUIPMENT. <br />TRAVEL SPEED AND ELECTRODE STICK OUT SHALL BE VERIFIED TO BE IN COMPLIANCE <br />WITH THE ELECTRODE MANUFACTURER'S RECOMMENDATIONS. <br />13. ULTRASONIC TESTING IS REQUIRED FOR ALL PARTIAL AND COMPLETE PENETRATION <br />WELDS. TEST GROVE WELDING ON CONTINUITY PLATES BY ULTRASONIC TESTING AFTER <br />BEAM FLANGE WELD CONNECTION. TESTING SHALL BE PERFORMED NO SOONER THAN 24 <br />HOURS AFTER COMPLETION OF WELDING. <br />14. DISCONTINUITIES IN WELD CREATED BY ERRORS OR BY FABRICATION OR ERECTION <br />OPERATIONS SUCH AS TACK WELDS, ERECTION AIDS, AIR -ARC GOUGING AND FLAME <br />CUTTING, SHALL BE REPAIRED AS REQUIRED BY THE ENGINEER OF RECORD. <br />15. FOR CONNECTIONS WITH WELDED FLANGE JOINTS, WELDED BACKING AND RUN-OFF <br />TABS SHALL BE REMOVED AND REPAIRED INCLUDING THE USE OF REINFORCING FILLET <br />WELD, EXCEPT THAT THE TOP -FLANGE BACKING IS PERMITTED TO REMAIN IN PLACE <br />IF IT IS ATTACHED TO THE COLUMN FLANGE WITH A CONTINUOUS FILLET WELD ON <br />THE EDGE BELOW THE COMPLETE -JOINT -PENETRATION GROOVE WELD. <br />16. FIELD WELDING TO BE DONE BY WELDERS CERTIFIED BY THE LA DBS FOR <br />STRUCTURAL STEE, REINFORCING STEEL AND LIGHT GAGE STEEL. CONTINUOUS <br />INSPECTION BY A DEPUTY INSPECTOR IS REQUIRED. <br />17. SHOP WELDS MUST BE PERFORMED IN LA CITY BUILDING DEPT, LICENSED FABRICATOR <br />SHOP. <br />,S <br />NO.84252 <br />21� <br />s�5 0WRL <br />,r / <br />Project Name <br />Z <br />Q <br />N <br />W <br />� <br />Z <br />= <br />� <br />0O <br />o_ <br />Q <br />-� <br />.. <br />J <br />O) <br />Q <br />0 <br />W <br />0 <br />�U <br />Q <br />Z <br />06 <br />o <br />W <br />3: <br />J <br />o <br />DQ <br />O <br />- <br />0 <br />+1 <br />_ <br />cf) <br />E <br />J <br />0 <br />N <br />U) <br />Z <br />Q <br />2 <br />Project ID <br />01-23 <br />Drawing Title <br />DATE <br />R-2 <br />05-14-2025 <br />R-1 <br />11-07-2024 <br />R-0 <br />08-16-2024 <br />Rev. <br />Desciption <br />Date <br />Drawing No. <br />S-002 <br />