1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ACCURATELY SIZING, LOCATING, AND CUTTING
<br /> ALL OPENINGS REQUIRED FOR FIRE PROTECTION SYSTEMS. REFERENCE I SERIES DRAWINGS
<br /> FOR PENETRATION DETAILS. COORDINATE WITH CONTRACTOR INSTALLING / RESPONSIBLE FOR
<br /> INSTALLING THE WALL, FLOOR, PANEL, CEILING, FOUNDATION OR ROOF.
<br />PENETRATION DETAILS
<br />PIPE MATERIAL / VALVE SCHEDULE
<br />SYSTEM DESCRIPTION LOCATION SIZES MATERIAL
<br />PIPING
<br />STANDARDS METHOD
<br />CONNECTIONS / FITTINGS
<br />STANDARDS TYPE
<br />VALVES
<br />METHOD NOTES
<br />FIRE PROTECTION ABOVE GROUND ASTM A 135 / A 135 M
<br />ASTM A 795 / A 795 M
<br />ASTM B16.3
<br />ASTM A 536
<br />ISOLATION VALVES
<br />CLASS RATED
<br />150 PSI SWP, 600 PSI NON-SHOCK CWP
<br />125 PSI SWP, 200 PSI NON-SHOCK CWPN/A
<br />FIRE PROTECTION ABOVE GROUND 2" & SMALLER ASTM A135 / A 135 M
<br />ASTM A795 / A 795 M
<br />ASME B36.10M2-1/2" & LARGER
<br />FIRE PROTECTION ABOVE GROUND 2" & SMALLER ASTM A53 / A 53 M
<br />2-1/2" & LARGER
<br />GROOVED-END
<br />ASTM A 47/A 47M
<br />ASTM B16.3
<br />ASTM A 536
<br />ANGLE VALVES
<br />BUTTERFLY VALVES
<br />175 PSI SWP, 400 PSI NON-SHOCK CWP
<br />GATE VALVES
<br />GLOBE VALVES
<br />ISOLATION VALVES
<br />BUTTERFLY VALVES
<br />GATE VALVES
<br />ISOLATION VALVES
<br />BUTTERFLY VALVES
<br />GATE VALVES
<br />ASTM A 47/A 47M
<br />ASTM B16.3
<br />ASTM A 536
<br />150 PSI SWP, 600 PSI NON-SHOCK CWPN/A
<br />150 PSI SWP, 600 PSI NON-SHOCK CWPN/A
<br />125 PSI SWP, 200 PSI NON-SHOCK CWP
<br />125 PSI SWP, 200 PSI NON-SHOCK CWP
<br />100 PSI SWP, 150 PSI NON-SHOCK CWP
<br />100 PSI SWP, 150 PSI NON-SHOCK CWP
<br />GROOVED-END
<br />FLANGED
<br />CONDENSATE DRAIN ABOVE GROUND 2" & SMALLER COPPER TUBE, TYPE L, HARD DRAWN ASTM B88 LEAD FREE 95-5,
<br />TIN/ANTIMONY SOLDER
<br />ASTM B16.18,
<br />ASTM B16.22
<br />ISOLATION VALVES
<br />GLOBE VALVES
<br />THREADED 95/5 LEAD FREE SOLDER
<br />CHECK VALVES
<br />150 PSI SWP, 600 PSI NON-SHOCK CWP
<br />125 PSI SWP, 200 PSI NON-SHOCK CWP125
<br />GATE VALVES
<br />N/A
<br />GALVANIZED STEEL, SCHEDULE 30
<br />GALVANIZED STEEL, SCHEDULE 40
<br />BLACK STEEL, SCHEDULE 40, GRADE B
<br />BLACK STEEL, SCHEDULE 30 THREADED
<br />GROOVED-END
<br />GALVANIZED STEEL, SCHEDULE 10
<br />BLACK STEEL, SCHEDULE 10
<br />THREADED
<br />2-1/2" & LARGER
<br />THREADED
<br />GROOVED-END
<br />GROOVED-END
<br />FLANGED
<br />THREADED
<br />GROOVED-END
<br />COMPRESSED AIR ABOVE GROUND 2" & SMALLER
<br />2-1/2" & LARGER
<br />BLACK STEEL, SCHEDULE 40,
<br />TYPE E or S, GRADE B
<br />ASTM A 53/A 53M
<br />GROOVED-END
<br />ASME B16.3, CLASS 150 or 300
<br />BUTTERFLY VALVES
<br />THREADED
<br />ASTM A 47/A 47M FLANGED
<br />CHECK VALVES
<br />200 PSI NON-SHOCK CWP
<br />125 PSI SWP, 200 PSI NON-SHOCK CWP2" & SMALLER
<br />2-1/2" & LARGER 125 PSI SWP, 200 PSI NON-SHOCK CWP
<br />125
<br />THREADED
<br />GROOVED-END
<br />ASME B16.3, CLASS 150 or 300
<br />ASTM A 47/A 47M
<br />THREADED
<br />FLANGED
<br />ISOLATION VALVES THREADEDTHREADED 150 PSI SWP, 600 PSI NON-SHOCK CWPN/A
<br />DISCLAIMER:
<br />FIRE PROTECTION DRAWINGS BEING SUBMITTED ARE INTENDED TO BE
<br />PERFORMANCE-LEVEL DOCUMENTS TO REFLECT SPACE / HAZARD
<br />CLASSIFICATIONS AND PRELIMINARY DESIGN COORDINATION DETAIL,
<br />ONLY. FINAL FIRE PROTECTION DESIGN SUBMISSION FOR PERMITTING
<br />WILL BE THE RESPONSIBILITY OF THE FIRE PROTECTION CONTRACTOR.
<br />1. THE FIRE PROTECTION PACKAGE IS A PERFORMANCE LEVEL
<br />PACKAGE INTENDED TO DEFINE THE SCOPE AND NATURE OF THE
<br />DELEGATED WORK. THE FIRE PROTECTION CONTRACTOR SHALL
<br />PROVIDE THE FINAL DESIGN IN ACCORDANCE WITH THIS DESIGN
<br />PACKAGE AND SHALL COMPLY WITH APPLICABLE OWNERS'
<br />INSURANCE COMPANY AND FM GLOBAL DESIGN CRITERIA.
<br />2.THE FIRE PROTECTION CONTRACTOR OR THEIR ASSOCIATED
<br />DESIGN CONSULTANT SHALL BE LICENSED OR OTHERWISE
<br />AUTHORIZED IN THE STATE OF CALIFORNIA TO PERFORM THE DESIGN
<br />WORK INVOLVED AND SHALL SIGN AND CERTIFY IF REQUIRED BY
<br />THE AHJ.
<br />3. SITE VISITATION: VISIT THE SITE OF THE PROPOSED
<br /> CONSTRUCTION TO BECOME THOROUGHLY FAMILIAR WITH ALL
<br /> DETAILS OF THE WORK AND WORKING CONDITIONS. VERIFY ALL
<br /> DIMENSIONS IN THE FIELD, AND ADVISE OWNER ON SITE
<br /> SUPERVISION OF ANY DISCREPANCY BEFORE PERFORMING ANY
<br /> WORK.
<br />4. HYDROSTATICALLY TEST ENTIRE SYSTEM IN ACCORDANCE WITH
<br /> FM GLOBAL. SYSTEM SHOULD BE TESTED TO 200 PSI OR 50 PSI
<br /> ABOVE THE MAXIMUM SYSTEM OPERATING PRESSURE
<br /> (WHICHEVER IS GREATER) FOR A MINIMUM OF 2 HOURS.
<br />5. INSTALL PIPING IN ACCORDANCE WITH FM GLOBAL FOR
<br /> SPRINKLER SYSTEMS, STANDPIPE AND HOSE
<br /> SYSTEMS (AS APPLICABLE).
<br />6. DO NOT ROUTE SPRINKLER PIPING DIRECTLY ABOVE ELECTRICAL
<br /> PANELS PER NATIONAL ELECTRICAL CODE AND THE
<br /> AUTHORITY HAVING JURISDICTION.
<br />7. FIRE PROTECTION PIPING SHOULD NOT BE ROUTED OR TERMINATE IN
<br /> FRONT OF WINDOWS.
<br />8. PROVIDE SPRINKLER COVERAGE BELOW ANY DUCTWORK,
<br /> CATWALKS, PLATFORMS AND/OR ANY OTHER OBSTRUCTION
<br /> GREATER THAN 4'-0" WIDE AS REQUIRED TO MAINTAIN CEILING
<br /> DENSITY REQUIREMENTS.
<br />9. SPRINKLER TEMPERATURE RATINGS IDENTIFIED IN THE ROOM SCHEDULE
<br /> DEPICT GENERAL ROOM REQUIREMENTS.SOME SPRINKLERS
<br /> MAY REQUIRE HIGHER TEMPERATURE RATINGS DEPENDING ON THE
<br /> LOCATION OF SPRINKLERS RELATIVE TO HEAT PRODUCING EQUIPMENT,
<br /> PIPING, ETC.THE FIRE PROTECTION CONTRACTOR SHALL REVIEW
<br /> PROJECT DRAWINGS TO IDENTIFY ANY AREAS WHERE HIGHER SPRINKLER
<br /> TEMPERATURE RATINGS ARE REQUIRED PER FM GLOBAL.
<br />GENERAL NOTES:
<br />Fire Protection Zones
<br />1
<br />NOT REQUIRED
<br />DOCK ADDITION
<br />131
<br />TEMPORARY
<br />TENT
<br />133
<br />1
<br />2
<br />3
<br />MAX. CEILING TEMP. (°F)
<br />100
<br />TEMP. RATING (°F)
<br />135-170
<br />TEMP. CLASSIFICATION (°F)
<br />ORDINARY
<br />COLOR CODE
<br />BLACK OR NONE
<br />GLASS BULB COLOR
<br />RED OR ORANGE
<br />150 175-225 INTERMEDIATE WHITE YELLOW OR GREEN
<br />225 250-300 HIGH BLUE BLUE
<br />300 325-375 EXTRA HIGH RED PURPLE
<br />375 400-475 VERY EXTRA HIGH GREEN BLACK
<br />475 500-575 ULTRA HIGH ORANGE BLACK
<br />625 650 ULTRA HIGH PINK BLACK
<br />SPRINKLER HEAD TEMPERATURE RATINGS AND COLOR CODINGS
<br />DRAWN BY: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
<br />CHECKED BY: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
<br />SHEET ISSUE DATE: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
<br />SHEET NUMBER
<br />THE INFORMATION CONTAINED ON THIS AND ANY
<br />RELATED DOCUMENT SHALL NOT BE USED FOR
<br />ANY PURPOSE OTHER THAN THE CONVEYANCE
<br />OF INFORMATION FOR THE STATED CLIENT AND
<br />PROJECT WITHOUT THE EXPRESS WRITTEN
<br />CONSENT OF THE ENGINEER.
<br />ANY INFORMATION TRANSFERRED OR UTILIZED
<br />IN AUTOCAD .DWG FORMAT SHALL BE USED FOR
<br />REFERENCE ONLY
<br />WEBBER/SMITH Associates, Inc.
<br />20 Wright Avenue
<br />Lititz, Pennsylvania 17543
<br />Phone: 717.625.4140
<br />Email:info@webbersmith.com
<br />SHEET TITLE:
<br />FOR
<br />DRAWING STATUS
<br />FINAL
<br />PROJECT NUMBER
<br />www.webbersmith.com
<br />SEAL
<br />F-001-1
<br />KCH
<br />JSD
<br />04/02/2024
<br />OVERALL FIRE
<br />PROTECTION PLAN
<br />2350 Pullman WSS OCTA Aspire
<br />Bakeries
<br />2350 Pullman Street
<br />Santa Ana, CA 92705
<br />CA
<br />5387
<br />© 2024 WEBBER/SMITH Associates, Inc., All Rights Reserved
<br />2350
<br />Pullman,LLC
<br />AREA OF PRODUCTION APPLICABLE FM DATA SHEET
<br />PRODUCTION, UTILITY, OFFICE /
<br />EMPLOYEE SPACES 3.26
<br />SHEET INDEX - FIRE PROTECTION -
<br />SHEET
<br />NUMBER SHEET NAME
<br />F-001-1 OVERALL FIRE PROTECTION PLAN
<br />1/16" = 1'-0"F-001-1
<br />5 DESIGN CRITERIA - FIRE PROTECTION ZONES Fire Protection Room Schedule Phase 1
<br />Number Name Area (SF) Room Temperature (°F) FP Occupancy FP Zone FP System Type FP SPRINKLER TYPE
<br />FP STAINLESS STEEL
<br />REQUIREMENT FP NOTES
<br />131 DOCK ADDITION 1714 72-75 HC-1 1 WET UPRIGHT -
<br />1 AREA TO BE SERVICED OFF OF THE
<br />EXISTING RISER SERVING THE REST OF THE
<br />BUILDING. EXTEND SPRINKLER PIPING AND
<br />PROVIDE NEW SPRINKLER HEADS.
<br />SHEET KEYED NOTES 1X
<br />2 NEW SPRINKLER PIPING SHALL BE
<br />CONFIGURED TO ACCOMMODATE
<br />APPROXIMATELY 630 SF ADDITION
<br />ASSOCIATED WITH PHASE 2.
<br />3 FOR THIS PROJECT, PROVIDE THE SAME
<br />TYPE OF SPRINKLER HEADS USED IN THE
<br />EXISTING FACILITY.
<br />1. DELEGATED DESIGN: ENGAGE A QUALIFIED PROFESSIONAL ENGINEER TO
<br />DESIGN SEISMIC CONTROLS FOR FIRE SUPPRESSION PIPING.
<br />2.SEISMIC DESIGN CALCULATIONS: PERFORM CALCULATIONS TO OBTAIN
<br />FORCE INFORMATION NECESSARY TO PROPERLY SELECT RESTRAINT
<br />DEVICES, FASTENERS, AND ANCHORAGE.
<br />VIBRATION AND SEISMIC CONTROLS FOR FIRE SUPPRESSION PIPING
<br />NO. DATE DESCRIPTION
<br />A 04/02/2024 ISSUED FOR PERMIT AND
<br />CONSTRUCTION
<br />REGISTERED PROFESSIONAL ENGINEER33478
<br />JAMES S DEPEW
<br />STATE OF CALIFORNIAMECHANICAL
<br />4/2/24
<br />2350 S Pullman St -
<br />Phase I3/4/2025
|