Company JOB TITLE 2350 Pullman, LLC <br />Webber/Smith Associates <br />Lititz, PA JOB NO.5387 SHEET NO. <br />(717) 625-4140 CALCULATED BY DATE <br />CHECKED BY DATE <br />3/5/24 <br />3/5/24 <br />Location of C&C Wind Pressure Zones - ASCE 7-16 <br />Roofs w/ θ ≤ 10° Walls h ≤ 60' <br />and all walls & alt design h<90'and Gable θ ≤7 degrees &Monoslope roofs <br />h > 60'Monoslope ≤ 3 degrees 3° < θ ≤ 10° <br />h ≤ 60' & alt design h<90'h ≤ 60' & alt design h<90' <br />Monoslope roofs Multispan Gable > 10° Hip 7°< θ ≤ 27° <br />10° < θ ≤ 30°& Gable 7°< θ ≤ 45° <br />h ≤ 60' & alt design h<90' <br />Sawtooth 10° < θ ≤ 45° <br />h ≤ 60' & alt design h<90' <br />Stepped roofs θ ≤ 3° <br />h ≤ 60' & alt design h<90' <br />Note: The hatched area indicates <br />where roof positive pressures are <br />equal to the adjacent wall positive <br />pressure. <br />Multispan Gable & Sawtooth ≤ 10° <br />Note: The stepped roof zones above are as shown in ASCE 7-16 . Prior editions didn't show zones, <br />but the notes sent you to the low slope gable figure. The note in ASCE 7-16 still sends you to the low <br />slope gable figure, but for some reason the zones shown are per editions prior to ASCE 7-16. <br />Therefore, the above zones may be a code mistake and the correct zone locations may be per the low <br />slope gable roof shown at the top of this page. <br />2.5 <br />2350 S Pullman St - <br />Phase I3/4/2025