Laserfiche WebLink
CITY OF SANTA ANA <br />SPECIFICATIONS <br />PROJECT NO.: XX-XXXX <br />PROJECT TITLE <br /> <br />105 <br />shall be replaced at the Contractor's expense. The new link shall then be <br />tested to demonstrate acceptability. Copies of the test results shall be <br />submitted to the Engineer for approval. <br />b. Test Failures <br />If during any of these system verification tests, the results prove to be <br />unsatisfactory, the fiber optic cable and or defective splice enclosures will <br />not be accepted. The unsatisfactory components shall be replaced at the <br />Contractor's expense. The new segment of cable shall undergo the same <br />testing procedure to determine acceptability. Copies of the test results <br />shall be submitted to the Engineer for approval. The removal and <br />replacement of a segment of cable shall be interpreted as the removal and <br />replacement of a single contiguous length of cable connecting two splices, <br />two connectors, or a splice and a connector. The removal of only the <br />small section containing the failure and therefore introducing new <br />unplanned splices will not be allowed. <br />4.33 CLOSED CIRCUIT TELEVISION (CCTV) SYSTEM <br />When CCTV system is required, the Contractor shall furnish and install Axis Q6 155-E <br />PTZ Network Camera as shown on the plan. The CCTV system shall consist of <br />camera/pan-tilt assembly, mounting, cables, conductors and wires, control software and <br />video management system licensing. <br />1. Mounting <br />The Contractor shall mount the integrated camera/position unit on existing traffic <br />signal pole as shown on plans and per manufacturer’s recommendation. The <br />Contractor shall verify the mounting requirements of the integrated camera/position <br />unit, and the suitability of the approach depicted in these plans. The C ontractor may <br />request approval for alternate mounting details by submitting a shop drawing signed <br />by a registered Engineer. <br />2. Video Cable <br />The Contractor shall furnish and install manufacturer recommended Outdoor CAT-6 <br />Ethernet cable with IP66-rated connectors and incidental hardware from the camera <br />to an Ethernet switch in the cabinet to establish circuit continuity. The cable shall be <br />installed without damaging the conductors, dielectric or jacket. The cable ass embly <br />shall not be kinked or bent tighter than the Manufacturer's recommended bending <br />radius. <br />3. Testing <br />The Contractor shall test and document the installation and operation of all material, <br />equipment, cables and connectors for continuity, shorts or grounds. The Contractor <br />shall also carry out system integration testing to ensure that the video interface and <br />505 E Central Ave <br />#B11/6/2024