Laserfiche WebLink
PAGE <br />REV: F 6/2/2025 <br />2500 WHITE RD. SUITE A, IRVINE CA 92614 <br />PHONE 805.540.7603 <br />FAX 949.215.7778 <br />EFREN LUMBRERAS <br />2100 E WELLINGTON AVE, <br />SANTA ANA, CA, 92701 <br />PROJECT NUMBER: <br /> 109R-100LUMB <br />SHEET <br />DESIGNER: <br />KEVIN SIN <br />CUSTOMER RESIDENCE: <br />TEL. (949) 763-0025 <br />APN: 400-153-29 <br />GILBERT CORREIA, C10, C46 <br />CA CL #750184 <br />(415) 580-6920 ex3 <br />PV-2.1 <br />INTERIOR GARAGE WALL <br />ACD <br />ESS ELEVATION VIEW - SCALE = NTS <br />ESS ELEVATION VIEW <br />ESS ELEVATION VIEW <br />PW3 <br />ESS SHALL BE INSTALLED 3FT FROM DOORS AND WINDOWS IN ACCORDANCE WITH R328.4. <br />ESS UNITS SHALL BE SEPARATED FROM EACH OTHER BY NOT LESS THAN 3 FEET EXCEPT <br />WHERE SMALLER SEPARATION DISTANCES ARE DOCUMENTED TO BE ADEQUATE BASED ON <br />LARGE/SCALE FIRE TESTING. <br />NO DWELLING DOORS OR WINDOWS ARE IN NEARBY <br />HEAT SENSOR <br />15' <br />3'MIN <br /> A HEAT DETECTOR, LISTED AND INTERCONNECTED TO THE SMOKE <br />ALARMS, SHALL BE INSTALLED IN LOCATIONS WITHIN DWELLING UNITS <br />AND ATTACHED GARAGES WHERE SMOKE ALARMS CANNOT BE INSTALLED <br />BASED ON THEIR LISTING. <br />F <br />Signed: 06/03/2025 <br />Revision to 20184282 issued on 11/18/2024 <br />Rev 1 # 20185569 <br />APPROVALS: <br />ELECT - M. Smith