THESE DRAWINGS REPRESENT THE POOL & SPA FEATURE FOR THIS PROJECT
<br />ALL DECKING LIMITS, DRAINAGE, WALKWAYS, FENCING DESIGN, BATHROOMS
<br />DESIGN, UTILITIES, AND OTHER STRUCTURES SHOWN ON THE PLAN SHALL BE
<br />DOCUMENTED BY OTHER DISCIPLINES. THE CONTRACTED SCOPE OF WORK
<br />REPRESENTS THE FOLLOWING:
<br />SPECIFICATIONS:
<br />·POOL & SPA TYPE: ELEVATED IN STRUCTURE
<br />·POOL & SPA SIZE: PER DESIGN REQUIREMENTS
<br />·CONSTRUCTION TYPE: PNEUMATICALLY PLACED CONCRETE
<br />·WALL AND FLOOR COATING: WHITE PLASTER
<br />·FILTRATION SYSTEM: HIGH RATE SAND FILTRATION SYSTEM
<br />·SANITATION SYSTEM: CHEMICAL PUMPS AND TANKS, CHEMISTRY
<br />CONTROLLER
<br />·ACCESSORIES: LIFE SAFETY EQUIPMENT AND SIGNAGE - DESIGN PER
<br />LOCAL CODE
<br />·DECK EQUIPMENT: HANDRAILS, ANCHORS, ADA LIFT AS REQUIRED
<br />INCLUDED IN POOL PACKAGE:
<br />·INSTALL OF POOL & SPA SHELL SHELL AND PIPING.
<br />·POOL & SPA INSTALLED AS A COMPLETE WORKING SYSTEM.
<br />·POOL & SPA EDGE COPING EDGE WITH PROVISIONS FOR DECKING.
<br />·INSTALLATION OF INTERIOR SURFACE.
<br />·TILE AT BORDER OF POOL WITH DEPTH MARKINGS.
<br />·COMPLETE FILTRATION AND SANITATION EQUIPMENT.
<br />·ELECTRICAL PANEL WITH CHEMICAL FEED INTERLOCK PROVIDED BY G.C.
<br />·INTERIOR LIGHTING TO GFCI CIRCUIT.
<br />·INTERCONNECTION OF POOL PIPING TO FILTRATION SYSTEM. (Sch. 80 PVC)
<br />·HAND RAILS, GRAB RAILS, DECK ANCHORS, SAFETY AND TEST EQUIPMENT.
<br />ASME HEATER (NG) - GAS LINE PROVIDED BY G.C.
<br />·ADA LIFT ANCHOR WITH REMOVABLE LIFT.
<br />·CONNECTION OF FRESH WATER FILL PROVIDED BY G.C. (PROTECTED) TO
<br />AUTOMATIC WATER LEVEL SYSTEM.
<br />·RELATED PERMITTING AND INFORMATION.
<br />·START-UP AND OWNER TRAINING.
<br />·INITIAL CHEMICAL BATCH AND WATER BALANCING.
<br />·OPERATION GUIDE MANUAL.
<br />COMMON PROPERTY NAME: SANI-CHLOR - HYPOCHLORITE (BLEACH) - NaOCL
<br />MATERIAL: OXIDIZER
<br />CLASS: 1
<br />STORAGE AMOUNT: MAXIMUM STORAGE PER TABLE 5003.1.1(1) - 400 GALLONS
<br />ON SITE STORAGE: NONE
<br />USED IN CLOSED SYSTEM: 20 GALLONS USED IN CHEMICAL TANK
<br />CSA REGISTRATION NO: 7681-52-9
<br />1.AMERICANS WITH DISABILITIES ACT
<br />2.VIRGINIA GRAEME BAKER SAFETY ACT
<br />3.2018 CAEHA - CALIFORNIA ASSOCIATION OF ENVIRONMENTAL HEALTH
<br />ADMINISTRATORS
<br />4.2019 CALIFORNIA BUILDING CODE STANDARDS - TITLE 24:
<br />-CHAPTER 31B - PUBLIC POOLS
<br />-CALIFORNIA BUILDING STANDARDS
<br />-CALIFORNIA BUILDING CODE
<br />-CALIFORNIA ELECTRICAL CODE
<br />-CALIFORNIA MECHANICAL CODE
<br />-CALIFORNIA PLUMBING CODE
<br />-CALIFORNIA ENERGY CODE
<br />-CALIFORNIA FIRE CODE
<br />-CALIFORNIA GREEN BUILDING STANDARDS CODE
<br />5.GUIDELINES SET FORTH BY THE COUNTY OF ORANGE
<br />POOL & SPA SHEET INDEX
<br />603.5.20 SWIMMING POOLS, SPAS, AND HOT TUBS.
<br />POTABLE WATER SUPPLY TO SWIMMING POOLS, SPAS, AND HOT TUBS SHALL
<br />BE PROTECTED BY AN AIR GAP OR A REDUCED PRESSURE PRINCIPLE
<br />BACKFLOW PREVENTER IN ACCORDANCE WITH THE FOLLOWING:
<br />(1)THE UNIT IS EQUIPPED WITH A SUBMERGED FILL LINE.
<br />THE POTABLE WATER SUPPLY IS DIRECTLY CONNECTED TO THE UNIT
<br />CIRCULATION SYSTEM.
<br />POTABLE WATER
<br />COMMON PROPERTY NAME: HYDROCHLORIC ACID - HCL
<br />MATERIAL: CORROSIVE
<br />CLASS: 1
<br />STORAGE AMOUNT: MAXIMUM STORAGE PER TABLE 5003.1.1(2) - 50 GALLONS
<br />ON SITE STORAGE: NONE
<br />USED IN CLOSED SYSTEM: 20 GALLONS USED IN CHEMICAL TANK
<br />CSA REGISTRATION NO: 7647-01-0
<br />BONDING & GROUNDING
<br />CODE COMPLIANCE
<br />SCOPE OF WORK
<br />HEATER NOTES
<br />CBC ELECTRICAL NOTES
<br />CBC PLUMBING NOTES
<br />1.EACH FIXTURE TRAP SHALL HAVE A PROTECTING VENT SO LOCATED THAT
<br />THE DEVELOPED LENGTH OF THE TRAP ARM FROM THE TRAP WEIR TO THE
<br />INNER EDGE OF THE VENT SHALL BE WITHIN THE DISTANCE GIVEN IN TABLE
<br />1002.2 IPC, BUT IN NO CASE LESS THAN TWO TIMES THE DIAMETER OF THE
<br />TRAP ARM.
<br />2.EACH PLUMBING FIXTURE THAT CONNECTS TO THE SANITARY SEWER
<br />SYSTEM SHALL BE PROPERLY TRAPPED AND VENTED IN ACCORDANCE WITH
<br />THE 2019 IPC.
<br />3.FLOOR DRAINS OR SIMILAR TRAPS DIRECTLY CONNECTED TO THE
<br />DRAINAGE SYSTEMS AND SUBJECT TO INFREQUENT USE SHALL BE
<br />PROVIDED WITH AN APPROVED AUTOMATIC MEANS OF MAINTAINING THEIR
<br />WATER SEALS.
<br />4.BUILDING DRAIN AND VENT PIPING MATERIALS SHALL COMPLY WITH
<br />SECTIONS 701.0 AND 903.0 OF THE INTERNATIONAL PLUMBING CODE.
<br />5.EACH VENT SHALL RISE VERTICALLY TO A POINT NOT LESS THAN SIX (6)
<br />INCHES ABOVE THE FLOOD-LEVEL RIM OF THE FIXTURE SERVED BEFORE
<br />OFFSETTING HORIZONTALLY OR BEFORE CONNECTING TO ANOTHER VENT.
<br />1.THE POOL HEATER SHALL:
<br />A.) MEET ASME STANDARDS
<br />B.) BOND BOILER PER ELECTRIC CODE
<br />C.) HAVE A CODE COMPLIANT GAS TRAIN ASSEMBLY
<br />D.) HAVE A NATURAL GAS APPLIANCE APPROVED BALL/SHUTOFF VALVE
<br />PROVIDED BY THE BOILER INSTALLATION CONTRACTOR
<br />2.IMC SECTION 1010.1:
<br /> A.) THE DISCHARGE OF THE RELIEF VALVE SHALL BE PIPED TO WITHIN 18
<br />INCHES OF THE FLOOR OR TO AN OPEN RECEPTACLE (IMC 1006.1)
<br />B.) NO VALVE SHALL BE PLACED BETWEEN THE SAFETY RELIEF VALVE
<br />AND THE HEATER, NOR ON THE DISCHARGE PIPE BETWEEN THE SAFETY
<br />RELIEF VALVE AND THE ATMOSPHERE (IMC 1006.1)
<br />3.ENERGY EFFICIENCY STANDARDS SECTION
<br />A.) ANY POOL OR SPA HEATING SYSTEM OR EQUIPMENT MAY BE
<br />INSTALLED ONLY IF THE MANUFACTURER HAS CERTIFIED THAT THE
<br />SYSTEM OR EQUIPMENT HAS THE FOLLOWING:
<br />i.) THERMAL EFFICIENCY THAT COMPLIES WITH THE APPLIANCE
<br />EFFICIENCY REGULATION
<br />ii.) ON/OFF SWITCH MOUNTED TO OUTSIDE OF HEATER THAT
<br />ALLOWS SHUTTING OFF THE HEATER WITHOUT ADJUSTING THE
<br />THERMOSTAT AND INSTRUCTIONS CONSISTING OF A PERMANENT,
<br />EASILY READABLE AND WEATHERPROOF PLATE OR CARD THAT
<br />GIVES INSTRUCTIONS FOR THE ENERGY EFFICIENT OPERATION
<br />OF THE POOL OR SPA HEATER AND FOR PROPER CARE WHEN THE
<br />POOL OR SPA WATER COVER IS USED.
<br />iii.) NO ELECTRIC RESISTANCE HEATING.
<br />B.) INSTALLATION OF ANY POOL & SPA SYSTEM OR EQUIPMENT SHALL BE
<br />INSTALLED WITH AT LEAST 36 INCHES OF PIPE BETWEEN THE FILTER AND
<br />THE HEATER OR SUCTION AND RETURN LINES, OR BUILT-IN OR BUILT-UP
<br />CONNECTIONS AND SHALL BE INSTALLED TO ALLOW FOR THE FUTURE
<br />ADDITION OF SOLAR HEATING EQUIPMENT.
<br />4.EQUIPMENT AND APPLIANCES SHALL BE INSTALLED AS REQUIRED BY THE
<br />TERMS OF THEIR APPROVAL, IN ACCORDANCE WITH THE CONDITIONS OF
<br />THEIR LISTING THE MANUFACTURERS INSTALLATION INSTRUCTIONS AND
<br />CODE. MANUFACTURERS INSTALLATION INSTRUCTIONS SHALL BE
<br />AVAILABLE ON THE JOB SITE AT THE TIME OF INSPECTION. (IMC 304.1)
<br />5.VENTING FOR THE POOL HEATER SHALL BE IN ACCORDANCE WITH ALL
<br />REQUIREMENTS OF THE MANUFACTURERS INSTALLATION INSTRUCTIONS
<br />AND THE 2015 IMC CHAPTER 8.
<br />6.AIR FOR COMBUSTION, VENTILATION AND DILUTION OF FLUE GASSES
<br />SHALL BE PROVIDED FOR THE POOL HEATER ENCLOSURE IN
<br />ACCORDANCE WITH THE MANUFACTURES INSTALLATION INSTRUCTIONS
<br />AND THE 2015 INTERNATIONAL FUEL AND GAS CODE.
<br />1.ALL ELECTRICAL WORK SHALL COMPLY WITH FOLLOW: 2019 CEC -
<br />ARTICLE 680 - SWIMMING POOL INSTALLATIONS - SEE: ELECTRICAL
<br />SHEETS FOR ADDITIONAL NOTES:
<br />- 680.7 - CORD-AND-PLUG-CONNECTED EQUIPMENT
<br />- 680.8 - OVERHEAD CONDUCTOR CLEARANCE
<br />- 680.9 - ELECTRIC WATER HEATER
<br />- 680.10 - UNDERGROUND WIRING
<br />- 680.11 - EQUIPMENT ROOMS AND PITS
<br />- 680.12 - MAINTENANCE DISCONNECTING MEANS
<br />- 680.21 - MOTORS
<br />- 680.22 - AREA LIGHTING, RECEPTACLES AND EQUIPMENT
<br />- 680.23 - UNDERWATER LUMINARIES
<br />- 680.24 - JUNCTION BOX, TRANSFORMER, OR GFCI ENCLOSURE
<br />- 680.25 - FEEDERS
<br />- 680.26 - EQUIPOTENTIAL BONDING
<br />- 680.27 - SPECIALIZED EQUIPMENT
<br />- ANY ADDITIONAL STATE AND LOCAL REQUIREMENTS
<br />CHEMICALS & STORAGE
<br />APPROVAL STAMP:
<br />CONTACT INFORMATION
<br />POOL & SPA DATA
<br />1.[POOL]
<br />PERIMETER:116'-0" LF.
<br />SURFACE AREA:616 SQFT.
<br />APPROXIMATE VOLUME:15,505 GALLONS
<br />MINIMUM TURN OVER:6 HRS
<br />MINIMUM FLOW RATE:43 GPM
<br />DESIGNED FLOW RATE:75 GPM @ 60 TDH
<br />OCCUPANCY LOAD:30 PERSONS PER CBC(POSTED)
<br />GUTTER SURGE:698 GAL. (616 MIN.)
<br />2.[SPA]
<br />PERIMETER:56'-0" LF.
<br />SURFACE AREA:196 SQFT.
<br />APPROXIMATE VOLUME:3,908 GALLONS
<br />MINIMUM TURN OVER:1/2 HRS
<br />MINIMUM FLOW RATE:130 GPM
<br />DESIGNED FLOW RATE:150 GPM @ 60 TDH
<br />OCCUPANCY LOAD:24 PERSONS (POSTED)
<br />BOOSTER FLOW RATE:155 GPM
<br />GUTTER SURGE:270 GAL. (196 MIN.)
<br />11B-1009 SWIMMING POOLS, WADING POOLS, AND SPAS
<br />11B-1009.1 GENERAL. WHERE PROVIDED, POOL LIFTS, SLOPED ENTRIES,
<br />TRANSFER WALLS, TRANSFER SYSTEMS, AND POOL STAIRS SHALL COMPLY
<br />WITH 11B-1009.
<br />11B-1009.2 POOL LIFTS. POOL LIFTS SHALL COMPLY WITH 11B-1009.2.
<br />11B-1009.2.1 POOL LIFT LOCATION. POOL LIFTS SHALL BE LOCATED WHERE
<br />THE WATER LEVEL IS 36 INCHES MINIMUM AND 48 INCHES MAXIMUM.
<br />EXCEPTIONS:
<br />1. WHERE THE ENTIRE POOL DEPTH IS GREATER THAN 48 INCHES,
<br />COMPLIANCE WITH 11B-1009.2.1 SHALL NOT BE REQUIRED.
<br />2. WHERE MULTIPLE POOL LIFT LOCATIONS ARE PROVIDED, NO MORE THAN
<br />ONE POOL LIFT SHALL BE REQUIRED TO BE LOCATED IN AN AREA WHERE THE
<br />WATER LEVEL IS 48 INCHES MAXIMUM.
<br />3. WHERE THE WATER DEPTH OF THE ENTIRE SWIMMING POOL, WADING
<br />POOL OR SPA IS LESS THAN 36 INCHES, POOL LIFTS SHALL BE LOCATED
<br />WHERE THE WATER LEVEL IS LESS THAN 36 INCHES.
<br />11B-1009.2.2 SEAT LOCATION. IN THE RAISED POSITION, THE CENTERLINE OF
<br />THE SEAT SHALL BE LOCATED OVER THE DECK AND 16 INCHES MINIMUM
<br />FROM THE EDGE OF THE POOL. THE DECK SURFACE BETWEEN THE
<br />CENTERLINE OF THE SEAT AND THE POOL EDGE SHALL HAVE A SLOPE NOT
<br />STEEPER THAN 1:48.
<br />11B-1009.2.3 CLEAR DECK SPACE. ON THE SIDE OF THE SEAT OPPOSITE THE
<br />WATER, A CLEAR DECK SPACE SHALL BE PROVIDED PARALLEL WITH THE
<br />SEAT. THE SPACE SHALL BE 36 INCHES WIDE MINIMUM AND SHALL EXTEND
<br />FORWARD 48 INCHES MINIMUM FROM A LINE LOCATED 12 INCHES BEHIND
<br />THE REAR EDGE OF THE SEAT. THE CLEAR DECK SPACE SHALL HAVE A
<br />SLOPE NOT STEEPER THAN 1:48.
<br />11B-1009.2.4 SEAT . THE SEAT SHALL BE RIGID AND SHALL HAVE A BACK
<br />SUPPORT THAT IS AT LEAST 12 INCHES TALL. THE HEIGHT OF THE LIFT SEAT
<br />SHALL BE DESIGNED TO ALLOW A STOP AT 17 INCHES MINIMUM TO 19 INCHES
<br />MAXIMUM MEASURED FROM THE DECK TO THE TOP OF THE SEAT SURFACE
<br />WHEN IN THE RAISED (LOAD) POSITION. THE SEAT SHALL HAVE A RESTRAINT
<br />FOR THE USE OF THE OCCUPANT WITH OPERABLE PARTS COMPLYING WITH
<br />11B-309.
<br />11B-1009.2.5 SEAT WIDTH. THE SEAT SHALL BE 16 INCHES WIDE MINIMUM.
<br />11B-1009.2.6 FOOTRESTS AND ARMRESTS. . FOOTRESTS SHALL BE PROVIDED
<br />AND SHALL MOVE WITH THE SEAT. THE SEAT SHALL HAVE TWO ARMRESTS.
<br />THE ARMREST POSITIONED OPPOSITE THE WATER SHALL BE REMOVABLE OR
<br />SHALL FOLD CLEAR OF THE SEAT WHEN THE SEAT IS IN THE RAISED
<br />POSITION.
<br />EXCEPTION: FOOTRESTS SHALL NOT BE REQUIRED ON POOL LIFTS PROVIDED
<br />IN SPAS.
<br />11B-1009.2.7 OPERATION. THE LIFT SHALL BE CAPABLE OF UNASSISTED
<br />OPERATION FROM BOTH THE DECK AND WATER LEVELS. CONTROLS AND
<br />OPERATING MECHANISMS SHALL BE UNOBSTRUCTED WHEN THE LIFT IS IN
<br />USE AND SHALL COMPLY WITH 11B-309.4 (OPERATION). THE LIFT SHALL BE
<br />STABLE AND NOT PERMIT UNINTENDED MOVEMENT WHEN A PERSON IS
<br />GETTING INTO OR OUT OF THE SEAT.
<br />11B-1009.2.8 SUBMERGED DEPTH. THE LIFT SHALL BE DESIGNED SO THAT THE
<br />SEAT WILL SUBMERGE TO A WATER DEPTH OF 18 INCHES MINIMUM BELOW
<br />THE STATIONARY WATER LEVEL.
<br />11B-1009.2.9 LIFTING CAPACITY. SINGLE PERSON POOL LIFTS SHALL HAVE A
<br />WEIGHT CAPACITY OF 300 POUNDS MINIMUM AND BE CAPABLE OF
<br />SUSTAINING A STATIC LOAD OF AT LEAST ONE AND A HALF TIMES THE RATED
<br />LOAD.
<br />1. R1-SP-001 POOL & SPA PLAN COVER
<br />2. R1-SP-002 POOL & SPA SITE PLAN
<br />3. R1-SP-003 POOL & SPA CUT SHEETS
<br />4. R1-SP-004 POOL & SPA CUT SHEETS
<br />5. R1-SP-005 POOL & SPA CUT SHEETS
<br />6. R1-SP-006 POOL & SPA CUT SHEETS
<br />7. R1-SP-007 POOL & SPA CUT SHEETS
<br />8. R1-SP-008 POOL & SPA CUT SHEETS
<br />9. R1-SP-009 POOL & SPA CUT SHEETS
<br />10. R1-SP-101 POOL & SPA PLAN
<br />11. R1-SP-102 POOL & SPA EQUIPMENT PLAN
<br />12. R1-SP-103 POOL & SPA PLUMBING PLAN
<br />13. R1-SP-301 POOL & SPA SECTIONS
<br />14. R1-SP-501 POOL & SPA DETAILS
<br />15. R1-SP-502 POOL & SPA DETAILS
<br />16. R1-SP-503 POOL & SPA DETAILS
<br />17. R1-SP-504 POOL & SPA DETAILS
<br />18. R1-SP-505 POOL & SPA DETAILS
<br />19. R1-SP-506 INTELLICENTER SCHEMATIC
<br />© Gensler
<br />Date Description
<br />Project Name
<br />Project Number
<br />Description
<br />Scale
<br />Seal / Signature
<br />2021
<br />Tel 949.863.9434
<br />Fax 949-553-1676
<br />4675 MacArthur Court
<br />Suite 100
<br />Newport Beach, CA
<br />92600
<br />USA
<br />BI
<br />M
<br />
<br />3
<br />6
<br />0
<br />:
<br />/
<br />/
<br />0
<br />0
<br />7
<br />.
<br />3
<br />7
<br />5
<br />7
<br />.
<br />0
<br />0
<br />0
<br />
<br />-
<br />
<br />C
<br />a
<br />r
<br />i
<br />b
<br />o
<br />u
<br />
<br />I
<br />n
<br />d
<br />u
<br />s
<br />t
<br />r
<br />i
<br />e
<br />s
<br />
<br />-
<br />
<br />3
<br />r
<br />d
<br />
<br />&
<br />
<br />B
<br />r
<br />o
<br />a
<br />d
<br />w
<br />a
<br />y
<br />/
<br />3
<br />R
<br />D
<br />-
<br />B
<br />_
<br />A
<br />R
<br />C
<br />H
<br />_
<br />W
<br />E
<br />S
<br />T
<br />_
<br />R
<br />2
<br />0
<br />.
<br />r
<br />v
<br />t
<br />07.3757.000
<br />3rd & Broadway
<br />301 N. Broadway, Santa Ana, CA
<br />09/21/2021 Issue for Plan Check
<br />A 12/10/2021 Reissue for Plan Check
<br />B 07/11/2022 Reissue for Plan Check
<br />C 06/17/2024 REVISION TO PERMIT
<br />AQUA DESIGN INTERNATIONAL
<br />7534 N. LA CHOLLA BLVD.
<br />TUCSON, AZ 85741
<br />OFFICE: 520-219-8929
<br />CONTACT: ADEN ACKLIN
<br />QUADESIGN
<br />INTERNATIONAL
<br />R
<br />AMMTEC CONSULTANTS
<br />2447 WEST 12TH STREET SUITE #1
<br />TEMPE, AZ 85281
<br />OFFICE: 480-972-9696
<br />CONTACT: ALAN MONEY - P.E.
<br />R1-SP-001
<br />POOL & SPA PLAN COVER
<br />COMMON PROPERTY NAME: EZ POOL PRO
<br />MATERIAL: WATER CLARIFIER
<br />CLASS: N/A
<br />STORAGE AMOUNT: MAXIMUM STORAGE PER TABLE 5003.1.1(2) 400 GALLONS
<br />ON SITE STORAGE: (2) 40 LB. SEALED TUBS
<br />USED IN CLOSED SYSTEM: 30 GALLONS USED IN DOUBLE CHEMICAL TANK
<br />CSA REGISTRATION NO: N/A - CERTIFIED TO NSF/ANSI STANDARD 50.
<br />COMMON PROPERTY NAME: REVIVE PRO
<br />MATERIAL: WATER CLARIFIER
<br />CLASS: N/A
<br />STORAGE AMOUNT: MAXIMUM STORAGE PER TABLE 5003.1.1(2) 400 GALLONS
<br />ON SITE STORAGE: (2) 5 GAL. SEALED TUBS
<br />USED IN CLOSED SYSTEM: 10 GALLONS USED IN DOUBLE CHEMICAL TANK
<br />CSA REGISTRATION NO: N/A - CERTIFIED TO NSF/ANSI STANDARD 50
<br />1.PRODUCT SUBMITTAL:
<br />POOL CONTRACTOR TO INCLUDE MANUFACTURER'S DATA,
<br />INSTALLATION INSTRUCTIONS AND GENERAL RECOMMENDATIONS FOR
<br />EACH SPECIFIED PRODUCT.
<br />2.SHOP DRAWING SUBMITTAL:
<br />SHOP DRAWINGS OF EACH ITEM SPECIFIED SHOWING
<br />LAYOUT,PROFILES, METHODS OF JOINING AND ANCHORAGE DETAILS
<br />3.SUBMITTAL FORM:
<br />USE SUBMITTAL FORM AS A COVER PAGE FOR EACH PRODUCT AND
<br />SHOP DRAWING. SEE SPECIFICATIONS FOR SUBMITTAL FORM.
<br />SUBMITTALS
<br />1.INSPECTIONS AS REQUIRED BY THE COUNTY OF ORANGE:
<br />- PLUMBING INSTALLATION.
<br />- PRE-DECK.
<br />- PRE-INTERIOR SURFACE & DECK.
<br /> - AT THE COMPLETION OF CONSTRUCTION AND ANY OTHER
<br />INSPECTIONS THAT MAY BE REQUIRED BY THE COUNTY OF LOS
<br />ANGELES NO SPA SHALL BE OPENED TO THE PUBLIC WITHOUT WRITTEN
<br />APPROVAL OF THE BUILDING AND HEALTH DEPARTMENT.
<br />2.THE SPECIAL INSPECTIONS IDENTIFIED ON PLANS ARE, IN ADDITION TO,
<br />AND NOT A SUBSTITUTE FOR, THOSE INSPECTIONS REQUIRED TO BE
<br />PERFORMED BY A CITY BUILDING INSPECTOR.
<br />ENCLOSURE NOTES
<br />2019 CALIFORNIA BUILDING CODE STANDARDS - TITLE 24:
<br />-CHAPTER 31B - PUBLIC POOLS:
<br />3119B.1 ENCLOSURE. THE POOL SHALL BE ENCLOSED BY ONE OR A
<br />COMBINATION OF THE FOLLOWING: A FENCE, PORTION OF A BUILDING,
<br />WALL, OR OTHER APPROVED DURABLE ENCLOSURE. DOORS, WINDOWS,
<br />GATES OF LIVING UNITS OR ASSOCIATED PRIVATE PREMISES SHALL NOT
<br />BE PERMITTED AS PART OF THE POOL ENCLOSURE. THE ENCLOSURE,
<br />DOORS AND GATES SHALL MEET ALL OF THE FOLLOWING
<br />SPECIFICATIONS:
<br />4.THE ENCLOSURE SHALL HAVE A MINIMUM EFFECTIVE PERPENDICULAR
<br />HEIGHT OF 5 FEET (1524 MM) AS MEASURED FROM THE OUTSIDE AS
<br />DEPICTED IN FIGURE 31B-4; AND
<br />5.OPENINGS, HOLES OR GAPS IN THE ENCLOSURE, DOORS AND/OR
<br />GATES SHALL NOT ALLOW THE PASSAGE OF A 4-INCH (102 MM)
<br />DIAMETER SPHERE. THE ENCLOSURE SHALL BE CONSTRUCTED OVER
<br />A HARD AND PERMANENT MATERIAL EQUIVALENT TO CONCRETE; AND
<br />6.THE ENCLOSURE SHALL BE DESIGNED AND CONSTRUCTED SO THAT IT
<br />CANNOT BE READILY CLIMBED BY SMALL CHILDREN. HORIZONTAL AND
<br />DIAGONAL MEMBER DESIGNS WHICH MIGHT SERVE AS A LADDER FOR
<br />SMALL CHILDREN ARE PROHIBITED. HORIZONTAL MEMBERS SHALL BE
<br />SPACED AT LEAST 48 INCHES (1219 MM) APART. NO PLANTERS OR
<br />OTHER STRUCTURES THAT CAN BE CLIMBED SHALL BE PERMITTED
<br />WITHIN 5 FEET (1524 MM) OF THE OUTSIDE OF THE POOL ENCLOSURE
<br />OR WITHIN A 5 FOOT (1524 MM) ARC AS DEPICTED IN FIGURE 31B-5. THE
<br />AREA 5 FEET (1524 MM) OUTSIDE OF THE POOL ENCLOSURE SHALL BE
<br />A COMMON AREA OPEN TO THE PUBLIC; AND
<br />7.CHAIN LINK MAY BE USED, PROVIDED THAT THE OPENINGS ARE NOT
<br />GREATER THAN 13/4 INCHES (44 MM) MEASURED HORIZONTALLY.
<br />3119B.2 GATES. GATES AND DOORS OPENING INTO THE POOL ENCLOSURE
<br />ALSO SHALL MEET THE FOLLOWING SPECIFICATIONS:
<br />1.GATES AND DOORS SHALL BE EQUIPPED WITH SELF-CLOSING AND
<br />SELF-LATCHING DEVICES. THE SELF-LATCHING DEVICE SHALL KEEP
<br />THE GATE OR DOOR SECURELY CLOSED. GATES AND DOORS SHALL
<br />OPEN OUTWARDLY AWAY FROM THE POOL EXCEPT WHERE
<br />OTHERWISE PROHIBITED BY LAW. HAND ACTIVATED DOOR OR GATE
<br />OPENING HARDWARE SHALL BE LOCATED AT A HEIGHT NO LOWER
<br />THAN 42 INCHES (1067 MM) BUT NO HIGHER THAN 44 INCHES (1179 MM)
<br />ABOVE THE DECK OR WALKWAY; AND
<br />2.GATES AND DOORS SHALL BE CAPABLE OF BEING LOCKED DURING
<br />TIMES WHEN THE POOL IS CLOSED. EXIT DOORS WHICH COMPLY WITH
<br />CHAPTER 10, TITLE 24, CALIFORNIA CODE OF REGULATIONS SHALL BE
<br />CONSIDERED AS MEETING THESE REQUIREMENTS; AND
<br />3.THE POOL ENCLOSURE SHALL HAVE AT LEAST ONE MEANS OF EGRESS
<br />WITHOUT A KEY FOR EMERGENCY PURPOSES. UNLESS ALL GATES OR
<br />DOORS ARE SO EQUIPPED, THOSE GATES AND/OR DOORS WHICH WILL
<br />ALLOW EGRESS WITHOUT A KEY SHALL HAVE A SIGN IN LETTERS AT
<br />LEAST 4 INCHES (102 MM) HIGH STATING EMERGENCY EXIT; AND
<br />4.THE ENCLOSURE SHALL BE CONSTRUCTED SO THAT ALL PERSONS
<br />WILL BE REQUIRED TO PASS THROUGH COMMON POOL ENCLOSURE
<br />GATES OR DOORS IN ORDER TO GAIN ACCESS TO THE POOL AREA. ALL
<br />GATES AND DOORS EXITING THE POOL AREA SHALL OPEN INTO A
<br />PUBLIC AREA OR A WALKWAY ACCESSIBLE BY ALL POOL PATRONS.
<br />1.ALL GROUNDING SHALL BE COMPLETED IN ACCORDANCE WITH
<br />NATIONAL ELECTRIC CODE (NEC) AND THE LOCAL AUTHORITY HAVING
<br />JURISDICTION.
<br />2.THESE PLANS ARE DIAGRAMMATIC AND MAY NOTE REPRESENT THE
<br />FINAL LOCATIONS OF THE EQUIPMENT. THE POOL AND FOUNTAIN
<br />CONTRACTORS SHALL COORDINATE ALL GROUNDING REQUIREMENTS
<br />AND EQUIPMENT ELECTRICAL CONNECTIONS WITH ALL OTHER WORK
<br />TO BE COMPLETED WITH CONSIDERED FIELD CONDITIONS.
<br />3.THE GROUNDING GRID TO BE INSTALLED WITHIN THE POOL AND
<br />FOUNTAIN ASSEMBLIES SHALL BE INSTALLED WITH A MINIMUM OF BARE
<br />#8 GROUND WIRE (99% PURE COPPER) AND INSTALLATION IS TO BE
<br />COORDINATED WITH FINAL FEATURE CONSTRUCTION.
<br />4.GROUNDING GRID SHALL BE INSTALLED A MINIMUM OF 1 METER THE
<br />POOL AND FOUNTAIN EDGES IN ACCORDANCE WITH NEC.
<br />5.ALL GROUNDING CONNECTIONS SHALL BE CAD-WELDED OR AS
<br />OTHERWISE REQUIRED, CAD WELDING SHALL BE COPPER TO COPPER
<br />WITH 6% SILVER FOR DUCTILITY.
<br />6.PROVIDE #8 BARE COPPER WIRE SPACED AT 300MM APART FOR ENTIRE
<br />LENGTH OF BONDING GRID, COPPER WELD AT EACH JOINT. PROVIDE #8
<br />COPPER GROUNDING CONDUCTOR FROM LIGHTS, RAILS, AND OTHER
<br />REQUIRED POOL ACCESSORIES PER POOL BONDING DIAGRAM DETAIL.
<br />GENERAL NOTES
<br />WATER CHEMISTRY:
<br />FREE AVAILABLE CHLORINE 1.0 - 3.0 ppm
<br />COMBINED CHLORINE N/A
<br />POTENTIAL HYDROGEN (pH)7.4 - 7.6 ppm
<br />SALT CONCENTRATION N/A
<br />TOTAL ALKALINITY 80 - 100 ppm
<br />TDS 1,500 ppm max.
<br />CALCIUM HARDNESS 250 ppm max.
<br />CYANURIC ACID 20 ppm
<br />ORP / HHR 700 - 780 mV
<br />TEMPERATURES 82° (POOL) & 102° (SPA)
<br />ACCESSIBILITY NOTES
<br />23.THE OWNER SHALL KEEP DAILY RECORD FOR THE POOL SANITATION
<br />AND pH READING PER COUNTY REQUIREMENTS.
<br />24. ALL PIPING IN THE EQUIPMENT ROOM MUST BE PERMANENTLY MARKED
<br />WITH DIRECTIONAL ARROWS AND IDENTIFIED AS TO THE ORIGIN OF
<br />USE, E.G., GUTTER, MAIN DRAIN, ETC.
<br />PIPING COLOR CODE:
<br />FRESH WATER - BLUE (TO CHECK VALVE)
<br />BACKWASH - BLACK
<br />INFLUENT - YELLOW
<br /> RE-CIRCULATION SYSTEM - GREEN
<br />1.ALL EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER'S
<br />INSTRUCTIONS.
<br />2.ANY CHANGES IN CONSTRUCTION PLANS OR EQUIPMENT MUST BE
<br />APPROVED BY THE ORANGE HEALTH DEPARTMENT. CHANGES MAY
<br />REQUIRE ADDITIONAL PLAN CHECK FEES AND RE-SUBMITTAL.
<br />3.POOL PLAN APPROVAL DOES NOT AUTHORIZE THE VIOLATION OF ANY
<br />LAW, ORDINANCE, OR REGULATION AND FINAL APPROVAL IS SUBJECT
<br />TO FIELD INSPECTION AND EVALUATION.
<br />4.MINIMUM OF 6 FOOT WIDE, CONTINUOUS, SLIP-RESISTANT,
<br />NON-ABRASIVE DECK AREA OF CONCRETE OR CONCRETE LIKE
<br />MATERIAL MUST BE PROVIDED FLUSH WITH THE TOP OF THE POOL AND
<br />EXTENDED COMPLETELY AROUND.
<br />5.THE REQUIRED DECKING AROUND THE POOL MUST BE FREE OF ALL
<br />POSTS, COLUMNS, OR OTHER OBSTRUCTIONS AND EXTEND AT LEAST 4
<br />FEET BEHIND ANY PERMANENT HANDICAP EQUIPMENT.
<br />6.ALL PARTS OF THE DECK MUST DRAIN NATURALLY OR TO FLOOR
<br />DRAINS AT A SLOPE BETWEEN 1% AND 2% WITH NO ACCUMULATIONS
<br />OF WATER. SPACE BETWEEN THE COPING AND THE DECK MUST BE
<br />SEALED WITH AN APPROPRIATE CAULKING.
<br />7.AUTOMATIC CHLORINATOR IS REQUIRED WHICH IS CAPABLE OF
<br />SUPPLYING NOT LESS THAN THE EQUIVALENT OF 3 POUNDS OF
<br />CHLORINE PER DAY PER 10,000 GALLONS POOL WATER CAPACITY.
<br />8.ADEQUATE NUMBER OF HOSE BIBBS ARE REQUIRED IN THE POOL AREA
<br />IN SUFFICIENT NUMBERS TO ALLOW A 75 FOOT HOSE TO REACH ALL
<br />AREAS OF THE POOL DESK. HOSE BIBB IS REQUIRED IN THE
<br />EQUIPMENT AREA. EACH HOSE BIBB MUST BE PROTECTED BY AN
<br />APPROVED BACKFLOW DEVICE.
<br />9.PERFORM A HYDROSTATIC TEST TO 35 PSI (3.5KG/CM2) FOR 30
<br />MINUTES AND KEEP A MINIMUM OF 25 PSI (1.75KG/CM2) ON SYSTEM
<br />UNTIL AFTER DECK PHASE.
<br />10.PRESSURE GAUGES SHALL BE BE INSTALLED ON THE INLET AND
<br />OUTLET OF THE EACH FILTER SYSTEM AND LOCATED WHERE THEY CAN
<br />BE EASILY READ.
<br />11.VACUUM GAUGES SHALL BE INSTALLED ON THE INLET TO EACH PUMP
<br />AND INSTALLED IN WHERE THEY CAN BE EASILY READ.
<br />12.PIPE SLEEVING AND PENETRATIONS THROUGH VAULT STRUCTURE
<br />SHALL BE SLEEVED PER THE LINK SEAL REQUIREMENTS THROUGH
<br />WALLS. COORDINATE WITH ALL TRADES. PER IPC, SLEEVING: ANNULAR
<br />SPACES SHALL BE FILLED OR TIGHTLY CAULKED.
<br />13.THE PIPING INSTALLATION IN EACH EQUIPMENT ROOM, IPC SHALL BE
<br />SUPPORTED IN ACCORDANCE WITH TABLE 308.5 IN THE IPC.
<br />CONTRACTOR SHALL SUBMIT SUPPORT SYSTEM DESIGN TO BEFORE
<br />START OF THIS WORK.
<br />14.POTABLE WATER SUPPLY SYSTEMS SHALL BE DESIGNED, INSTALLED
<br />AND MAINTAINED SO AS TO PREVENT CONTAMINATION FROM
<br />NONPOTABLE LIQUIDS, SOLIDS OR GASES BEING INTRODUCED INTO
<br />THE POTABLE WATER SUPPLY THROUGH CROSS-CONNECTIONS OR
<br />ANY OTHER PIPING CONNECTIONS TO THE SYSTEM. MEANS OF
<br />PROTECTION AGAINST BACKFLOW IN THE POTABLE WATER SUPPLY
<br />SHALL BE PROVIDED THROUGH AN AIR GAP COMPLYING WITH ASME
<br />A112.1.2 INTERNATIONAL PLUMBING CODE.
<br />15.CARTRIDGE FILTER CLEANING AND DRAINING WATER SHALL BE
<br />DISCHARGED TO THE SANITARY, OR INTO AN APPROVED DISPOSAL
<br />SYSTEM APPROVED BY THE STATE OR LOCAL AUTHORITY.
<br />16.REINFORCING STEEL OF ALL AQUATIC BODY'S SHALL BE BONDED WITH
<br />A #8 COPPER WIRE TIED BOND INTO THE MECHANICAL SYSTEM FOR
<br />EACH BODY OF WATER. EACH MECHANICAL SYSTEM SHALL THEN BE
<br />BONDED TO THE ELECTRIC PANEL THAT SUPPLIES POWER TO THAT
<br />FEATURE. FOLLOW USA NATIONAL ELECTRIC CODE FOR BONDING GRID
<br />AROUND PERIMETER OF STRUCTURE. SEE: SHEET SP-503, DETAIL 5.
<br />17.POOL UNDERWATER LIGHTING SHALL BE A MINIMUM OF .5 WATTS PER
<br />SQ FT OF SURFACE AREA.
<br />18.POOL SHALL BE PROVIDED WITH LIFE SAVING EQUIPMENT AND SHALL
<br />BE VISUALLY CONSPICUOUS AND CONVENIENTLY LOCATED AT ALL
<br />TIMES. SWIMMING POOL ACCESSORY POLE NOT LESS THAN 12 FEET IN
<br />LENGTH AND INCLUDING A BODY HOOK SHALL BE PROVIDED.
<br />19.DEPTH MARKERS OF CONTRASTING COLOR ARE REQUIRED ON BOTH
<br />SIDES, AT THE MINIMUM AND MAXIMUM DEPTHS, AT THE BREAK AT 4 ½
<br />FT. AND BOTH ENDS OF THE POOL. PERMANENT DEPTH MARKERS ARE
<br />REQUIRED ON THE POOL DECK, CORRESPONDING TO EVERY DEPTH
<br />MARKER ON THE WALL. ALL DEPTH MARKERS MUST BE MARKED WITH
<br />THE LETTERS FEET OR FT. AND INCHES OR IN. PAINTED LETTERS ARE
<br />NOT PERMITTED. DEPTH MARKERS MUST BE AT LEAST 4 INCHES IN
<br />HEIGHT AND MUST BE POSITIONED TO INDICATE THE WATER DEPTH
<br />ACCURATE TO THE NEAREST 6 INCHES AS MEASURED FROM THE POOL
<br />FLOOR TO THE MIDDLE OF THE SKIMMER OPENING.
<br />20.BARRIERS SHALL BE PROVIDED TO MEET LOCAL CODES.SEE:
<br />ARCHITECTURAL SHEETS.
<br />21.USING THE PUMP BYPASS IS RECOMMENDED PROCESS TO TAKE POOL
<br />WATER BACK TO OPERATIONAL LEVELS, IN THE EVENT THE POOL
<br />SHOULD EVER EXPERIENCE HIGH WATER LEVELS OR AN OVERFLOW
<br />FROM EXCESSIVE RAIN FALL.
<br />22.THROWING ROPE ATTACHED TO RING BUOY OR SIMILAR FLOTATION
<br />DEVICE SHALL BE PROVIDED. THE ROPE SHALL BE NOT LESS THAN ¼
<br />INCH IN DIAMETER AND SHALL HAVE A LENGTH OF NOT LESS THAN 1 ½
<br />TIMES THE MAXIMUM WIDTH OF THE POOL OR 50 FEET, WHICHEVER IS
<br />LESS. A RING BUOY SHALL HAVE AN OUTSIDE DIAMETER IS NOT LESS
<br />THAN 15 INCHES.
<br />GENERAL OPERATIONS:
<br />1.POOL PIPE ROUTING IS FOR DIAGRAM ONLY. THE POOL CONTRACTOR AND G.C. SHALL
<br />COORDINATE ROUTING LOCATIONS WITH SUPPORT SYSTEM LAYOUT. THE POOL
<br />CONTRACTOR SHALL PROVIDE PIPE MOUNTING, SUPPORT, EXPANSION JOINTS IF
<br />NEEDED AND INSULATION. THE POOL CONTRACTOR SHALL PROVIDE A SHOP
<br />DRAWING FOR THESE ITEMS TO THE G.C., ARCHITECT AND AQUATIC CONSULTANT.
<br />2.THE PUMP AND HEATER EQUIPMENT SHALL BE SET ON A 4" MIN. CONCRETE
<br />HOUSE-KEEPING PAD THAT POSITIVELY SLOPES TOWARD THE FLOOR DRAINAGE
<br />SYSTEM.
<br />3.THE HEATER SHALL BE PROVIDED WITH A SYSTEM THAT DETECTS AND MONITORS
<br />CARBON MONOXIDE IN THE EQUIPMENT ROOM.
<br />4.ALL CIRCULATION PUMPS SHALL BE SET WITH THE PROVIDED VALVES AND FLOW
<br />METERS AT START FOR THE FLOW RATES LISTED ON POOL PLANS AND BACKWASH
<br />RATES FOR THE FILTERS.
<br />INSPECTIONS
<br />TITLE 24 REQUIRMENTS
<br />1.AT LEAST 36 INCHES OF PIPE SHALL BE INSTALLED BETWEEN THE FILTER
<br />AND THE HEATER OR DEDICATED SUCTION AND RETURN LINES, OR
<br />BUILT-IN OR BUILT-UP CONNECTIONS SHALL BE INSTALLED TO ALLOW
<br />FOR THE FUTURE ADDITION OF SOLAR HEATING EQUIPMENT."
<br />2.A COVER FOR OUTDOOR POOLS OR OUTDOOR SPAS THAT HAVE A HEAT
<br />PUMP OR GAS HEATER SHALL BE PROVIDED."
<br />3.A TIME SWITCH OR SIMILAR CONTROL MECHANISM SHALL BE INSTALLED
<br />AS PART OF A POOL WATER CIRCULATION CONTROL SYSTEM THAT WILL
<br />ALLOW ALL PUMPS TO BE SET OR PROGRAMMED TO RUN ONLY DURING
<br />THE OFF-PEAK ELECTRIC DEMAND PERIOD AND FOR THE MINIMUM TIME
<br />NECESSARY TO MAINTAIN THE WATER IN THE CONDITION REQUIRED BYAPPLICABLE PUBLIC HEALTH STANDARDS."
<br />1.PROVIDE WATERPROOFING SYSTEM AQURON CPSP BY AQURON
<br />CORPORATION INTERNATIONAL (WWW.AQURON.COM) BETWEEN
<br />INTERIOR COATING AND SHOTCRETE PER PRODUCT INSTRUCTIONS.
<br />2.SEAL ALL PENETRATIONS THROUGH SHOTCRETE SHELL WITH
<br />AQUABOND UW-5000 EPOXY AT CONNECTION OF PVC TO SHOTCRETE.
<br />WATERPROOFING NOTES
<br />CONCRETE & REBAR NOTES
<br />SPECIFICATIONS
<br />A.MATERIALS
<br />1.GEO-SYNTHETIC FILL: INSULFOAM GF SHALL CONFORM TO ASTM D 6817
<br />AND MAY BE FABRICATED USING MATERIAL WITH RECYCLED CONTENT.
<br />BLOCKS SHALL HAVE A HEIGHT OF AT LEAST 36 INCHES (.91 M), A WIDTH
<br />OF AT LEAST 48 INCHES (1.22 M), AND LENGTH OF AT LEAST 96 INCHES
<br />(2.44 M). BLOCKS SHALL BE WITHIN TOLERANCES OF 0.5 PERCENT OF
<br />RESPECTIVE HEIGHT, WIDTH AND LENGTH DIMENSIONS. ADDITIONAL
<br />FIELD AND/OR SHOP TRIMMING AND CUTTING SHALL BE REQUIRED AS
<br />NECESSITATED BY THE GEOMETRY OF THE FILL BEING CONSTRUCTED.
<br />a.TYPE EPS29: PHYSICAL PROPERTIES WHEN TESTED IN
<br />ACCORDANCE WITH ASTM D 6817 SHALL BE:
<br />1)DENSITY SHALL BE A MINIMUM OF 1.80 LB/FT3 (28.8 KG/M3),
<br />WHEN TESTED IN ACCORDANCE WITH ASTM D 1622.
<br />2)COMPRESSIVE RESISTANCE AT 1 PERCENT DEFORMATION
<br />SHALL BE A MINIMUM OF 10.9 PSI (75 KPA) WHEN TESTED IN
<br />ACCORDANCE WITH ASTM D 1621.
<br />3)FLEXURAL STRENGTH SHALL BE A MINIMUM OF 50.0 PSI (345
<br />KPA) WHEN TESTED IN ACCORDANCE WITH ASTM C 203.
<br />4)ELASTIC MODULUS SHALL BE A MINIMUM OF 1090 PSI (7500 KPA)
<br />WHEN TESTED IN ACCORDANCE WITH ASTM C 203.
<br />5)OXYGEN INDEX SHALL HAVE A MINIMUM VOLUME OF 24.0
<br />PERCENT WHEN TESTED IN ACCORDANCE WITH ASTM C 2863.
<br />2.CONNECTORS: CONNECTORS SHALL BE GALVANIZED STEEL
<br />MULTI-BARBED CONNECTORS OR A URETHANE ADHESIVE AS
<br />RECOMMENDED BY THE MANUFACTURER. EACH CONNECTOR SHALL
<br />HAVE A LATERAL HOLDING STRENGTH OF AT LEAST 60 LBS (27.22 KG)
<br />WHEN TESTED WITH AN EPS15 GEOFOAM.
<br />STRUCTURAL FOAM NOTES
<br />1.80 (28.8)
<br />10.9 (75)
<br />24.7 (170)
<br />29.0 (200)
<br />50.0 (345)
<br />24.0
<br />< 2%
<br />60.6 (970)
<br />.05
<br />.6
<br />< 4.0
<br />1090 (7500)
<br />TYPE - EPS 29
<br />DENSITY (NOMICAL PCF)
<br />COMPRESSIVE RESISTANCE MIN. @ 1% DEFORMATION
<br />COMPRESSIVE RESISTANCE MIN. @ 5% DEFORMATION
<br />COMPRESSIVE STRENGTH (PSI, 10% DEFORMATION)
<br />FLEXURAL STRENGTH (MIN. PSI)
<br />OXYGEN INDEX, MIN.
<br />DIMENSIONAL STABILITY
<br />BUOYANCY FORCE
<br />POISSON’S RATIO
<br />COEFfiCIENT OF FRICTION
<br />ABSORPTION
<br />ELASTIC MODULUS, MIN.
<br />1.PLAN SHALL BE IN ACCORDANCE WITH 2018 CBC.
<br />2.REINFORCEMENT STEEL SHALL MEET ASTM A615-40. LAP SPLICES SHALL
<br />BE AT LEAST 40 BAR DIAMETERS. ALL BENDS SHALL BE SHARP. IBC 2018
<br />SHALL BE USED AS A GUIDELINE.
<br />3.REBAR PLACEMENT SHALL BE SUCH THAT THE DISTANCE FROM THE INSIDE
<br />GROUT FACE TO REBAR SHOULD BE A MIN. OF "TG" - 3 INCHES.
<br />4.UP TO 2 INCH DIAMETER PIPE MAY BE PLACED IN THE LOWER OUTSIDE
<br />CORNER OF THE BOND BEAM PROVIDED A MINIMUM CLEARANCE EQUAL TO
<br />0.75 TIMES THE NOMINAL MAXIMUM AGGREGATE SIZE (I.E., 1/4 INCH FOR
<br />SHOTCRETE) IS MAINTAINED BETWEEN THE PIPE AND ANY PARALLEL
<br />REINFORCEMENT PER IBC 2018.
<br />5.IF METAL PIPING IS USED AND IS PLACED IN SHOTCRETE, IT SHALL BE
<br />WRAPPED WITH VISQUEEN OR HEAVY BROWN PAPER EXCEPT WHERE IT
<br />PASSES PERPENDICULARLY THROUGH THE SHOTCRETE.
<br />6.CONCRETE CAN BE PLACED AGAINST SHOTCRETE AND STRUCTURAL
<br />FOAM.
<br />7.ELECTRICAL SHALL BE SECURELY GROUNDED BEFORE APPLYING
<br />SHOTCRETE.
<br />8.ALL STATE AND LOCAL LAWS AND CODES SHALL BE FOLLOWED.
<br />9.POOL & SPA SHALL BE MAINTAINED FULL OF WATER EXCEPT DURING
<br />CHANGE OF WATER OR SIMILAR SHORT TERM MAINTENANCE ACTIVITIES.
<br />10.SHOTCRETE SHALL BE EQUAL TO CEMEX (MIX CODE: 1559997) 4,000 PSI, 3
<br />8"
<br />FLY ASH SHOTCRETE.
<br />11.THE BEGINNER OF RECORD FOR THE VAULT STRUCTURE SUPPORTING THE
<br />POOL SHALL REVIEW THE STRUCTURAL DETAILS AND BASED ON THE POOL
<br />DESIGN AND DEPTH, CERTIFY THAT THE VAULT STRUCTURE WAS
<br />DESIGNED TO SUPPORT THE WEIGHT OF THE POOL & SPA WITHOUT
<br />DEFLECTION.
<br />12.IF THE POOL & SPA ARE LOCATED SUCH THAT WATER LEAKAGE FROM THE
<br />THEM COULD DAMAGE UNDERLYING OR ADJACENT FACILITIES, A
<br />SECONDARY LEAKAGE CONTAINMENT AND DISPOSAL SYSTEM SHALL BE
<br />INCORPORATED AS PART OF THE POOL & SPA INSTALLATION.
<br />13.PRIOR TO THE APPLICATION OF THE POOL & SPA WATERPROOFING FINISH
<br />SURFACE COATING, THE SHOTCRETE SHELL SHALL BE CLOSELY EXAMINED
<br />TO LOCATE ANY SHRINKAGE CRACKS. THE SHRINKAGE CRACKS SHALL BE
<br />INJECTED WITH HIGH PRESSURE EPOXY TO THE GREATEST DEPTH
<br />POSSIBLE.
<br />STRUCTURAL SHOTCRETE
<br />1.SHOTCRETING SHALL CONFORM TO ALL REQUIREMENTS OF
<br />”SPECIFICATIONS FOR MATERIALS, PROPORTIONS, AND APPLICATION OF
<br />SHOTCRETE” (ACI--506.2, LATEST EDITION).
<br />2.PORTLAND CEMENT SHALL CONFORM TO ASTM C--150, TYPE I OR II,
<br />ALKALI CONTENT NOT TO EXCEED 0.6G WHEN §5 OR SMALLER BARS ARE
<br />USED, THERE SHALL BE A MINIMUM CLEARANCE BETWEEN PARALLEL.
<br />3.REINFORCEMENT BARS OF 2 1/2” INCHES. WHEN BARS LARGER THAN §5
<br />ARE USED, THERE SHALL BE A MINIMUM CLEARANCE BETWEEN PARALLEL
<br />BARS EQUAL TO 6 DIAMETERS OF THE BARS USED. WHEN T\Y0 CURTAINS
<br />OR STEEL ARE PROVIDED, THE CURTAIN NEAREST THE NOZZLE SHALL
<br />HA\/E A MINIMUM SPACING EQUAL TO 12 BAR DIAMETERS AND THE
<br />REMAINING CURTAIN SHALL HAVE A MINIMUM SPACING OF 6 BAR
<br />DIAMETERS.
<br />4.LAP SPLICES IN REINFORCING BARS SHALL BE BY THE NON--CONTACT
<br />LAP SLICE METHOD WITH AT LEAST 2 INCHES CLEARANCE BETWEEN
<br />BARS. CONTACT LAP SPLICES MAY BE PERMITTED WHEN NECESSARY
<br />FOR THE SUPPORT OF THE REINFORCING PROVIDED IT CAN BE
<br />DEMONSTRATED BE MEANS OF PRE--CONSTRUCTION TESTING THAT
<br />ADEQUATE ENCASEMENT OF THE BARS AT THE SPLICE CAN BE ACHIEVED
<br />AND PROVIDED THAT THE SPICES ARE PLACED SO THAT A LINE THROUGH
<br />THE CENTER OF THE TWO SPLICED BARS IN PERPENDICULAR TO THE
<br />SURFACE OF THE SHOTCRETE WORK.
<br />5.ANY REBOUND OR ACCUMULATED LOOSE AGGREGATE SHALL BE
<br />REMOVED FROM THE SURFACES TO BE COVERED PRIOR TO PLACING
<br />THE INITIAL OR ANY SUCCEEDING LAYERS OF SHOTCRETE. REBOUND
<br />SHALL NOT BE USED AS AGGREGATE.
<br />6.UNFINISHED W0RK SHALL NOT BE ALLOWED TO STAND FOR MORE THAN
<br />30 MINUTES UNLESS ALL EDGES ARE SKIPPED T0 A THIN EDGE. BEFORE
<br />PLACING ADDITIONAL MATERIEL ADJACENT TO PREVIOUSLY APPLIED
<br />WORK, SLOPING AND SQUARE EDGES SHALL BE CLEANED AND WETTED.
<br />7.IN PLACE SHOTCRETE WHICH EXHIBITS SAGS OR SLOUGHS,
<br />SEGREGATION, HONEYCOMBING, SAND POCKETS OR OTHER OBVIOUS
<br />DEFECTS SHALL BE REMOVED AND REPLACED. SHOTCRETE ABOVE SAGS
<br />AND SLOUGHS SHALL BE REMOVED AND REPLACED WHILE SILL PLASTIC.
<br />8.DURING THE CURING PERIODS SPECIFIED HEREIN.
<br />9.SHOTCRETE SHALL BE MAINTAINED ABOVE 40 DEGREE F AND IN MOIST
<br />CONDITION.
<br />10.IN INITIAL CURING, SHOTCRETE SHALL BE KEPT CONTINUOUSLY MOIST
<br />FOR 24 HOURS AFTER PLACEMENT IS COMPLETE.
<br />11.FINAL CURING SHALL CONTINUE FOR 7 DAYS AFTER SHOTCRETING FOR 3
<br />DAYS IF HIGH EARLY STRENGTH CEMENT IS USED, OR UNTIL THE
<br />SPECIFIED STRENGTH IS OBTAINED.
<br />12.FINAL CURING SHALL CONSIST OF A FOG SPRAY OR AN APPROVED
<br />MOISTURE RETAINING COVER OR MEMBRANE.
<br />13.IN SECTIONS OF A DEPTH IN EXCESS OF 12 INCHES, FINAL CURING SHALL
<br />BE THE SAME AS THAT FOR INITIAL CURING.
<br />14.STRENGTH TEST FOR SHOTCRETE SHALL BE MADE BY AN APPRO\/ED
<br />AGENCY ON SPECIMENS MICH ARE REPRESENTATIVE OF AND IN
<br />ACCORDANCE WITH THE IBC.
<br />15.WHEN SHOTCRETE IS USED FOR STRUCTURAL MEMBERS, A SPECIAL
<br />INSPECTOR IS REQUIRED. THE SPECIAL INSPECTOR SHALL PROVIDE
<br />CONTINUOUS INSPECTION OF THE PLACEMENT OF THE REINFORCEMENT
<br />AND SHOTCRETINC AND SHALL SUBMIT A STATEMENT INDICATING
<br />COMPLIANCE RTH THE PLANS AND SPECIFICATIONS, NOTE: SUMMARY
<br />SPECIAL INSPECTION SUBMITTED TO BUILDING DEPT.
<br />16.REFERENCE ibc 2018 TABLE 25.3.1—STANDARD HOOK GEOMETRY FOR
<br />DEVELOPMENT OF DEFORMED BARS IN TENSION
<br />COORDINATION ITEMS
<br />POOL ENCLOSURE
<br />DECK DESIGN
<br />DECK DRAINAGE
<br />BATHROOM DESIGN
<br />DECK LEVEL LIGHTING
<br />DECK CLEANING HYDRANTS
<br />DRINKING FOUNTAIN
<br />DECK LEVEL ACCESS CONTROL
<br />SHEET
<br />EQUIPMENT ROOM LIGHTING
<br />DECK LEVEL POWER PLAN
<br />FILTER WASTE
<br />HEATER GAS SUPPLY
<br />POOL FILL COLD WATER SUPPLY
<br />POOL LIFE SATETY PLAN
<br />EQUIPMENT ROOM FLOOR DRAIN
<br />1.03 3714 - SHOTCRETE FOR POOLS.
<br />2.07 1417 - COLD FLUID-APPLIED WATERPROOFING FOR POOLS.
<br />3.09 3014 - CERAMIC TILING FOR SWIMMING POOLS.
<br />4.09 9727 - CEMENTITIOUS COATINGS FOR POOLS.
<br />5.13 1133 - ELEVATED SWIMMING POOLS
<br />ABBREVIATIONS
<br />ACI AMERICAN CONCRETE INSTITUTE
<br />ADA AMERICAN WITH DISABILITIES ACT
<br />ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
<br />ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
<br />ASTM AMERICAN SOCIETY OF TESTING MATERIALS
<br />BTU BRITISH THERMAL UNIT
<br />CAS CHEMICAL ABSTRACT SERVICES
<br />CPVC CHLORINATED POLYVINYL CHLORIDE
<br />GC GENERAL CONTRACTOR
<br />GFCI GROUND FAULT CIRCUIT INTERRUPTER
<br />GPM GALLONS PER MINUTE
<br />Hz HERTZ
<br />LBS POUNDS
<br />MCEHC MARICOPA COUNTY ENVIRONMENTAL HEALTH CODE
<br />NFPA NATIONAL FIRE PROTECTION ASSOCIATION
<br />NSF NATIONAL SANITATION FOUNDATION
<br />NTS NOT TO SCALE
<br />ORP OXIDATION REDUCTION POTENTIAL
<br />OSHA OCCUPATIONAL SAFETY & HEALTH ADMINISTRATION
<br />pH POTENTIAL HYDROGEN
<br />PPM PARTS PER MILLION
<br />PSI POUNDS PER SQUARE INCH
<br />PVC POLYVINYL CHLORIDE
<br />SCH SCHEDULE
<br />SS STAINLESS STEEL
<br />UL UNDERWRITERS LABORATORIES INC.
<br />V VOLTS
<br />Jun 04, 2024
<br />1/7/25
|