<br /> <br /> <br /> <br /> <br /> <br />3rd & Broadway, Santa Ana, CA <br />Volume 2 - Structural Calculations June 17, 2024 | Project # S21043.00 <br /> pg. 49 <br />4.4.1 REDUNDANCY CHECK FOR RESIDENTIAL BUILDING AND HOTEL BUILDING <br />Redundancy factor ρ, is assumed to be 1.0 for the Residential building, and 1.0 for the Hotel building per <br />Section 12.3.4.2 of ASCE 7-16. Per Table 12.3-3 of ASCE 7-16 ρ=1 is permitted if removals of a shear <br />wall or wall pier with height to length ratio greater than 1.0 within any story it connects to would not: <br />1) Result in more than a 33% reduction in story strength. And <br />2) The resulting system has an extreme torsional irregularity. <br />For both the Residential and the Hotel building, all the shear wall and wall piers including the core walls <br />were checked, and none of them had a height to length ratio greater than 1.0. Per ASCE 7 -10, the <br />building is qualified for a redundancy factor of 1.0. <br />