Laserfiche WebLink
ST. BARBARA CATHOLIC SCHOOL TASK 2 75-24272-01 <br />DIOCESE OF ORANGE SEPTEMBER 12TH, 2024 <br />SANTA ANA, CA BID & PERMIT SET <br /> <br />CONDUIT 260111 - 7 <br />E. Use conduit bodies to make sharp changes in direction, as around beams. <br />F. Use hydraulic one-shot conduit bender or factory elbows for bends in conduit larger than 2 inch <br />size. <br />G. Avoid moisture traps where possible; where unavoidable, provide junction box with drain <br />fitting at conduit low point. <br />H. Use suitable conduit caps to protect installed conduit against entrance of dirt and moisture. <br />I. Provide No. 12 AWG insulated conductor or suitable pull string or rope in empty conduit, <br />except sleeves and nipples. <br />J. Install expansion-deflection joints where conduit crosses building expansion or seismic joints <br />and between building and walkway covers. <br />K. Where conduit penetrates fire-rated walls and floors, provide mechanical firestop fittings with <br />UL listed fire rating equal to wall or floor rating. <br />L. Route conduit through roof openings for piping and ductwork where possible; otherwise, route <br />through roof jack with pitch pocket. <br />M. Do not install conduit in slabs above grade. <br />N. PVC conduit shall not be used in any locations above grade. <br />O. From each panel or cabinet which is flush mounted in wall, stub from top of the panel a <br />minimum of 5-3/4 inch conduits to the nearest accessible ceiling space or other accessible <br />location and cap for future use unless noted otherwise on the drawings. <br />P. Flexible steel conduit is permitted in concealed dry interior locations at power and lighting <br />fixture connections only. <br />Q. Seal conduit from exterior outlets at first interior junction to prevent moisture from entering the <br />building through the conduit. <br />R. Use insulating fittings on conduits where entering pullboxes, junction boxes, outlet boxes, <br />cabinets and similar enclosures, and for signal and telephone conduits terminated in cabinets or <br />backboards. <br />S. Conduit risers and ell's through concrete shall be PVC wrapped Rigid Galvanized Steel <br />minimum. <br />T. Conduit installed in corrosive atmospheres (pool mechanical, tank or chlorine rooms, etc.) shall <br />be IMC conduit minimum and shall comply with CEC 358.10(B).