Laserfiche WebLink
ST. BARBARA CATHOLIC SCHOOL TASK 2 75-24272-01 <br />DIOCESE OF ORANGE SEPTEMBER 12TH, 2024 <br />SANTA ANA, CA BID & PERMIT SET <br /> <br />BOXES 260130 - 1 <br />SECTION 260130 - BOXES <br />PART 1 - GENERAL <br />1.1 WORK INCLUDED <br />A. Wall and ceiling outlet boxes. <br />B. Pull and junction boxes. <br />1.2 REFERENCES <br />A. ANSI/NEMA FB 1 - Fittings and Supports for Conduit and Cable Assemblies. <br />B. ANSI/NEMA OS 1 - Sheet-Steel Outlet Boxes, Device Boxes, Covers and Box Supports. <br />C. NEMA 250 - Enclosures for Electrical Equipment (1000 Volts Maximum). <br />D. C.E.C.- California Electrical Code. <br />1.3 PROJECT RECORD DOCUMENTS <br />A. Submit under provisions of Division 01. <br />B. Accurately record actual locations and mounting heights of outlet, pull and junction boxes. <br />1.4 REGULATORY REQUIREMENTS <br />A. Conform to requirements of C.E.C. <br />B. Furnish products listed and classified by Underwriters Laboratories, Inc. as suitable for purpose <br />specified and shown. <br />1.5 PROJECT CONDITIONS <br />A. Verify field measurements are as shown on drawings. <br />B. Electrical boxes are shown on drawings in approximate locations unless dimensioned. Install at <br />location required for box to serve intended purpose. <br />C. Exact location of all outlet boxes shall be as indicated on architectural elevations. Outlets not <br />shown shall be coordinated with the Architect prior to rough-in. Any outlets not coordinated, <br />which are mounted in locations not accepted by the Architect, shall be relocated at no <br />additional cost to the Owner.