Laserfiche WebLink
ST. BARBARA CATHOLIC SCHOOL TASK 2 75-24272-01 <br />DIOCESE OF ORANGE SEPTEMBER 12TH, 2024 <br />SANTA ANA, CA BID & PERMIT SET <br /> <br />LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 2 <br />1.6 COORDINATION <br />A. Determine required separation between cable and other work. <br />B. Determine cable routing to avoid interference with other work. <br />PART 2 - PRODUCTS <br />2.1 BUILDING WIRE AND CABLE <br />A. Description: Single conductor insulated wire, new, manufactured not more than 6 months prior <br />to installation, with size, type of insulation, voltage rating and manufacturer's name <br />permanently marked on outer covering at regular intervals. <br />B. Conductor: Copper. <br />C. Insulation Voltage Rating: 600 volts. <br />PART 3 - EXECUTION <br />3.1 EXAMINATION <br />A. Verify that interior of building has been protected from weather. <br />B. Verify that mechanical work likely to damage wire and cable has been completed. <br />3.2 PREPARATION <br />A. Completely and thoroughly swab raceway before installing wire. <br />3.3 WIRING METHOD <br />A. Type THHN/THWN insulation for dry interior locations, in raceway. <br />B. Type THWN for exterior or wet locations, in raceway. <br />3.4 INSTALLATION <br />A. Provide conductors continuous from outlet to outlet and splice only at outlet or junction boxes. <br />B. Circuit all feeders and branch circuits as shown on the drawings. Suggested deviation from the <br />plans must be provided by the Architect. <br />C. Install products in accordance with manufacturers instructions.