Laserfiche WebLink
ST. BARBARA CATHOLIC SCHOOL TASK 2 75-24272-01 <br />DIOCESE OF ORANGE SEPTEMBER 12TH, 2024 <br />SANTA ANA, CA BID & PERMIT SET <br /> <br />WIRING DEVICES 262726 - 3 <br />I. GFCI Receptacle: Convenience receptacle with integral ground fault circuit interrupter to meet <br />regulatory requirements. <br />2.3 WALL PLATES <br />A. Plates shall be brushed stainless steel and supplied for every local switch, receptacle, telephone <br />and data outlet, wall speaker outlet, etc. <br />B. Weatherproof Cover Plate: Gasketed cast metal with hinged gasketed device cover. <br />C. Locking Weatherproof Cover Plate: Pass & Seymour Legrand #4600 Series with mounting <br />plates as required or equal at locations indicated on drawings. <br />D. Plates shall be engraved and filled, when used for: <br />1. More than two gangs. <br />2. Equipment that cannot be seen from the locations. <br />3. All lock type switches. <br />4. All receptacles other than 120 volts. <br />5. All pilot switches. <br />6. Switches in locations from which the equipment or circuits controlled cannot be readily <br />seen. <br />7. Manual motor starting switches. <br />8. Where so indicated on the drawings. <br />9. As required on all control circuit switches, such as heater controls, etc. <br />2.4 TIME SWITCHES <br />A. Manufacturers: <br />1. Tork. <br />2. Paragon. <br />3. Intermatic. <br />B. Description: AC electronic time clock, 7 day. <br />C. Input voltage: 120V. <br />D. Poles: 40A, 120V, number as indicated. (4 pole minimum) <br />E. Enclosure: Type as required to meet installation. <br />F. Configuration: 365 Day Astronomic, electronic, programmable. <br />G. Accessories: Photocell control as indicated.