MASTER SPECIFICATIONS - ELECTRICAL SPECIFICATIONS <br />SECTION 260513 - MEDIUM-VOLTAGE CABLES <br />PART 1 - GENERAL <br />1. SUMMARY <br />A. SECTION INCLUDES CABLES AND RELATED CABLE SPLICES, TERMINATIONS, AND ACCESSORIES FOR MEDIUM-VOLTAGE (2001 TO 35,000 V) ELECTRICAL DISTRIBUTION SYSTEMS. <br />2. SUBMITTALS <br />B. PRODUCT DATA: FOR EACH TYPE OF CABLE. INCLUDE SPLICES AND TERMINATIONS FOR CABLES AND CABLE ACCESSORIES. <br />PART 2 - PRODUCTS <br />2.1 SYSTEM DESCRIPTION <br />A. ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTED AND LABELED AS DEFINED IN NFPA 70, BY A CERTIFIED NETA TESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND APPLICATION. <br />B. COMPLY WITH IEEE C2 AND NFPA 70. <br />C. SOURCE LIMITATIONS: OBTAIN CABLES AND ACCESSORIES FROM SINGLE SOURCE FROM SINGLE MANUFACTURER. <br />D. MANUFACTURERS <br />1. GENERAL CABLE <br />2. KERNITE POWER CABLE <br />3. OKONITE COMPANY <br />4. SOUTHWIRE COMPANY <br />2.2 CABLES <br />A. CABLE TYPE: TYPE MV 105. <br />B. CONDUCTOR INSULATION: ETHYLENE-PROPYLENE RUBBER. <br />1. VOLTAGE RATING: 15 KV. <br />2. INSULATION THICKNESS: 133 PERCENT INSULATION LEVEL. <br />C. CONDUCTOR: ALUMINUM. <br />D. COMPLY WITH UL 1072, AEIC CS8, ICEA S-93-639/NEMA WC 74, AND ICEA S-97-682. <br />E. CONDUCTOR STRANDING: COMPACT ROUND, CONCENTRIC LAY, CLASS B. <br />F. STRAND FILLING: CONDUCTOR INTERSTICES ARE FILLED WITH IMPERMEABLE COMPOUND. <br />G. SHIELDING: COPPER TAPE, HELICALLY APPLIED OVER SEMICONDUCTING INSULATION SHIELD. <br />H. CABLE JACKET: SUNLIGHT-RESISTANT PVC. <br />2.3 CONNECTORS <br />A. COMPLY WITH ANSI C119.4 FOR CONNECTORS BETWEEN ALUMINUM CONDUCTORS OR FOR CONNECTIONS BETWEEN ALUMINUM TO COPPER CONDUCTORS. <br />2.4 SOLID TERMINATIONS <br />A. SHIELDED-CABLE TERMINATIONS: COMPLY WITH THE FOLLOWING CLASSES OF IEEE 48. INSULATION CLASS SHALL BE EQUIVALENT TO THAT OF CABLE. INCLUDE SHIELD GROUND STRAP FOR SHIELDED <br />CABLE TERMINATIONS. <br />1. CLASS 1 TERMINATIONS: MODULAR TYPE, FURNISHED AS A KIT, WITH STRESS-RELIEF TUBE; MULTIPLE, MOLDED-SILICONE-RUBBER, INSULATOR MODULES; SHIELD GROUND STRAP; AND <br /> COMPRESSION-TYPE CONNECTOR. <br />2.5 SEPARABLE INSULATED CONNECTORS <br />A. DESCRIPTION: MODULAR SYSTEM WITH DISCONNECTING, SINGLE-POLE, CABLE TERMINATORS AND WITH MATCHING, STATIONARY, PLUG-IN, DEAD-FRONT TERMINALS DESIGNED FOR CABLE VOLTAGE AND <br />FOR SEALING AGAINST MOISTURE. <br />B. STANDARD: COMPLY WITH IEEE 386. <br />C. TERMINATIONS AT DISTRIBUTION POINTS: MODULAR TYPE, CONSISTING OF TERMINATORS INSTALLED ON CABLES AND MODULAR, DEAD-FRONT, TERMINAL JUNCTIONS FOR INTERCONNECTING CABLES. <br />D. LOAD-BREAK CABLE TERMINATORS: ELBOW-TYPE UNITS WITH 200-A-LOAD MAKE/BREAK AND CONTINUOUS-CURRENT RATING; COORDINATED WITH INSULATION DIAMETER, CONDUCTOR SIZE, AND <br />MATERIAL OF CABLE BEING TERMINATED. INCLUDE TEST POINT ON TERMINATOR BODY THAT IS CAPACITANCE COUPLED. <br />E. DEAD-BREAK CABLE TERMINATORS: ELBOW-TYPE UNIT WITH 600-A CONTINUOUS-CURRENT RATING; DESIGNED FOR DE-ENERGIZED DISCONNECTING AND CONNECTING; COORDINATED WITH INSULATION <br />DIAMETER, CONDUCTOR SIZE, AND MATERIAL OF CABLE BEING TERMINATED. INCLUDE TEST POINT ON TERMINATOR BODY THAT IS CAPACITANCE COUPLED. <br />F. DEAD-FRONT TERMINAL JUNCTIONS: MODULAR BRACKET-MOUNTED GROUPS OF DEAD-FRONT STATIONARY TERMINALS THAT MATE AND MATCH WITH ABOVE CABLE TERMINATORS. TWO-, THREE-, OR <br />FOUR-TERMINAL UNITS AS INDICATED, WITH FULLY RATED, INSULATED, WATERTIGHT CONDUCTOR CONNECTION BETWEEN TERMINALS AND COMPLETE WITH GROUNDING LUG, MANUFACTURER'S STANDARD <br />ACCESSORY STANDS, STAINLESS-STEEL MOUNTING BRACKETS, AND ATTACHING HARDWARE. <br />1. PROTECTIVE CAP: INSULATING, ELECTROSTATIC-SHIELDING, WATER-SEALING CAP WITH DRAIN WIRE. <br />2. PORTABLE FEED-THROUGH ACCESSORY: TWO-TERMINAL, DEAD-FRONT JUNCTION ARRANGED FOR REMOVABLE MOUNTING ON ACCESSORY STAND OF STATIONARY TERMINAL JUNCTION. <br />3. GROUNDING KIT: JUMPERED ELBOWS, PORTABLE FEED-THROUGH ACCESSORY UNITS, PROTECTIVE CAPS, TEST RODS SUITABLE FOR CONCURRENTLY GROUNDING THREE PHASES OF FEEDERS, <br />AND CARRYING CASE. <br />4. STANDOFF INSULATOR: PORTABLE, SINGLE DEAD-FRONT TERMINAL FOR REMOVABLE MOUNTING ON ACCESSORY STAND OF STATIONARY TERMINAL JUNCTION. INSULATORS SUITABLE FOR <br />FULLY INSULATED ISOLATION OF ENERGIZED CABLE-ELBOW TERMINATOR. <br />2.6 SPLICE KITS <br />A. DESCRIPTION: FOR SPLICING MEDIUM VOLTAGE CABLES; TYPE AS RECOMMENDED BY CABLE OR SPLICING KIT MANUFACTURER FOR THE APPLICATION. <br />B. STANDARD: COMPLY WITH IEEE 404. <br />C. SPLICING PRODUCTS: AS RECOMMENDED, IN WRITING, BY SPLICING KIT MANUFACTURER FOR SPECIFIC SIZES, MATERIALS, RATINGS, AND CONFIGURATIONS OF CABLE CONDUCTORS. INCLUDE ALL <br />COMPONENTS REQUIRED FOR COMPLETE SPLICE, WITH DETAILED INSTRUCTIONS. <br />2.7 MEDIUM-VOLTAGE TAPES <br />A. DESCRIPTION: ELECTRICAL GRADE, INSULATING TAPE FOR MEDIUM VOLTAGE APPLICATION. <br />B. ETHYLENE/PROPYLENE RUBBER-BASED, 30-MIL (0.76-MM) SPLICING TAPE, RATED FOR 130 DEG C OPERATION. MINIMUM 3/4 INCH (20 MM) WIDE. <br />C. INSULATING-PUTTY, 125-MIL (3.175-MM) ELASTIC FILLER TAPE. MINIMUM 1-1/2 INCHES (38 MM) WIDE. <br />2.8 ARC-PROOFING MATERIALS <br />A. TAPE FOR FIRST COURSE ON METAL OBJECTS: 10-MIL- (250-MICROMETER-) THICK, CORROSION-PROTECTIVE, MOISTURE-RESISTANT, PVC PIPE-WRAPPING TAPE. <br />B. ARC-PROOFING TAPE: FIREPROOF TAPE, FLEXIBLE, CONFORMABLE, INTUMESCENT TO 0.3 INCH (8 MM) THICK, AND COMPATIBLE WITH CABLE JACKET. <br />2.9 SOURCE QUALITY CONTROL <br />A. TEST AND INSPECT CABLES ACCORDING TO ICEA S-97-682 BEFORE SHIPPING. <br />B. TEST STRAND-FILLED CABLES FOR WATER-PENETRATION RESISTANCE ACCORDING TO ICEA T-31-610, USING A TEST PRESSURE OF 5 PSIG (35 KPA). <br />PART 3 - EXECUTION <br />3.1 INSTALLATION <br />A. INSTALL CABLES ACCORDING TO IEEE 576. <br />B. PROOF CONDUITS PRIOR TO CONDUCTOR INSTALLATION BY PASSING A WIRE BRUSH MANDREL AND THEN A RUBBER DUCT SWAB THROUGH THE CONDUIT. SEPARATE THE WIRE BRUSH AND THE RUBBER <br />SWAB BY 48 TO 72 INCHES (1200 TO 1800 MM) ON THE PULL ROPE. <br />1. WIRE BRUSH MANDREL: CONSISTS OF A LENGTH OF BRUSH APPROXIMATELY THE SIZE OF THE CONDUIT INNER DIAMETER WITH STIFF STEEL BRISTLES AND AN EYE ON EACH END FOR <br />ATTACHING THE PULL ROPES. IF AN OBSTRUCTION IS FELT, PULL THE BRUSH BACK AND FORTH REPEATEDLY TO BREAK UP THE OBSTRUCTION. <br />2. RUBBER DUCT SWAB: CONSISTS OF A SERIES OF RUBBER DISCS APPROXIMATELY THE SIZE OF THE CONDUIT INNER DIAMETER ON A LENGTH OF STEEL CABLE WITH AN EYE ON EACH END FOR <br />ATTACHING THE PULL ROPES. PULL THE RUBBER DUCT SWAB THROUGH THE DUCT TO EXTRACT LOOSE DEBRIS FROM THE DUCT. <br />C. PULL CONDUCTORS: DO NOT EXCEED MANUFACTURER'S RECOMMENDED MAXIMUM PULLING TENSIONS AND SIDEWALL PRESSURE VALUES. <br />1. WHERE NECESSARY, USE MANUFACTURER-APPROVED PULLING COMPOUND OR LUBRICANT THAT DOES NOT DETERIORATE CONDUCTOR OR INSULATION. <br />2. USE PULLING MEANS, INCLUDING FISH TAPE, CABLE, ROPE, AND BASKET-WEAVE CABLE GRIPS, THAT DO NOT DAMAGE CABLES AND RACEWAYS. DO NOT USE ROPE HITCHES FOR PULLING <br />ATTACHMENT TO CABLE. <br />3. USE PULL-IN GUIDES, CABLE FEEDERS, AND DRAW-IN PROTECTORS AS REQUIRED TO PROTECT CABLES DURING INSTALLATION. <br />4. DO NOT PULL CABLES WITH ENDS UNSEALED. SEAL CABLE ENDS WITH RUBBER TAPE. <br />D. IN MANHOLES, HANDHOLES, PULL BOXES, JUNCTION BOXES, AND CABLE VAULTS, TRAIN CABLES AROUND WALLS BY THE LONGEST ROUTE FROM ENTRY TO EXIT; SUPPORT CABLES AT INTERVALS <br />ADEQUATE TO PREVENT SAG. <br />E. INSTALL SUFFICIENT CABLE LENGTH TO REMOVE CABLE ENDS UNDER PULLING GRIPS. REMOVE LENGTH OF CONDUCTOR DAMAGED DURING PULLING. <br />F. INSTALL CABLE SPLICES AT PULL POINTS AND ELSEWHERE AS INDICATED; USE STANDARD KITS. USE DEAD-FRONT SEPARABLE WATERTIGHT CONNECTORS IN MANHOLES AND OTHER LOCATIONS SUBJECT <br />TO WATER INFILTRATION. <br />G. INSTALL SEPARABLE INSULATED-CONNECTOR COMPONENTS AS FOLLOWS: <br />1. PROTECTIVE CAP: AT EACH TERMINAL JUNCTION, WITH ONE ON EACH TERMINAL TO WHICH NO FEEDER IS INDICATED TO BE CONNECTED. <br />2. PORTABLE FEED-THROUGH ACCESSORY: AT EACH TERMINAL JUNCTION, WITH ONE ON EACH TERMINAL. <br />3. STANDOFF INSULATOR: AT EACH TERMINAL JUNCTION, WITH ONE ON EACH TERMINAL. <br />H. ARC PROOFING: UNLESS OTHERWISE INDICATED, ARC PROOF MEDIUM-VOLTAGE CABLE AT LOCATIONS NOT PROTECTED BY CONDUIT, CABLE TRAY, DIRECT BURIAL, OR TERMINATION MATERIALS. IN <br />ADDITION TO ARC-PROOFING TAPE MANUFACTURER'S WRITTEN INSTRUCTIONS, APPLY ARC PROOFING AS FOLLOWS: <br />1. CLEAN CABLE SHEATH. <br />2. WRAP METALLIC CABLE COMPONENTS WITH 10-MIL (250-MICROMETER) PIPE-WRAPPING TAPE. <br />3. SMOOTH SURFACE CONTOURS WITH ELECTRICAL INSULATION PUTTY. <br />4. APPLY ARC-PROOFING TAPE IN ONE HALF-LAPPED LAYER WITH COATED SIDE TOWARD CABLE. <br />5. BAND ARC-PROOFING TAPE WITH TWO LAYERS OF 1-INCH- (25-MM-) WIDE HALF-LAPPED, ADHESIVE, GLASS-CLOTH TAPE AT EACH END OF THE ARC-PROOF TAPE. <br />I. GROUND SHIELDS OF SHIELDED CABLE AT TERMINATIONS, SPLICES, AND SEPARABLE INSULATED CONNECTORS. GROUND METAL BODIES OF TERMINATORS, SPLICES, CABLE AND SEPARABLE INSULATED- <br />CONNECTOR FITTINGS, AND HARDWARE. <br />J. GROUND SHIELDS OF SHIELDED CABLE AT ONE POINT ONLY. MAINTAIN SHIELD CONTINUITY AND CONNECTIONS TO METAL CONNECTION HARDWARE AT ALL CONNECTION POINTS. <br />K. IDENTIFY CABLES ACCORDING TO SECTION 260553 "IDENTIFICATION FOR ELECTRICAL SYSTEMS." IDENTIFY PHASE AND CIRCUIT NUMBER OF EACH CONDUCTOR AT EACH SPLICE, TERMINATION, PULL POINT, <br />AND JUNCTION BOX. ARRANGE IDENTIFICATION SO THAT IT IS UNNECESSARY TO MOVE THE CABLE OR CONDUCTOR TO READ THE IDENTIFICATION. <br />3.2 FIELD QUALITY CONTROL <br />A.THE FOLLOWING TESTS AND INSPECTIONS SHALL BE PREFORMED BY A NETA CERTIFIED TESTING AGENCY: <br />1. PERFORM EACH VISUAL AND MECHANICAL INSPECTION AND ELECTRICAL TEST STATED IN NETA ATS. CERTIFY COMPLIANCE WITH TEST PARAMETERS. <br />2. AFTER INSTALLING MEDIUM-VOLTAGE CABLES AND BEFORE ELECTRICAL CIRCUITRY HAS BEEN ENERGIZED, TEST FOR COMPLIANCE WITH REQUIREMENTS. <br />3. PERFORM PARTIAL DISCHARGE TEST OF EACH NEW CONDUCTOR ACCORDING TO NETA ATS, CH. 7.3.3 AND TO TEST EQUIPMENT MANUFACTURER'S RECOMMENDATIONS. <br />4. PERFORM TAN DELTA AND WITHSTAND TEST OF EACH NEW CONDUCTOR ACCORDING TO NETA ATS, CH. 7.3.3 AND IEEE 400.2 TO TEST EQUIPMENT MANUFACTURER'S RECOMMENDATIONS. <br />B. PREPARE TEST AND INSPECTION REPORTS. <br />END OF SECTION 260513 <br />SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES <br />PART 1 - GENERAL <br />1.1 SUMMARY <br />A. SECTION INCLUDES: <br />1. COPPER BUILDING WIRE RATED 600 V OR LESS. <br />2. ALUMINUM BUILDING WIRE RATED 600 V OR LESS. <br />3. CONNECTORS, SPLICES, AND TERMINATIONS RATED 600 V AND LESS. <br />1.2 SUBMITTALS <br />A. PRODUCT DATA: FOR EACH TYPE OF PRODUCT. <br />PART 2 - PRODUCTS <br />2.1 MANUFACTURERS <br />A. BELDEN INC. <br />B. GENERAL CABLE <br />C. OKONITE COMPANY <br />D. SERVICE WIRE COMPANY <br />E. SOUTHWIRE COMPANY <br />2.2 COPPER BUILDING WIRE <br />A. DESCRIPTION: FLEXIBLE, INSULATED AND UNINSULATED, DRAWN COPPER CURRENT-CARRYING CONDUCTOR WITH AN OVERALL INSULATION LAYER OR JACKET, OR BOTH, RATED 600 V OR LESS. <br />B. STANDARDS: <br />1. LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND USE. <br />2. ROHS COMPLIANT. <br />3. CONDUCTOR AND CABLE MARKING: COMPLY WITH WIRE AND CABLE MARKING ACCORDING TO UL'S "WIRE AND CABLE MARKING AND APPLICATION GUIDE." <br />C. CONDUCTORS: COPPER, COMPLYING WITH ASTM B3 FOR BARE ANNEALED COPPER AND WITH ASTM B496 FOR STRANDED CONDUCTORS. <br />D. CONDUCTOR INSULATION: <br />1. TYPE NM: COMPLY WITH UL 83 AND UL 719. <br />2. TYPE THHN AND TYPE THWN-2: COMPLY WITH UL 83. <br />3. TYPE XHHW-2: COMPLY WITH UL 44. <br />2.3 ALUMINUM BUILDING WIRE <br />A. DESCRIPTION: FLEXIBLE, INSULATED AND UNINSULATED, DRAWN ALUMINUM CURRENT-CARRYING CONDUCTOR WITH AN OVERALL INSULATION LAYER OR JACKET, OR BOTH, RATED 600 V OR LESS. <br />B. STANDARDS: <br />1. LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND USE. <br />2. ROHS COMPLIANT. <br />3. CONDUCTOR AND CABLE MARKING: COMPLY WITH WIRE AND CABLE MARKING ACCORDING TO UL'S "WIRE AND CABLE MARKING AND APPLICATION GUIDE." <br />C. CONDUCTORS: ALUMINUM, COMPLYING WITH ASTM B800 AND ASTM B801. <br />D. CONDUCTOR INSULATION: <br />1. TYPE NM: COMPLY WITH UL 83 AND UL 719. <br />2. TYPE THHN AND TYPE THWN-2: COMPLY WITH UL 83. <br />3. TYPE XHHW-2: COMPLY WITH UL 44. <br />2.4 CONNECTORS AND SPLICES <br />A. DESCRIPTION: FACTORY-FABRICATED CONNECTORS, SPLICES, AND LUGS OF SIZE, AMPACITY RATING, MATERIAL, TYPE, AND CLASS FOR APPLICATION AND SERVICE INDICATED; LISTED AND LABELED AS <br />DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND USE. <br />B. JACKETED CABLE CONNECTORS: FOR STEEL JACKETED CABLES, ZINC DIE-CAST WITH SET SCREWS, DESIGNED TO CONNECT CONDUCTORS SPECIFIED. <br />C. LUGS: ONE PIECE, SEAMLESS, DESIGNED TO TERMINATE CONDUCTORS SPECIFIED IN THIS SECTION. <br />1. MATERIAL: COPPER OR ALUMINUM. <br />2. TYPE: TWO HOLE WITH STANDARD BARRELS. <br />3. TERMINATION: COMPRESSION. <br />PART 3 - EXECUTION <br />3.1 CONDUCTOR MATERIAL APPLICATIONS <br />A. FEEDERS: COPPER; SOLID FOR NO. 10 AWG AND SMALLER; STRANDED FOR NO. 8 AWG AND LARGER. <br />B. FEEDERS: COPPER FOR FEEDERS SMALLER THAN NO. 4 AWG; COPPER OR ALUMINUM FOR FEEDERS NO. 4 AWG AND LARGER. CONDUCTORS SHALL BE SOLID FOR NO. 10 AWG AND SMALLER; STRANDED <br />FOR NO. 8 AWG AND LARGER. <br />C. BRANCH CIRCUITS: COPPER. SOLID FOR NO. 10 AWG AND SMALLER; STRANDED FOR NO. 8 AWG AND LARGER. <br />3.2 CONDUCTOR INSULATION AND MULTICONDUCTOR CABLE APPLICATIONS AND WIRING METHODS <br />A. SERVICE ENTRANCE: TYPE XHHW-2, SINGLE CONDUCTORS IN RACEWAY. <br />B. EXPOSED FEEDERS: TYPE XHHW-2, SINGLE CONDUCTORS IN RACEWAY. <br />C. FEEDERS CONCEALED IN CONCRETE, BELOW SLABS-ON-GRADE, AND UNDERGROUND: TYPE THHN/THWN-2, SINGLE CONDUCTORS IN RACEWAY. <br />D. EXPOSED BRANCH CIRCUITS: TYPE THHN/THWN-2, SINGLE CONDUCTORS IN RACEWAY. <br />E. BRANCH CIRCUITS CONCEALED IN CONCRETE, BELOW SLABS-ON-GRADE, AND UNDERGROUND: TYPE THHN/THWN-2, SINGLE CONDUCTORS IN RACEWAY. <br />3.3 INSTALLATION OF CONDUCTORS AND CABLES <br />A. COMPLETE RACEWAY INSTALLATION BETWEEN CONDUCTOR AND CABLE TERMINATION POINTS ACCORDING TO SECTION 260533 "RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS" PRIOR TO PULLING <br />CONDUCTORS AND CABLES. <br />B. USE MANUFACTURER-APPROVED PULLING COMPOUND OR LUBRICANT WHERE NECESSARY; COMPOUND USED MUST NOT DETERIORATE CONDUCTOR OR INSULATION. DO NOT EXCEED MANUFACTURER'S <br />RECOMMENDED MAXIMUM PULLING TENSIONS AND SIDEWALL PRESSURE VALUES. <br />C. USE PULLING MEANS, INCLUDING FISH TAPE, CABLE, ROPE, AND BASKET-WEAVE WIRE/CABLE GRIPS, THAT WILL NOT DAMAGE CABLES OR RACEWAY. <br />SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (CONTINUED) <br />3.4 CONNECTIONS <br />A. TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS ACCORDING TO MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES. IF MANUFACTURER'S TORQUE VALUES ARE NOT INDICATED, USE THOSE <br />SPECIFIED IN UL 486A-486B. <br />B. MAKE SPLICES, TERMINATIONS, AND TAPS THAT ARE COMPATIBLE WITH CONDUCTOR MATERIAL AND THAT POSSESS EQUIVALENT OR BETTER MECHANICAL STRENGTH AND INSULATION RATINGS THAN <br />UNSPLICED CONDUCTORS. <br />1. USE OXIDE INHIBITOR IN EACH SPLICE, TERMINATION, AND TAP FOR ALUMINUM CONDUCTORS. <br />3.5 IDENTIFICATION <br />A. IDENTIFY AND COLOR-CODE CONDUCTORS AND CABLES ACCORDING TO SECTION 260553 "IDENTIFICATION FOR ELECTRICAL SYSTEMS." <br />B. IDENTIFY EACH SPARE CONDUCTOR AT EACH END WITH IDENTITY NUMBER AND LOCATION OF OTHER END OF CONDUCTOR AND IDENTIFY AS SPARE CONDUCTOR. <br />3.6 FIRESTOPPING <br />A. APPLY FIRESTOPPING TO ELECTRICAL PENETRATIONS OF FIRE-RATED FLOOR AND WALL ASSEMBLIES TO RESTORE ORIGINAL FIRE-RESISTANCE RATING OF ASSEMBLY. <br />END OF SECTION 260519 <br />SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS <br />PART 1 - GENERAL <br />1.1 SUMMARY <br />A. SECTION INCLUDES GROUNDING AND BONDING SYSTEMS AND EQUIPMENT. <br />B. SECTION INCLUDES GROUNDING AND BONDING SYSTEMS AND EQUIPMENT, PLUS THE FOLLOWING SPECIAL APPLICATIONS: <br />1. UNDERGROUND DISTRIBUTION GROUNDING. <br />2. GROUND BONDING COMMON WITH LIGHTNING PROTECTION SYSTEM. <br />3. FOUNDATION STEEL ELECTRODES. <br />1.2 SUBMITTALS <br />A. PRODUCT DATA: FOR EACH TYPE OF PRODUCT. <br />B. OPERATION AND MAINTENANCE DATA. <br />1. PLANS SHOWING AS-BUILT, DIMENSIONED LOCATIONS OF SYSTEM DESCRIBED IN "FIELD QUALITY CONTROL" ARTICLE, INCLUDING THE FOLLOWING: <br />1.1 GROUND RODS. <br />1.2 GROUND RINGS. <br />1.3 GROUNDING ARRANGEMENTS AND CONNECTIONS FOR SEPARATELY DERIVED SYSTEMS. <br />PART 2 - PRODUCTS <br />2.1 SYSTEM DESCRIPTION <br />A. ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND APPLICATION. <br />B. COMPLY WITH UL 467 FOR GROUNDING AND BONDING MATERIALS AND EQUIPMENT. <br />2.2 CONDUCTORS <br />A. INSULATED CONDUCTORS: COPPER OR ALUMINUM WIRE OR CABLE INSULATED FOR 600 V UNLESS OTHERWISE REQUIRED BY APPLICABLE CODE OR AUTHORITIES HAVING JURISDICTION. <br />B. BARE COPPER CONDUCTORS: <br />1. SOLID COPPER CONDUCTORS: ASTM B3. <br />2. STRANDED COPPER CONDUCTORS: ASTM B496. <br />3. ALUMINUM CONDUCTORS: ASTM B800 AND ASTM B801. <br />4. THWN-2 INSULATION COMPLYING WITH UL 83 OR XHHW-2 INSULATION COMPLYING WITH UL 44. <br />5. GROUNDING ELECTRODE CONDUCTOR OR BONDING JUMPER: SIZED PER NFPA 70 TABLE 250.66. <br />6. SUPPLY-SIDE BONDING JUMPER: SIZED PER NFPA 70 TABLE 250.102(C)(1). <br />7. EQUIPMENT GROUNDING CONDUCTOR: SIZED PER NFPA 70 TABLE 250.122. <br />2.3 CONNECTORS <br />A. LISTED AND LABELED BY AN NRTL ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION FOR APPLICATIONS IN WHICH USED AND FOR SPECIFIC TYPES, SIZES, AND COMBINATIONS OF CONDUCTORS AND <br />B. OTHER ITEMS CONNECTED. <br />C. WELDED CONNECTORS: EXOTHERMIC-WELDING KITS OF TYPES RECOMMENDED BY KIT MANUFACTURER FOR MATERIALS BEING JOINED AND INSTALLATION CONDITIONS. <br />D. BUS-BAR CONNECTORS: MECHANICAL TYPE, CAST SILICON BRONZE, SOLDERLESS COMPRESSION-TYPE WIRE TERMINALS, AND LONG-BARREL, TWO-BOLT CONNECTION TO GROUND BUS BAR. <br />E. CABLE-TO-CABLE CONNECTORS: COMPRESSION TYPE, COPPER OR COPPER ALLOY. <br />F. CONDUIT HUBS: MECHANICAL TYPE, TERMINAL WITH THREADED HUB. <br />G. GROUND ROD CLAMPS: MECHANICAL TYPE, COPPER OR COPPER ALLOY, TERMINAL WITH HEX HEAD BOLT. <br />2.4 GROUNDING ELECTRODES <br />A. GROUND RODS: COPPER-CLAD STEEL, SECTIONAL TYPE; 5/8 BY 96 INCHES (16 BY 2400 MM). <br />PART 3 - EXECUTION <br />3.1 APPLICATIONS <br />A. CONDUCTORS: INSTALL SOLID CONDUCTOR FOR NO. 8 AWG AND SMALLER, AND STRANDED CONDUCTORS FOR NO. 6 AWG AND LARGER UNLESS OTHERWISE INDICATED. <br />B. UNDERGROUND GROUNDING CONDUCTORS: INSTALL BARE COPPER CONDUCTOR, NO. 2/0 AWG MINIMUM. BURY AT LEAST 30 INCHES (750 MM) BELOW GRADE. <br />C. CONDUCTOR TERMINATIONS AND CONNECTIONS: <br />1. GROUNDING CONDUCTOR TERMINATIONS: BOLTED CONNECTORS. <br />2. UNDERGROUND CONNECTIONS: WELDED CONNECTORS EXCEPT AS OTHERWISE INDICATED. <br />3.2 GROUNDING AT THE SERVICE <br />A. EQUIPMENT GROUNDING CONDUCTORS AND GROUNDING ELECTRODE CONDUCTORS SHALL BE CONNECTED TO THE GROUND BUS. INSTALL A MAIN BONDING JUMPER BETWEEN THE NEUTRAL AND <br />GROUND BUSES. <br />B. PAD-MOUNTED SWITCHES AND SWITCHGEAR: INSTALL TWO GROUND RODS AND GROUND RING AROUND THE PAD. GROUND PAD-MOUNTED EQUIPMENT AND NONCURRENT-CARRYING METAL ITEMS BY <br />CONNECTING THEM TO UNDERGROUND CABLE AND GROUNDING ELECTRODES. INSTALL TINNED-COPPER CONDUCTOR NOT LESS THAN NO. 2 AWG FOR GROUND RING AND FOR TAPS TO EQUIPMENT <br />GROUNDING TERMINALS. BURY GROUND RING NOT LESS THAN 6 INCHES (150 MM) FROM THE FOUNDATION. <br />3.3 EQUIPMENT GROUNDING <br />A. INSTALL INSULATED EQUIPMENT GROUNDING CONDUCTORS OR SUPPLY-SIDE BONDING JUMPERS WITH ALL FEEDERS AND BRANCH CIRCUITS. <br />B. INSTALL GROUNDING ELECTRODE(S) AT SWITCHBOARD AND PANEL LOCATIONS INDICATED. EQUIPMENT GROUNDING CONDUCTORS AND GROUNDING ELECTRODE CONDUCTORS SHALL BE CONNECTED TO <br />THE GROUND BUS. INSTALL A MAIN BONDING JUMPER BETWEEN THE NEUTRAL AND GROUND BUSES AT SERVICE AND SEPARATELY DERIVED SYSTEMS WHERE INDICATED. <br />3.4 INSTALLATION <br />A. GROUNDING CONDUCTORS: ROUTE ALONG SHORTEST AND STRAIGHTEST PATHS POSSIBLE UNLESS OTHERWISE INDICATED OR REQUIRED BY CODE. AVOID OBSTRUCTING ACCESS OR PLACING <br />CONDUCTORS WHERE THEY MAY BE SUBJECTED TO STRAIN, IMPACT, OR DAMAGE. <br />B. GROUND RODS: DRIVE RODS UNTIL TOPS ARE 2 INCHES (50 MM) BELOW FINISHED FLOOR OR FINAL GRADE UNLESS OTHERWISE INDICATED. INTERCONNECT GROUND RODS WITH GROUNDING ELECTRODE <br />CONDUCTOR BELOW GRADE. MAKE CONNECTIONS WITHOUT EXPOSING STEEL OR DAMAGING COATING IF ANY. <br /> 3.5 FIELD QUALITY CONTROL <br />A. TESTS AND INSPECTIONS: <br />1. AFTER INSTALLING GROUNDING SYSTEM BUT BEFORE PERMANENT ELECTRICAL CIRCUITS HAVE BEEN ENERGIZED, TEST FOR COMPLIANCE WITH REQUIREMENTS. <br />2. INSPECT PHYSICAL AND MECHANICAL CONDITION. VERIFY TIGHTNESS OF ACCESSIBLE, BOLTED, ELECTRICAL CONNECTIONS WITH A CALIBRATED TORQUE WRENCH ACCORDING TO <br />MANUFACTURER'S WRITTEN INSTRUCTIONS. <br />3. TEST COMPLETED GROUNDING SYSTEM AT EACH GROUNDING ELECTRODE CONNECTION POINT AND INDIVIDUAL GROUND RODS. MAKE TESTS AT GROUND RODS BEFORE ANY CONDUCTORS <br />ARE CONNECTED. <br />a. MEASURE GROUND RESISTANCE NO FEWER THAN TWO FULL DAYS AFTER LAST TRACE OF PRECIPITATION AND WITHOUT SOIL BEING MOISTENED BY ANY MEANS OTHER THAN <br />NATURAL DRAINAGE OR SEEPAGE AND WITHOUT CHEMICAL TREATMENT OR OTHER ARTIFICIAL MEANS OF REDUCING NATURAL GROUND RESISTANCE. <br />b. PERFORM TESTS BY FALL-OF-POTENTIAL METHOD ACCORDING TO IEEE 81. <br />B. PREPARE TEST AND INSPECTION REPORTS. <br />C. REPORT MEASURED GROUND RESISTANCES THAT EXCEED THE FOLLOWING VALUES: <br />1. POWER EQUIPMENT OR SYSTEM WITH CAPACITY OF 500 KVA AND LESS: 10 OHMS. <br />2. POWER EQUIPMENT OR SYSTEM WITH CAPACITY OF 500 TO 1000 KVA: 5 OHMS. <br />3. POWER EQUIPMENT OR SYSTEM WITH CAPACITY MORE THAN 1000 KVA: 3 OHMS. <br />D. EXCESSIVE GROUND RESISTANCE: IF RESISTANCE TO GROUND EXCEEDS SPECIFIED VALUES, NOTIFY ENGINEER PROMPTLY AND INCLUDE RECOMMENDATIONS TO REDUCE GROUND RESISTANCE. <br />END OF SECTION 260526 <br />SECTION 260529 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS <br />PART 1 - GENERAL <br />1,1 SUMMARY <br />A. SECTION INCLUDES: <br />1. STEEL SLOTTED SUPPORT SYSTEMS. <br />2. CONDUIT AND CABLE SUPPORT DEVICES. <br />3. SUPPORT FOR CONDUCTORS IN VERTICAL CONDUIT. <br />4. STRUCTURAL STEEL FOR FABRICATED SUPPORTS AND RESTRAINTS. <br />5. MOUNTING, ANCHORING, AND ATTACHMENT COMPONENTS, INCLUDING POWDER-ACTUATED FASTENERS, MECHANICAL EXPANSION ANCHORS, CONCRETE INSERTS, CLAMPS, THROUGH BOLTS, <br />TOGGLE BOLTS, AND HANGER RODS. <br />B. RELATED REQUIREMENTS: <br />1. SECTION 260548.16 "SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS" FOR PRODUCTS AND INSTALLATION REQUIREMENTS NECESSARY FOR COMPLIANCE WITH SEISMIC CRITERIA. <br />1.2 SUBMITTALS <br />A. PRODUCT DATA: FOR EACH TYPE OF PRODUCT. <br />B. SHOP DRAWINGS: FOR FABRICATION AND INSTALLATION DETAILS FOR ELECTRICAL SUPPORT SYSTEMS. <br />1. SLOTTED SUPPORT SYSTEMS. <br />2. EQUIPMENT SUPPORTS. <br />3. VIBRATION ISOLATION BASE DETAILS: DETAIL FABRICATION INCLUDING ANCHORAGES AND ATTACHMENTS TO STRUCTURE AND TO SUPPORTED EQUIPMENT. INCLUDE ADJUSTABLE MOTOR <br />BASES, RAILS, AND FRAMES FOR EQUIPMENT MOUNTING. <br />1.3 QUALITY ASSURANCE <br />A. WELDING QUALIFICATIONS: QUALIFY PROCEDURES AND PERSONNEL ACCORDING TO THE FOLLOWING: <br />1. AWS D1.1/D1.1M. <br />2. AWS D1.2/D1.2M. <br />PART 2 - PRODUCTS <br />2.1 PERFORMANCE REQUIREMENTS <br />A. SEISMIC PERFORMANCE: HANGERS AND SUPPORTS SHALL WITHSTAND THE EFFECTS OF EARTHQUAKE MOTIONS DETERMINED ACCORDING TO ASCE/SEI 7. THE TERM "WITHSTAND" MEANS "THE <br />SUPPORTED EQUIPMENT AND SYSTEMS WILL REMAIN IN PLACE WITHOUT SEPARATION OF ANY PARTS WHEN SUBJECTED TO THE SEISMIC FORCES SPECIFIED. <br />2.2 SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS <br />A. STEEL SLOTTED SUPPORT SYSTEMS: PREFORMED STEEL CHANNELS AND ANGLES WITH MINIMUM 13/32-INCH- (10-MM-) DIAMETER HOLES AT A MAXIMUM OF 8 INCHES (200 MM) O.C. IN AT LEAST ONE <br />SURFACE. <br />1. STANDARD: COMPLY WITH MFMA-4 FACTORY-FABRICATED COMPONENTS FOR FIELD ASSEMBLY. <br />2. MATERIAL FOR CHANNEL, FITTINGS, AND ACCESSORIES: GALVANIZED STEEL. <br />3. CHANNEL WIDTH: SELECTED FOR APPLICABLE LOAD CRITERIA. <br />4. METALLIC COATINGS: HOT-DIP GALVANIZED AFTER FABRICATION AND APPLIED ACCORDING TO MFMA-4. <br />5. PROTECT FINISHES ON EXPOSED SURFACES FROM DAMAGE BY APPLYING A STRIPPABLE, TEMPORARY PROTECTIVE COVERING BEFORE SHIPPING. <br />B. CONDUIT AND CABLE SUPPORT DEVICES: STEEL AND MALLEABLE-IRON HANGERS, CLAMPS, AND ASSOCIATED FITTINGS, DESIGNED FOR TYPES AND SIZES OF RACEWAY OR CABLE TO BE SUPPORTED. <br />C. SUPPORT FOR CONDUCTORS IN VERTICAL CONDUIT: FACTORY-FABRICATED ASSEMBLY CONSISTING OF THREADED BODY AND INSULATING WEDGING PLUG OR PLUGS FOR NONARMORED ELECTRICAL <br />CONDUCTORS OR CABLES IN RISER CONDUITS. PLUGS SHALL HAVE NUMBER, SIZE, AND SHAPE OF CONDUCTOR GRIPPING PIECES AS REQUIRED TO SUIT INDIVIDUAL CONDUCTORS OR CABLES SUPPORTED. <br />BODY SHALL BE MADE OF MALLEABLE IRON. <br />D. STRUCTURAL STEEL FOR FABRICATED SUPPORTS AND RESTRAINTS: ASTM A36/A36M STEEL PLATES, SHAPES, AND BARS; BLACK AND GALVANIZED. <br />E. MOUNTING, ANCHORING, AND ATTACHMENT COMPONENTS: ITEMS FOR FASTENING ELECTRICAL ITEMS OR THEIR SUPPORTS TO BUILDING SURFACES INCLUDE THE FOLLOWING: <br />1. POWDER-ACTUATED FASTENERS: THREADED-STEEL STUD, FOR USE IN HARDENED PORTLAND CEMENT CONCRETE, STEEL, OR WOOD, WITH TENSION, SHEAR, AND PULLOUT CAPACITIES <br />APPROPRIATE FOR SUPPORTED LOADS AND BUILDING MATERIALS WHERE USED. <br />2. MECHANICAL-EXPANSION ANCHORS: INSERT-WEDGE-TYPE, ZINC-COATED STEEL, FOR USE IN HARDENED PORTLAND CEMENT CONCRETE, WITH TENSION, SHEAR, AND PULLOUT CAPACITIES <br />APPROPRIATE FOR SUPPORTED LOADS AND BUILDING MATERIALS WHERE USED. <br />3. CONCRETE INSERTS: STEEL OR MALLEABLE-IRON, SLOTTED SUPPORT SYSTEM UNITS ARE SIMILAR TO MSS TYPE 18 UNITS AND COMPLY WITH MFMA-4 OR MSS SP-58. <br />4. THROUGH BOLTS: STRUCTURAL TYPE, HEX HEAD, AND HIGH STRENGTH. COMPLY WITH ASTM F3125/F3125M, GRADE A325 (GRADE A325M). <br />5. TOGGLE BOLTS: ALL-STEEL SPRINGHEAD TYPE. <br />6. HANGER RODS: THREADED STEEL. <br />PART 3 - EXECUTION <br />3.1 APPLICATION <br />A. COMPLY WITH THE FOLLOWING STANDARDS FOR APPLICATION AND INSTALLATION REQUIREMENTS OF HANGERS AND SUPPORTS, EXCEPT WHERE REQUIREMENTS ON DRAWINGS OR IN THIS SECTION ARE <br />STRICTER: <br />1 NECA 1. <br />2. NECA 101. <br />3. NECA 102. <br />4. NECA 105. <br />5. NECA 111. <br />B. COMPLY WITH REQUIREMENTS FOR RACEWAYS AND BOXES SPECIFIED IN SECTION 260533 "RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS." <br />C. MAXIMUM SUPPORT SPACING AND MINIMUM HANGER ROD SIZE FOR RACEWAYS: SPACE SUPPORTS FOR EMT, IMC, AND RMC AS REQUIRED BY NFPA 70. MINIMUM ROD SIZE SHALL BE 1/4 INCH (6 MM) IN <br />DIAMETER. <br />D. MULTIPLE RACEWAYS OR CABLES: INSTALL SUPPORTS FABRICATED WITH STEEL SLOTTED OR OTHER SUPPORT SYSTEM, SIZED SO CAPACITY CAN BE INCREASED BY AT LEAST 25 PERCENT AT A LATER <br />DATE WITHOUT EXCEEDING SPECIFIED DESIGN LOAD LIMITS. <br />1. SECURE RACEWAYS AND CABLES TO THESE SUPPORTS WITH TWO-BOLT CONDUIT CLAMPS. <br />E. SPRING-STEEL CLAMPS DESIGNED FOR SUPPORTING SINGLE CONDUITS WITHOUT BOLTS MAY BE USED FOR 1-1/2-INCH (38-MM) AND SMALLER RACEWAYS SERVING BRANCH CIRCUITS, AND FOR <br />FASTENING RACEWAYS TO TRAPEZE SUPPORTS. <br />3.2 SUPPORT INSTALLATION <br />A. COMPLY WITH NECA 1 AND NECA 101 FOR INSTALLATION REQUIREMENTS EXCEPT AS SPECIFIED IN THIS ARTICLE. <br />B. RACEWAY SUPPORT METHODS: IN ADDITION TO METHODS DESCRIBED IN NECA 1, EMT, IMC, AND RMC MAY BE SUPPORTED BY OPENINGS THROUGH STRUCTURE MEMBERS, ACCORDING TO NFPA 70. <br />C. STRENGTH OF SUPPORT ASSEMBLIES: WHERE NOT INDICATED, SELECT SIZES OF COMPONENTS SO STRENGTH WILL BE ADEQUATE TO CARRY PRESENT AND AT A LATER DATE STATIC LOADS WITHIN <br />SPECIFIED LOADING LIMITS. MINIMUM STATIC DESIGN LOAD USED FOR STRENGTH DETERMINATION SHALL BE WEIGHT OF SUPPORTED COMPONENTS PLUS 200 LB (90 KG). <br />D. MOUNTING AND ANCHORAGE OF SURFACE-MOUNTED EQUIPMENT AND COMPONENTS: ANCHOR AND FASTEN ELECTRICAL ITEMS AND THEIR SUPPORTS TO BUILDING STRUCTURAL ELEMENTS BY THE <br />FOLLOWING METHODS UNLESS OTHERWISE INDICATED BY CODE: <br />1. TO NEW CONCRETE: BOLT TO CONCRETE INSERTS. <br />2. TO MASONRY: APPROVED TOGGLE-TYPE BOLTS ON HOLLOW MASONRY UNITS AND EXPANSION ANCHOR FASTENERS ON SOLID MASONRY UNITS. <br />3. TO EXISTING CONCRETE: EXPANSION ANCHOR FASTENERS. <br />4. INSTEAD OF EXPANSION ANCHORS, POWDER-ACTUATED DRIVEN THREADED STUDS PROVIDED WITH LOCK WASHERS AND NUTS MAY BE USED IN EXISTING STANDARD-WEIGHT CONCRETE 4 <br />INCHES (100 MM) THICK OR GREATER. DO NOT USE FOR ANCHORAGE TO LIGHTWEIGHT-AGGREGATE CONCRETE OR FOR SLABS LESS THAN 4 INCHES (100 MM) THICK. <br />5. TO STEEL: WELDED THREADED STUDS COMPLYING WITH AWS D1.1/D1.1M, WITH LOCK WASHERS AND NUTS. <br />6. TO LIGHT STEEL: SHEET METAL SCREWS. <br />7. ITEMS MOUNTED ON HOLLOW WALLS AND NONSTRUCTURAL BUILDING SURFACES: MOUNT CABINETS, PANELBOARDS, DISCONNECT SWITCHES, CONTROL ENCLOSURES, PULL AND JUNCTION <br />BOXES, TRANSFORMERS, AND OTHER DEVICES ON SLOTTED-CHANNEL RACKS ATTACHED TO SUBSTRATE BY MEANS THAT COMPLY WITH SEISMIC-RESTRAINT STRENGTH AND ANCHORAGE <br />REQUIREMENTS. <br />E. DRILL HOLES FOR EXPANSION ANCHORS IN CONCRETE AT LOCATIONS AND TO DEPTHS THAT AVOID THE NEED FOR REINFORCING BARS. <br />END OF SECTION 260569 <br />1. <br />2. <br />3. <br />4. <br />5. <br />1. <br />2. <br />3. <br />4. <br />a. <br />b. <br />5. <br />1. <br />1. <br />2. <br />3. <br />1. <br />2. <br />1. <br />A. <br />1. <br />2. <br />B. <br />1. <br />2. <br />3. <br />4. <br />5. <br />6. <br />7. <br />1. <br />2. <br />3. <br />4. <br />5. <br />1. <br />2. <br />3. <br />a. <br />b. <br />c. <br />4. <br />5. <br />6. <br />7. <br />1. <br />2. <br />3. <br />1. <br />2. <br />3. <br />4. <br />5. <br />1. <br />2. <br />3. <br />4. <br />1. <br />a. <br />b. <br />1. <br />2. <br />a. <br />3. <br />a. <br />b. <br />c. <br />d. <br />A. <br />B. <br />C. <br />D. <br />SECTION 260533 - RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS <br />PART 1 - GENERAL <br />1.1 SUMMARY <br />A. SECTION INCLUDES: <br />1. METAL CONDUITS AND FITTINGS. <br />2. NON-METALLIC CONDUITS AND FITTINGS. <br />3. BOXES AND ENCLOSURES. <br />4. HANDHOLES AND BOXES FOR EXTERIOR UNDERGROUND CABLING. <br /> 1.2 SUBMITTALS <br />A. PRODUCT DATA: FOR EACH TYPE OF PRODUCT. <br />B. SEISMIC QUALIFICATION DATA: CERTIFICATES, FOR ENCLOSURES, CABINETS, AND CONDUIT RACKS AND THEIR MOUNTING PROVISIONS, INCLUDING THOSE FOR INTERNAL COMPONENTS, FROM <br />MANUFACTURER. <br />PART 2 - PRODUCTS <br />2.1 METAL CONDUITS AND FITTINGS <br />A. METAL CONDUIT: <br />LISTING AND LABELING: METAL CONDUITS, TUBING, AND FITTINGS SHALL BE LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY, AND MARKED <br />FOR INTENDED LOCATION AND APPLICATION. <br />GRC: COMPLY WITH ANSI C80.1 AND UL 6. <br />IMC: COMPLY WITH ANSI C80.6 AND UL 1242. <br />EMT: COMPLY WITH ANSI C80.3 AND UL 797. <br />LFMC: FLEXIBLE STEEL CONDUIT WITH PVC JACKET AND COMPLYING WITH UL 360. <br />B .METAL FITTINGS: COMPLY WITH NEMA FB 1 AND UL 514B. <br />LISTING AND LABELING: LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND APPLICATION. <br />FITTINGS, GENERAL: LISTED AND LABELED FOR TYPE OF CONDUIT, LOCATION, AND USE. <br />CONDUIT FITTINGS FOR HAZARDOUS (CLASSIFIED) LOCATIONS: COMPLY WITH UL 1203 AND NFPA 70. <br />FITTINGS FOR EMT: <br />MATERIAL: STEEL OR DIE CAST. <br />TYPE: SETSCREW. <br />EXPANSION FITTINGS: PVC OR STEEL TO MATCH CONDUIT TYPE, COMPLYING WITH UL 651, RATED FOR ENVIRONMENTAL CONDITIONS WHERE INSTALLED, AND INCLUDING <br />FLEXIBLE EXTERNAL BONDING JUMPER. <br />C. JOINT COMPOUND FOR IMC OR GRC: APPROVED, AS DEFINED IN NFPA 70, BY AUTHORITIES HAVING JURISDICTION FOR USE IN CONDUIT ASSEMBLIES, AND COMPOUNDED FOR USE TO LUBRICATE AND <br />PROTECT THREADED CONDUIT JOINTS FROM CORROSION AND TO ENHANCE THEIR CONDUCTIVITY. <br />2.2 NONMETALLIC CONDUITS AND FITTINGS <br />A. LISTING AND LABELING: LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND APPLICATION. <br />RNC: TYPE EPC-40-PVC, COMPLYING WITH NEMA TC 2 AND UL 651 UNLESS OTHERWISE INDICATED. <br />B. NONMETALLIC FITTINGS: <br />FITTINGS, GENERAL: LISTED AND LABELED FOR TYPE OF CONDUIT, LOCATION, AND USE. <br />FITTINGS FOR RNC: COMPLY WITH NEMA TC 3; MATCH TO CONDUIT OR TUBING TYPE AND MATERIAL. <br />SOLVENTS AND ADHESIVES: AS RECOMMENDED BY CONDUIT MANUFACTURER. <br />2.3 BOXES AND ENCLOSURES <br />A. GENERAL REQUIREMENTS FOR BOXES AND ENCLOSURES: BOXES, ENCLOSURES, AND CABINETS INSTALLED IN WET LOCATIONS SHALL BE LISTED FOR USE IN WET LOCATIONS. <br />B. CAST-METAL OUTLET AND DEVICE BOXES: COMPLY WITH NEMA FB 1, FERROUS ALLOY, TYPE FD, WITH GASKETED COVER. <br />C. SMALL SHEET METAL PULL AND JUNCTION BOXES: NEMA OS 1. <br />D. CAST-METAL ACCESS, PULL, AND JUNCTION BOXES: COMPLY WITH NEMA FB 1 AND UL 1773, GALVANIZED, CAST IRON WITH GASKETED COVER. <br />E. DEVICE BOX DIMENSIONS: 4 INCHES SQUARE BY 2-1/8 INCHES DEEP (100 MM SQUARE BY 60 MM DEEP). <br />F. HINGED-COVER ENCLOSURES: COMPLY WITH UL 50 AND NEMA 250, TYPE 4 WITH CONTINUOUS-HINGE COVER WITH FLUSH LATCH UNLESS OTHERWISE INDICATED. <br />METAL ENCLOSURES: STEEL, FINISHED INSIDE AND OUT WITH MANUFACTURER''S STANDARD ENAMEL. <br />INTERIOR PANELS: STEEL; ALL SIDES FINISHED WITH MANUFACTURER''S STANDARD ENAMEL. <br />HANDHOLES AND BOXES FOR EXTERIOR UNDERGROUND WIRING <br />GENERAL REQUIREMENTS FOR HANDHOLES AND BOXES: <br />BOXES AND HANDHOLES FOR USE IN UNDERGROUND SYSTEMS SHALL BE DESIGNED AND IDENTIFIED AS DEFINED IN NFPA 70, FOR INTENDED LOCATION AND APPLICATION. <br />BOXES INSTALLED IN WET AREAS SHALL BE LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND <br />APPLICATION. <br />POLYMER-CONCRETE HANDHOLES AND BOXES WITH POLYMER-CONCRETE COVER: MOLDED OF SAND AND AGGREGATE, BOUND TOGETHER WITH POLYMER RESIN, AND REINFORCED <br />WITH STEEL, FIBERGLASS, OR A COMBINATION OF THE TWO. <br />STANDARD: COMPLY WITH SCTE 77. <br />CONFIGURATION: DESIGNED FOR FLUSH BURIAL WITH INTEGRAL CLOSED BOTTOM UNLESS OTHERWISE INDICATED. <br />COVER: WEATHERPROOF, SECURED BY TAMPER-RESISTANT LOCKING DEVICES AND HAVING STRUCTURAL LOAD RATING CONSISTENT WITH ENCLOSURE AND HANDHOLE <br />LOCATION. <br />COVER FINISH: NONSKID FINISH SHALL HAVE A MINIMUM COEFFICIENT OF FRICTION OF 0.50. <br />COVER LEGEND: MOLDED LETTERING, "ELECTRIC.". <br />TRAFFIC RATED FOR AREA OF INSTALLATION. <br />CONDUIT ENTRANCE PROVISIONS: CONDUIT-TERMINATING FITTINGS SHALL MATE WITH ENTERING DUCTS FOR SECURE, FIXED INSTALLATION IN ENCLOSURE WALL. <br />PART 3 - EXECUTION <br />3.1 RACEWAY APPLICATION <br />A. OUTDOORS: APPLY RACEWAY PRODUCTS AS SPECIFIED BELOW UNLESS OTHERWISE INDICATED: <br />EXPOSED CONDUIT: GRC. <br />CONCEALED CONDUIT, ABOVEGROUND: IMC. <br />UNDERGROUND CONDUIT: TYPE EPC-40-PVC, DIRECT BURIED. <br />CONNECTION TO VIBRATING EQUIPMENT (INCLUDING TRANSFORMERS AND HYDRAULIC, PNEUMATIC, ELECTRIC SOLENOID, OR MOTOR-DRIVEN EQUIPMENT): LFMC. <br />BOXES AND ENCLOSURES, ABOVEGROUND: NEMA 250, TYPE 4. <br />B. INDOORS: APPLY RACEWAY PRODUCTS AS SPECIFIED BELOW UNLESS OTHERWISE INDICATED. <br />EXPOSED, NOT SUBJECT TO PHYSICAL DAMAGE: EMT. <br />EXPOSED, NOT SUBJECT TO SEVERE PHYSICAL DAMAGE: EMT. <br />EXPOSED AND SUBJECT TO SEVERE PHYSICAL DAMAGE: GRC. RACEWAY LOCATIONS INCLUDE THE FOLLOWING: <br />LOADING DOCK. <br />CORRIDORS USED FOR TRAFFIC OF MECHANIZED CARTS, FORKLIFTS, AND PALLET-HANDLING UNITS. <br />MECHANICAL ROOMS. <br />CONCEALED IN CEILINGS AND INTERIOR WALLS AND PARTITIONS: EMT. <br />CONNECTION TO VIBRATING EQUIPMENT (INCLUDING TRANSFORMERS AND HYDRAULIC, PNEUMATIC, ELECTRIC SOLENOID, OR MOTOR-DRIVEN EQUIPMENT): LFMC. <br />DAMP OR WET LOCATIONS: IMC. <br />BOXES AND ENCLOSURES: NEMA 250, TYPE 12. <br />C. MINIMUM RACEWAY SIZE: 3/4-INCH (21-MM) TRADE SIZE. <br />D. RACEWAY FITTINGS: COMPATIBLE WITH RACEWAYS AND SUITABLE FOR USE AND LOCATION. <br />RIGID AND INTERMEDIATE STEEL CONDUIT: USE THREADED RIGID STEEL CONDUIT FITTINGS UNLESS OTHERWISE INDICATED. COMPLY WITH NEMA FB 2.10. <br />EMT: USE SETSCREW, CAST-METAL FITTINGS. COMPLY WITH NEMA FB 2.10. <br />FLEXIBLE CONDUIT: USE ONLY FITTINGS LISTED FOR USE WITH FLEXIBLE CONDUIT. COMPLY WITH NEMA FB 2.20. <br />3.2 INSTALLATION <br />A. COMPLY WITH NECA 1 AND NECA 101 FOR INSTALLATION REQUIREMENTS EXCEPT WHERE REQUIREMENTS ON DRAWINGS OR IN THIS ARTICLE ARE STRICTER. COMPLY WITH NFPA 70 LIMITATIONS FOR <br />TYPES OF RACEWAYS ALLOWED IN SPECIFIC OCCUPANCIES AND NUMBER OF FLOORS. <br />B. DO NOT INSTALL RACEWAYS OR ELECTRICAL ITEMS ON ANY "EXPLOSION-RELIEF" WALLS OR ROTATING EQUIPMENT. <br />C. DO NOT FASTEN CONDUITS ONTO THE BOTTOM SIDE OF A METAL DECK ROOF. <br />D. KEEP RACEWAYS AT LEAST 6 INCHES (150 MM) AWAY FROM PARALLEL RUNS OF FLUES AND STEAM OR HOT-WATER PIPES. INSTALL HORIZONTAL RACEWAY RUNS ABOVE WATER AND STEAM PIPING. <br />E. COMPLY WITH REQUIREMENTS IN SECTION 260529 "HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS" FOR HANGERS AND SUPPORTS. <br />F. ARRANGE STUB-UPS SO CURVED PORTIONS OF BENDS ARE NOT VISIBLE ABOVE GRADE. <br />G. INSTALL NO MORE THAN THE EQUIVALENT OF THREE 90-DEGREE BENDS IN ANY CONDUIT RUN EXCEPT FOR CONTROL WIRING CONDUITS, FOR WHICH FEWER BENDS ARE ALLOWED. SUPPORT WITHIN 12 I <br /> INCHES (300 MM) OF CHANGES IN DIRECTION. <br />H. MAKE BENDS IN RACEWAY USING LARGE-RADIUS PREFORMED ELLS. FIELD BENDING SHALL BE ACCORDING TO NFPA 70 MINIMUM RADII REQUIREMENTS. USE ONLY EQUIPMENT SPECIFICALLY DESIGNED <br />FOR MATERIAL AND SIZE INVOLVED. <br />I. INSTALL CONDUITS PARALLEL OR PERPENDICULAR TO BUILDING LINES. <br />J. SUPPORT CONDUIT WITHIN 12 INCHES (300 MM) OF ENCLOSURES TO WHICH ATTACHED. <br />K. THREADED CONDUIT JOINTS, EXPOSED TO WET, DAMP, CORROSIVE, OR OUTDOOR CONDITIONS: APPLY LISTED COMPOUND TO THREADS OF RACEWAY AND FITTINGS BEFORE MAKING UP JOINTS. FOLLOW <br />COMPOUND MANUFACTURER'S WRITTEN INSTRUCTIONS. <br />L. RACEWAY TERMINATIONS AT LOCATIONS SUBJECT TO MOISTURE OR VIBRATION: USE INSULATING BUSHINGS TO PROTECT CONDUCTORS INCLUDING CONDUCTORS SMALLER THAN NO. 4 AWG. <br />M. TERMINATE THREADED CONDUITS INTO THREADED HUBS OR WITH LOCKNUTS ON INSIDE AND OUTSIDE OF BOXES OR CABINETS. INSTALL BUSHINGS ON CONDUITS UP TO 1-1/4-INCH (35-MM) TRADE SIZE <br />AND INSULATED THROAT METAL BUSHINGS ON 1-1/2-INCH (41-MM) TRADE SIZE AND LARGER CONDUITS TERMINATED WITH LOCKNUTS. INSTALL INSULATED THROAT METAL GROUNDING BUSHINGS ON <br />SERVICE CONDUITS. <br />N. INSTALL PULL WIRES IN EMPTY RACEWAYS. USE POLYPROPYLENE OR MONOFILAMENT PLASTIC LINE WITH NOT LESS THAN 200-LB (90-KG) TENSILE STRENGTH. LEAVE AT LEAST 12 INCHES (300 MM) OF <br />SLACK AT EACH END OF PULL WIRE. CAP UNDERGROUND RACEWAYS DESIGNATED AS SPARE ABOVE GRADE ALONGSIDE RACEWAYS IN USE. <br />O. INSTALL DEVICES TO SEAL RACEWAY INTERIORS AT ACCESSIBLE LOCATIONS. LOCATE SEALS SO NO FITTINGS OR BOXES ARE BETWEEN THE SEAL AND THE FOLLOWING CHANGES OF ENVIRONMENTS. <br />SEAL THE INTERIOR OF ALL RACEWAYS AT THE FOLLOWING POINTS: <br />1. CONDUIT EXTENDING FROM INTERIOR TO EXTERIOR OF BUILDING. <br />2. WHERE OTHERWISE REQUIRED BY NFPA 70. <br />P. FLEXIBLE CONDUIT CONNECTIONS: COMPLY WITH NEMA RV 3. USE A MAXIMUM OF 36 INCHES (915 MM) OF FLEXIBLE CONDUIT FOR EQUIPMENT SUBJECT TO VIBRATION, NOISE TRANSMISSION, OR <br />MOVEMENT; AND FOR TRANSFORMERS AND MOTORS. <br />Q. MOUNT BOXES AT HEIGHTS INDICATED ON DRAWINGS. INSTALL BOXES WITH HEIGHT MEASURED TO TOP OF BOX UNLESS OTHERWISE INDICATED. <br />R. FASTEN JUNCTION AND PULL BOXES TO OR SUPPORT FROM BUILDING STRUCTURE. DO NOT SUPPORT BOXES BY CONDUITS. <br />3.3 INSTALLATION OF UNDERGROUND CONDUIT <br />A. DIRECT-BURIED CONDUIT: <br />EXCAVATE TRENCH BOTTOM TO PROVIDE FIRM AND UNIFORM SUPPORT FOR CONDUIT. PREPARE TRENCH BOTTOM AS SPECIFIED IN SECTION 312000 "EARTH MOVING" FOR <br />PIPE LESS THAN 6 INCHES (150 MM) IN NOMINAL DIAMETER. <br />INSTALL BACKFILL AS SPECIFIED IN SECTION 312000 "EARTH MOVING." <br />AFTER INSTALLING CONDUIT, BACKFILL AND COMPACT. START AT TIE-IN POINT, AND WORK TOWARD END OF CONDUIT RUN, LEAVING CONDUIT AT END OF RUN FREE TO <br />MOVE WITH EXPANSION AND CONTRACTION AS TEMPERATURE CHANGES DURING THIS PROCESS. FIRMLY HAND TAMP BACKFILL AROUND CONDUIT TO PROVIDE MAXIMUM <br />SUPPORTING STRENGTH. AFTER PLACING CONTROLLED BACKFILL TO WITHIN 12 INCHES (300 MM) OF FINISHED GRADE, MAKE FINAL CONDUIT CONNECTION AT END OF RUN <br />AND COMPLETE BACKFILLING WITH NORMAL COMPACTION AS SPECIFIED IN SECTION 312000 "EARTH MOVING." <br />INSTALL MANUFACTURED RIGID STEEL CONDUIT ELBOWS FOR STUB-UPS AT EQUIPMENT. <br />UNDERGROUND WARNING TAPE: COMPLY WITH REQUIREMENTS IN SECTION 260553 "IDENTIFICATION FOR ELECTRICAL SYSTEMS." <br />3.4 INSTALLATION OF UNDERGROUND HANDHOLES AND BOXES <br />A. INSTALL HANDHOLES AND BOXES LEVEL AND PLUMB AND WITH ORIENTATION AND DEPTH COORDINATED WITH CONNECTING CONDUITS TO MINIMIZE BENDS AND DEFLECTIONS REQUIRED FOR PROPER <br />ENTRANCES. <br />B. UNLESS OTHERWISE INDICATED, SUPPORT UNITS ON A LEVEL BED OF CRUSHED STONE OR GRAVEL, GRADED FROM 1/2-INCH (12.5-MM) SIEVE TO NO. 4 (4.75-MM) SIEVE AND COMPACTED TO SAME DENSITY <br />AS ADJACENT UNDISTURBED EARTH. <br />C. ELEVATION: IN PAVED AREAS, SET SO COVER SURFACE WILL BE FLUSH WITH FINISHED GRADE. SET COVERS OF OTHER ENCLOSURES 1 INCH (25 MM) ABOVE FINISHED GRADE. <br />D. INSTALL HANDHOLES WITH BOTTOM BELOW FROST LINE. <br />E. FIELD-CUT OPENINGS FOR CONDUITS ACCORDING TO ENCLOSURE MANUFACTURER'S WRITTEN INSTRUCTIONS. CUT WALL OF ENCLOSURE WITH A TOOL DESIGNED FOR MATERIAL TO BE CUT. SIZE HOLES <br />FOR TERMINATING FITTINGS TO BE USED, AND SEAL AROUND PENETRATIONS AFTER FITTINGS ARE INSTALLED. <br />3.5 PROTECTION <br />A. PROTECT COATINGS, FINISHES, AND CABINETS FROM DAMAGE AND DETERIORATION. <br />1. REPAIR DAMAGE TO GALVANIZED FINISHES WITH ZINC-RICH PAINT RECOMMENDED BY MANUFACTURER. <br />END OF SECTION 260533 <br />SECTION 260548.16 - SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS <br />PART 1 - GENERAL <br />1.1 SUMMARY <br />A. SECTION INCLUDES: <br />RESTRAINT CHANNEL BRACINGS. <br />RESTRAINT CABLES. <br />SEISMIC-RESTRAINT ACCESSORIES. <br />MECHANICAL ANCHOR BOLTS. <br /> 1.2 SUBMITTALS <br />A. PRODUCT DATA: FOR EACH TYPE OF PRODUCT. <br />ILLUSTRATE AND INDICATE STYLE, MATERIAL, STRENGTH, FASTENING PROVISION, AND FINISH FOR EACH TYPE AND SIZE OF SEISMIC-RESTRAINT COMPONENT USED. <br />TABULATE TYPES AND SIZES OF SEISMIC RESTRAINTS, COMPLETE WITH REPORT NUMBERS AND RATED STRENGTH IN TENSION AND SHEAR AS EVALUATED BY AN <br />AGENCY ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION. <br />ANNOTATE TO INDICATE APPLICATION OF EACH PRODUCT SUBMITTED AND COMPLIANCE WITH REQUIREMENTS. <br />B. DELEGATED-DESIGN SUBMITTAL: FOR EACH SEISMIC-RESTRAINT DEVICE. <br />INCLUDE DESIGN CALCULATIONS AND DETAILS FOR SELECTING SEISMIC RESTRAINTS COMPLYING WITH PERFORMANCE REQUIREMENTS, DESIGN CRITERIA, AND ANALYSIS <br />DATA SIGNED AND SEALED BY THE QUALIFIED PROFESSIONAL ENGINEER RESPONSIBLE FOR THEIR PREPARATION. <br />DESIGN CALCULATIONS: CALCULATE STATIC AND DYNAMIC LOADING CAUSED BY EQUIPMENT WEIGHT, OPERATION, AND SEISMIC FORCES REQUIRED TO SELECT SEISMIC <br />RESTRAINTS AND FOR DESIGNING VIBRATION ISOLATION BASES. <br />COORDINATE DESIGN CALCULATIONS WITH WIND LOAD CALCULATIONS REQUIRED FOR EQUIPMENT MOUNTED OUTDOORS. COMPLY WITH REQUIREMENTS IN <br />OTHER SECTIONS FOR EQUIPMENT MOUNTED OUTDOORS. <br />SEISMIC-RESTRAINT DETAILS: <br />DESIGN ANALYSIS: TO SUPPORT SELECTION AND ARRANGEMENT OF SEISMIC RESTRAINTS. INCLUDE CALCULATIONS OF COMBINED TENSILE AND SHEAR LOADS. <br />DETAILS: INDICATE FABRICATION AND ARRANGEMENT. DETAIL ATTACHMENTS OF RESTRAINTS TO THE RESTRAINED ITEMS AND TO THE STRUCTURE. SHOW <br />ATTACHMENT LOCATIONS, METHODS, AND SPACINGS. IDENTIFY COMPONENTS, LIST THEIR STRENGTHS, AND INDICATE DIRECTIONS AND VALUES OF FORCES <br />TRANSMITTED TO THE STRUCTURE DURING SEISMIC EVENTS. INDICATE ASSOCIATION WITH VIBRATION ISOLATION DEVICES. <br />COORDINATE SEISMIC-RESTRAINT AND VIBRATION ISOLATION DETAILS WITH WIND-RESTRAINT DETAILS REQUIRED FOR EQUIPMENT MOUNTED OUTDOORS. <br />COMPLY WITH REQUIREMENTS IN OTHER SECTIONS FOR EQUIPMENT MOUNTED OUTDOORS. <br />PREAPPROVAL AND EVALUATION DOCUMENTATION: BY AN AGENCY ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION, SHOWING MAXIMUM RATINGS OF <br />RESTRAINT ITEMS AND THE BASIS FOR APPROVAL (TESTS OR CALCULATIONS). <br />C. QUALIFICATION DATA: FOR PROFESSIONAL ENGINEER AND TESTING AGENCY. <br />1.3 QUALITY ASSURANCE <br />COMPLY WITH SEISMIC-RESTRAINT REQUIREMENTS IN THE IBC UNLESS REQUIREMENTS IN THIS SECTION ARE MORE STRINGENT. <br />WELDING QUALIFICATIONS: QUALIFY PROCEDURES AND PERSONNEL ACCORDING TO AWS D1.1/D1.1M, "STRUCTURAL WELDING CODE - STEEL." <br />SEISMIC-RESTRAINT DEVICES SHALL HAVE HORIZONTAL AND VERTICAL LOAD TESTING AND ANALYSIS. THEY SHALL BEAR ANCHORAGE PREAPPROVAL FROM OSHPD IN ADDITION TO <br />PREAPPROVAL, SHOWING MAXIMUM SEISMIC-RESTRAINT RATINGS, BY ICC-ES OR ANOTHER AGENCY ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION. RATINGS BASED ON <br />INDEPENDENT TESTING ARE PREFERRED TO RATINGS BASED ON CALCULATIONS. IF PREAPPROVED RATINGS ARE NOT AVAILABLE, SUBMITTALS BASED ON INDEPENDENT TESTING ARE <br />PREFERRED. CALCULATIONS (INCLUDING COMBINING SHEAR AND TENSILE LOADS) THAT SUPPORT SEISMIC-RESTRAINT DESIGNS MUST BE SIGNED AND SEALED BY A QUALIFIED <br />PROFESSIONAL ENGINEER. <br />COMPLY WITH NFPA 70. <br />PH: <br />RE <br />V <br />I <br />S <br />I <br />O <br />N <br />DA <br />T <br />E <br />2/ <br />1 <br />9 <br />/ <br />2 <br />5 <br />Ci <br />t <br />y <br /> <br />o <br />f <br /> <br />C <br />a <br />r <br />l <br />s <br />b <br />a <br />d <br /> <br />C <br />o <br />m <br />m <br />e <br />n <br />t <br />s <br />A <br />45 <br />0 <br /> <br />L <br />A <br />M <br />B <br />E <br />R <br />T <br /> <br />A <br />V <br />E <br />, <br /> <br />P <br />A <br />L <br />O <br /> <br />A <br />L <br />T <br />O <br />, <br /> <br />C <br />A <br /> <br />9 <br />4 <br />3 <br />0 <br />6 <br />(8 <br />8 <br />8 <br />) <br /> <br />3 <br />4 <br />2 <br />- <br />7 <br />3 <br />8 <br />3 <br />ORIGINAL SIZE 24"X36" <br />REV: <br />PROJ: <br />DL <br />X <br />8 <br /> <br />E <br />L <br />E <br />C <br />T <br />R <br />I <br />C <br /> <br />V <br />E <br />H <br />I <br />C <br />L <br />E <br /> <br />C <br />H <br />A <br />R <br />G <br />I <br />N <br />G <br /> <br />S <br />T <br />A <br />T <br />I <br />O <br />N <br />S <br />51 <br />5 <br /> <br />E <br />A <br />S <br />T <br /> <br />D <br />Y <br />E <br />R <br /> <br />R <br />O <br />A <br />D <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />7 <br />BSE14-2 <br />DLX8_EV_OSP <br />ALEXANDER SHORTS <br />PROFESSIONA L ENGINEER <br />ELECTRICALSTATE OF CALIFORNIA <br />E 21782 <br />7/ <br />1 <br />4 <br />/ <br />2 <br />5 <br />Ut <br />i <br />l <br />i <br />t <br />y <br /> <br />t <br />r <br />e <br />n <br />c <br />h <br /> <br />p <br />a <br />t <br />h <br />B <br />9/22/25 <br />SS <br />B <br />J <br /> <br />U <br />p <br />s <br />i <br />z <br />e <br />, <br /> <br />G <br />e <br />n <br />e <br />r <br />a <br />t <br />o <br />r <br /> <br />s <br />e <br />c <br />t <br />i <br />o <br />n <br />C <br />9/ <br />2 <br />2 <br />/ <br />2 <br />5 <br />ELECTRICAL <br />SPECIFICATIONS <br />E0.2 <br />IFP C